background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

6

the 100ths decimal point (X.XX). The display on the 
SZ1145 would then read 0.00 to 1.00.  The scaling is 
still 0 to 100 internal to the SZ1145.

Each input (AI1 & AI2) can be enabled to generate an 
alarm. Once enabled, you need to set a "High Limit" and 
a "Low Limit" (in units), and a "Hysteresis" (in percent of 
input span). For example, if your input was -40 to 160°F 
and you put in a hysteresis of 5%, the actual hysteresis 
would be 10°F because of the 200°F span. When the 
temperature reaches the High or Low limit, an alarm is 
generated. The alarm is automatically cleared when the 
temperature falls from the High Limit by the amount of 
the Hysteresis (for a High Alarm Condition) or when the 
temperature rises from the Low Limit by the amount of 
the Hysteresis (for a Low Alarm Condition).

Note:

 If a High Limit is set to the maximum span setting, 

it is disabled.  If a Low Limit is set to the minimum span 
setting, it is also disabled.

ALARM DELAY WAIT TIME

There is an Alarm Delay Wait Time which, when set, 
applied to all analog inputs (TEMP1-4 and AI1&2). If no 
delay is desired, set the delay time to 0 minutes and 
0 seconds. When this is done, an alarm is generated 
(or released) immediately when the input reaches the 
appropriate setting. If a delay time other than 0 minutes 
and 0 seconds, the SZ1145 makes sure that the analog 
input has been at the appropriate setting for that amount 
of time before generating (or releasing) an alarm. 

Note:

  The time set for the Alarm Delay Wait Time is 

used for all analog inputs that are set to generate an 
alarm.

DIGITAL INPUT MODES

Digital Input One (DI1) can be configured to use 
one of 3 modes (MONITOR, ALARM or TOGGLE 
MOMENTARY).

Digital Input Two (DI2) can be configured to use one of 
2 modes (MONITOR or ALARM).

DIGITAL INPUT MONITOR MODE

When a digital input is selected to be in MONITOR 
mode, the SZ1145 just monitors that input. No control 
action is taken. Open refers to the input as being "Open" 
or "Off", and closed refers to the input as being "Closed" 
or "On".

DIGITAL INPUT ALARM MODE

When a digital input is selected to be in ALARM mode, 
you need to select whether the "Alarm Condition" will 
occur when the digital input is "Open" or "Closed". The 
SZ1145 monitors the input. When the input "Opens" or 
"Closes", based on your selection, an "Alarm Condition" 
is generated. Open refers to the input as being "Open" 
or "Off", and closed refers to the input as being "Closed" 
or "On".

15 SECOND DI DELAY

If either of the two digital inputs are selected to use 
"Alarm" mode, then you will be given a choice of 
whether to enable a 15 second digital input delay. If not 
enabled, an alarm is generated (or released) imme-
diately upon a change of status for the digital input. If 
enabled, the SZ1145 makes sure that the digital input 
has been present for 15 seconds before generating (or 
releasing) an alarm. 

Note:

  If the 15 Second DI Delay is enabled, it is 

enabled for all digital inputs that are set to ALARM 
mode.

DI1 TOGGLE MOMENTARY MODE

Digital input one can be set for "Toggle Momentary" 
mode. In this mode, momentarily closing DI1 will acti-
vate an "Override" condition where all new alarms will 
be suspended. There is an "Override Time" to set which 
is adjustable from 0 to 255 minutes.

ALARM OUTPUT

Whenever an input of the SZ1145 is in an alarm condi-
tion, based on its settings, the SZ1145 will indicate the 
alarm from its display and through communications. In 
addition to this, the SZ1145 has a relay output which 
can be programmed to indicate an alarm. It can be set 
to be N.O. (normally open) or N.C. (normally closed) 
when an alarm occurs, or it can be disabled.

AUTOMATIC ALARM TIME-OUT

If the relay output is enabled, meaning set to normally 
open or closed, then you may enable an automatic 
alarm time-out feature by choosing "Yes" in the "Allow 
Alarm Time-Out" menu. If "Yes" is chosen, then you 
need to enter a time adjustable from 0 to 255 seconds, 
after which the relay output will revert back to its "Non-
Alarm" state. This is useful if an audible horn is attached 
to the relay output. The horn can indicate the alarm con-
dition and then automatically time out without having to 
have someone go through the programming menus to 
disable the alarm.

Checkout & Troubleshooting       

CHECKOUT

You may verify the status of the alarm status, relay out-
put and all of the inputs in the monitoring screens, which 
are accessed by pressing the "Scroll" key.

1. Verify all wiring prior to powering the controller.

2. Turn power on. The controller will display a momen-

tary screen with the model and version number, and 
then the main monitoring screen. The "Alarm LED" 
will blink for 15 seconds. During this time no alarms 
will be generated. This time gives the circuit time to 
stabilize and prevents false alarm conditions immedi-
ately after a power outage.

Содержание SZ1145

Страница 1: ...F 6 7 to 48 9 C are suitable for monitoring temperatures in this range If any of these inputs exceed their high or low limits the alarm output relay is energized Features Stand alone or network opera...

Страница 2: ...ity sensing TS TX Series for temperature sensing TD TL Series for dif ferential air sensing The SZ1145 also accepts four two wire remote temperature sensors for general pur pose temperature monitoring...

Страница 3: ...on Temp2 Alarm Low Limit Screen Enter a low limit temperature setting When the Temp2 input temperature falls to this value an alarm will be generated This screen is not shown if the Temp2 alarm is not...

Страница 4: ...his screen is not shown if the AI1 alarm is not enabled AI1 Alarm High Limit Screen Enter a high limit value When the AI1 input rises to this value an alarm will be gen erated This screen is not shown...

Страница 5: ...the amount of time that an analog alarm condition Temp1 4 AI1 2 must be pres ent before actually generating the alarm The time is adjustable in 15 second incre ments from 0 minutes and 0 seconds to 6...

Страница 6: ...oses based on your selection an Alarm Condition is generated Open refers to the input as being Open or Off and closed refers to the input as being Closed or On 15 SECOND DI DELAY If either of the two...

Страница 7: ...the wires or terminal block from ter minals NO to COM Measure W from terminals NO to COM If the reading is 0W the mechanical relay is defective R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 6...

Страница 8: ...us Screen Shows the DI1 and DI2 status Alarm Relay Status Screen Shows alarm relay output status Override Status Screen Shows whether the override is active and if so how many minutes remaining This s...

Отзывы: