General information on the conduit in TCS audio systems  

 

The conduit is determined by structural conditions and is limited only by its length.  

 

  Observe when selecting the cable length: the 

loop resistance must  not exceed 20 

Ω (table)  

  To keep the max. permitted loop resistance, the 

cross-section of the wire can be doubled, that 
means, for one wire two lines are used (illustra-
tion). The lines must be twisted. 

  When using shielded lines: connect the shields 

with each other and connect one side to ground 
(b-wire) at the power supply. 

  optional strand or star formed wiring 

 

 

Table: loop resistances 

 

Line length

 in m 

Line diameter 

0.6 mm 

0.8 mm 

 

loop resistance

 

in Ω

 

10 

1.28 

0.71 

20 

2.55 

1.43 

30 

3.83 

2.14 

40 

5.10 

2.86 

50 

6.38 

3.57 

60 

7.65 

4.29 

70 

8.93 

5.00 

80 

10.20 

5.71 

90 

11.48 

6.43 

100 

12.76 

7.14 

150 

19.13 

10.71 

200 

25.51 

14.29 

250 

31.89 

17.86 

300 

38.27 

21.43 

 

Principle loop resistance 

  Measure loop resistance 

None of the devices (front-door station, indoor sta-
tion or extended function) should be further than 20 
Ohm away from the power supply and control 
unit(VS). 
 

 

  Switch off 230 V / 50 Hz of the power supply and 

control unit.  

  Install a-b short-circuit at the power supply and 

control unit.  

  Other devices are not disturbing the measure-

ment, they can stay connected. 

  Measure the resistance at a/b on the strand at the 

last indoor or front-door station. 

 

R/B    W/Y    W/G    W/Br   W|B/W  W/B 

Содержание ISH3022

Страница 1: ...TCS T rControlSysteme AG TCS Hotline Germany hotline tcsag de Subject to technical changes FAX 49 0 41 94 9 88 129 PI_ISH3022 uk Product information Door telephone ISH3022...

Страница 2: ...ended functions 7 Connect the lines 8 Connection lines 8 Wiring example 8 Connection diagram 2 wire technique 9 Connection diagram 3 wire technique 9 Note Replace an ISH1030 or TTS1 with an ISH3022 9...

Страница 3: ...ding to DIN VDE 0100 must be observed When installing TCS BUS systems the general safety regulations for telecommunication systems according to VDE 0800 must be observed separated conduit of heavy cur...

Страница 4: ...s put down if the light switch function is activated in the front door station Intended use The ISH3022 is an indoor station for duplex communication As door telephone it is suitable for the operation...

Страница 5: ...product information BVS100 NGV1011 3 strands 270 Short description large blue door release button ring tone volume can be adjusted continuously by a qualified electrician acoustic ring tone distinctio...

Страница 6: ...ews to the wall Connect the lines Minimise the length of the lines above the upper cover to place the lines without any problems and do not clamp the lines when snapping on the upper cover Connect the...

Страница 7: ...evice Insert a small screwdriver straight and with slight pressure into this opening The upper cover can be removed at the underside 1 Lift the upper cover out of the two upper adjustment increments 2...

Страница 8: ...t the lines Connection lines acceptable cross section diameter 0 08 0 82 mm2 0 32 1 0 mm max number of wires per terminal contact each 2 x 0 8 mm 3 x 0 6 mm Further wires have to be connected with aux...

Страница 9: ...tion both telephones must be replaced with an ISH3022 Commissioning Install the devices of the system voltage free and completely Check the a b and P wire against each other for short circuits Switch...

Страница 10: ...sion 1 3 3 ring tone volume x parallel allocation x x reload to factory setting x Programming with the Service Device TCSK 01 The indoor station is acting as a telephone Use the commands 8 for configu...

Страница 11: ...wer supply optional strand or star formed wiring Table loop resistances Line length in m Line diameter 0 6 mm 0 8 mm loop resistance in 10 1 28 0 71 20 2 55 1 43 30 3 83 2 14 40 5 10 2 86 50 6 38 3 57...

Страница 12: ...0 2 mA I P 0 2 mA max input current I Pmax 60 mA Repair Replace the indoor station program bell buttons Basic principle All devices at the TCS BUS have a unique serial number Programming a bell butto...

Страница 13: ...d shortly press LED is on programming mode of the system is switched off a Not necessary if the bell buttons have not been programmed comp product information of the front door station 1 If there soun...

Страница 14: ...mbol shows that the device has to be disposed separately from domestic waste The materials used are recyclable Please do help protecting our environment and dispose the device via a collection point f...

Страница 15: ...11 2012 15 TCS T rControlSysteme AG TCS Hotline Germany hotline tcsag de Subject to technical changes FAX 49 0 41 94 9 88 129 PI_ISH3022 uk...

Страница 16: ...de Subject to technical changes FAX 49 0 41 94 9 88 129 PI_ISH3022 uk Service Please send your questions and inquiries to hotline tcsag de Headquarters TCS T rControlSysteme AG Geschwister Scholl Str...

Отзывы: