4

Temp3 Alarm High Limit Screen. 

Enter 

a high limit temperature setting. When 
the Temp3 input temperature rises to 
this value, an alarm will be generated. 
(This screen is not shown if the Temp3 
alarm is not enabled.)

 

 

 

 

Temp3 Alarm Hysteresis Screen. 

Enter the number of degrees that the 
temperature must fall (for a high alarm) 
or must rise (for a low alarm) before an 
existing alarm condition for the Temp3 
input will be automatically cleared. (This 
screen is not shown if the Temp3 alarm 
is not enabled.)

 

 

Enable Temp4 Alarm Screen. 

Choose 

whether or not to enable the Temp4 
input alarm function.

 

 

 

 

Temp4 Alarm Low Limit Screen. 

Enter 

a low limit temperature setting. When 
the Temp4 input temperature falls to this 
value, an alarm will be generated. (This 
screen is not shown if the Temp4 alarm 
is not enabled.)

Temp4 Alarm High Limit Screen. 

Enter 

a high limit temperature setting. When 
the Temp4 input temperature rises to 
this value, an alarm will be generated. 
(This screen is not shown if the Temp4 
alarm is not enabled.)

 

 

 

 

Temp4 Alarm Hysteresis Screen. 

Enter the number of degrees that the 
temperature must fall (for a high alarm) 
or must rise (for a low alarm) before an 
existing alarm condition for the Temp4 
input will be automatically cleared. (This 
screen is not shown if the Temp4 alarm 
is not enabled.)

AI1 Low Limit Span Screen. 

Enter the 

lowest value of the span range of the 
transmitter connected to AI1 (i.e., value 
at 4mA).

AI1 High Limit Span Screen. 

Enter the 

highest value of the span range of the 
transmitter connected to AI1 (i.e., value 
at 20mA).

AI1 Decimal Point Screen. 

For display 

purposes, the SZ1145 allows a decimal 
point to be turned on. No scaling is 
done. Select NONE for no decimal point, 
XX.X for a decimal point in the tenths 
position, X.XX for a decimal point in the 
hundredth position or .XXX for a decimal 
point in the thousandths position.

Enable AI1 Alarm Screen

. Choose 

whether or not to enable the AI1 input 
alarm function. 

 

 

AI1 Alarm Low Limit Screen. 

Enter a 

low limit value. When the AI1 input falls 
to this value, an alarm will be generated. 
(This screen is not shown if the AI1 
alarm is not enabled.)

 

 

 

 

AI1 Alarm High Limit Screen. 

Enter 

a high limit value. When the AI1 input 
rises to this value, an alarm will be gen-
erated. (This screen is not shown if the 
AI1 alarm is not enabled.) 

 

 

 

 

 

 

 

 

 

AI1 Alarm Hysteresis Screen. 

Enter 

the number of units that the input must 
fall (for a high alarm) or must rise (for a 
low alarm) before an existing alarm con-
dition for the AI1 input will be automati-
cally cleared. (This screen is not shown 
if the AI1 alarm is not enabled.)   
 

 

 

 

AI2 Low Limit Span Screen. 

Enter the 

lowest value of the span range of the 
transmitter connected to AI2 (i.e., value 
at 4mA).

 

 

 

 

AI2 High Limit Span Screen. 

Enter the 

highest value of the span range of the 
transmitter connected to AI2 (i.e., value 
at 20mA).

 

 

 

 

 

 

 

 

AI2 Decimal Point Screen. 

For display 

purposes, the SZ1145 allows a deci-
mal point to be turned on. No scaling 
is done. Select NONE for no decimal 
point, XX.X for a decimal point in the 
tenths position, X.XX for a decimal point 
in the hundredth position or .XXX for a 
decimal point in the thousandths posi-
tion. 

   

 

 

 

 

Enable AI2 Alarm Screen. 

Choose 

whether or not to enable the AI2 input 
alarm function.

 

 

 

 

 

 

 

 

 

 

 

 

AI2 Alarm Low Limit Screen. 

Enter a 

low limit value. When the AI2 input falls 
to this value, an alarm will be generated. 
(This screen is not shown if the AI2 
alarm is not enabled.) 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI2 Alarm High Limit Screen. 

Enter 

a high limit value. When the AI2 input 
rises to this value, an alarm will be gen-
erated. (This screen is not shown if the 
AI2 alarm is not enabled.)

 

 

 

 

 

 

 

 

AI2 Alarm Hysteresis Screen. 

Enter 

the number of units that the input must 
fall (for a high alarm) or must rise (for a 
low alarm) before an existing alarm con-
dition for the AI2 input will be automati-
cally cleared. (This screen is not shown 
if the AI2 alarm is not enabled.)

TEMP3 ALARM HIGH

LIMIT: 100F

15.

TEMP3 ALARM 

HYSTERESIS 03F

16.

ENABLE TEMP4

ALARM? NO

17.

TEMP 4 ALARM LOW

LIMIT: 60F

18.

TEMP 4 ALARM HIGH

LIMIT: 100F

19.

TEMP4 ALARM 

HYSTERESIS 03F

20.

AI1SPAN LOW

LIMIT: 000

21.

AI1SPAN HIGH

LIMIT: 100

22.

SET AI1 DECIMAL

POINT: NONE

23.

ENABLE AI1

ALARM? NO

24.

AI1 ALARM LOW

LIMIT: 025

25.

AI1 ALARM HIGH

LIMIT: 075

26.

AI1 ALARM

HYSTERESIS 005%

27.

AI2 SPAN LOW

LIMIT: 000

28.

AI1 SPAN HIGH

LIMIT: 100

29.

SET AI2 DECIMAL 

POINT: NONE

30.

ENABLE AI2

ALARM? NO

31.

AI2 ALARM LOW

LIMIT: 025

32.

AI2 ALARM HIGH

LIMIT: 075

33.

AI2 ALARM

HYSTERESIS: 005%

34.

Содержание SZ1145

Страница 1: ...F 6 7 to 48 9 C are suitable for monitoring temperatures in this range If any of these inputs exceed their high or low limits the alarm output relay is energized Features Stand alone or network opera...

Страница 2: ...ity sensing TS TX Series for temperature sensing TD TL Series for dif ferential air sensing The SZ1145 also accepts four two wire remote temperature sensors for general pur pose temperature monitoring...

Страница 3: ...on Temp2 Alarm Low Limit Screen Enter a low limit temperature setting When the Temp2 input temperature falls to this value an alarm will be generated This screen is not shown if the Temp2 alarm is not...

Страница 4: ...his screen is not shown if the AI1 alarm is not enabled AI1 Alarm High Limit Screen Enter a high limit value When the AI1 input rises to this value an alarm will be gen erated This screen is not shown...

Страница 5: ...the amount of time that an analog alarm condition Temp1 4 AI1 2 must be pres ent before actually generating the alarm The time is adjustable in 15 second incre ments from 0 minutes and 0 seconds to 6...

Страница 6: ...oses based on your selection an Alarm Condition is generated Open refers to the input as being Open or Off and closed refers to the input as being Closed or On 15 SECOND DI DELAY If either of the two...

Страница 7: ...the wires or terminal block from ter minals NO to COM Measure W from terminals NO to COM If the reading is 0W the mechanical relay is defective R 2800 LAURA LANE MIDDLETON WI 53562 800 288 9383 FAX 6...

Страница 8: ...us Screen Shows the DI1 and DI2 status Alarm Relay Status Screen Shows alarm relay output status Override Status Screen Shows whether the override is active and if so how many minutes remaining This s...

Отзывы: