SZ1063/SZ1064

Modulating Fan Coil Thermostats

Product Manual           

Description                                        

The SZ1064 is a microprocessor based programmable modulating 

fan coil thermostat and the SZ1063 is a non-programmable modulat-

ing fan coil thermostat.

Features                                            

•  Stand-alone or network operation 

•  No battery backup required

•  Minimum on/off times for HVAC equipment protection

•  32-character LCD display

•  Six status LEDs 

•  Remote room sensing capability

•  User setpoint adjustment limits

•  Three speed fan

•  System and fan switching with access lockouts

•  External input for setback or aquastat changeover

•  Access to programming may be locked out or limited with the use 

of an access code

•  Fahrenheit or Celsius temperature display

•  Control for two or four pipe systems

•  7-day programmable time clock

•  Optional pipe sensor inputs for changeover (SZ1064 only)

•  Adjustable delay on start-up and power-up for soft starts

•  Smart recovery (SZ1064 only)

•  Local and remote override capability

•  External time clock and override options

•  Auxiliary output for heat, cool or time clock (SZ1064 only)

Contents                                            

Description

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Features

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Mounting 

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1

Wiring

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

Setup

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Programming

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Sequence of Operation

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Checkout & Troubleshooting

  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

LED Description

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10

Mounting                                          

The SZ1063 and 64 are designed for wall mounting using two #6 

sheet metal screws, either over a horizontally installed 2" x 4" junc-

tion box, or directly to block or drywall.
For best results, the thermostat should be mounted on an interior 

wall which reflects normal room environment, at a height of approxi-

mately five feet from the floor. Avoid areas exposed to direct sunlight, 

unusual heat or cool sources, open doors and windows, unventilated 

locations and hot or cold air from diffusers.
If using a remote room sensor, it should be mounted in the manner 

described above.The thermostat may then be mounted in an area 

which is accessible for adjusting its settings.

Caution:  Remove power from thermostat prior to mounting.

        Communicating Thermostats

        Communicating Thermostats

Содержание SZ1063

Страница 1: ...rt up and power up for soft starts Smart recovery SZ1064 only Local and remote override capability External time clock and override options Auxiliary output for heat cool or time clock SZ1064 only Contents Description 1 Features 1 Mounting 1 Wiring 2 Setup 3 Programming 3 Sequence of Operation 3 Checkout Troubleshooting 9 LED Description 10 Mounting The SZ1063 and 64 are designed for wall mounting...

Страница 2: ...on return paths When the Superstat is used as a stand alone thermostat without communications the unit transformer may be used to power it To do this install a jumper between the R and 24 terminals The 24 terminal must then be connected to the common side of the unit transformer Black 1 For communication wiring use twisted shielded 18 AWG Must be run separately 2 Dry momentary contct Must not be p...

Страница 3: ...oftware manual Programming through the keypad To access the programming screens press the program setup button Screens A thru F are monitoring screens and programming screens begin with 1 Access may be locked out with dipswitches or an access code may be required program setup ENTER ACCESS 000 CODE 9 OVERRIDE ON 178 MINUTES F program setup MOD OUT 1 00 MOD OUT 2 00 E program setup program setup PI...

Страница 4: ...up to two occupied periods SZ1064 only Schedule Announcement Screen Announces the next screen SZ1064 only Copy Schedule Screen Choose to use the same schedule that was used for the previous day If so the next screen does not appear SZ1064 only Occupied Times Screen Set the hours and minutes of start and end times for up to two occupied periods SZ1064 only Occupied Times Screen Set the hours and mi...

Страница 5: ... Fan Coil Enable Screen Choose YES if using a two pipe system Otherwise choose NO If NO is selected and skip to step 42 and it is assumed to be a four pipe system Digital Aquastat Input Screen Choose whether DI1 will be normally open N O or normally closed N C for cooling The next screen is skipped Analog Aquastat Input Screen If an analog aqua stat is selected choose the changeover setpoint to di...

Страница 6: ...erride or Continuous Unoccupied Override is enabled then pressing the override once and then pressing and holding it for 5 seconds puts the thermostat into a hold mode the override LED on the thermostat will flash quickly In this mode the override setpoints are used until the next occupied period is reached or until the thermostat is manually taken out of the Continuous Override mode by pressing t...

Страница 7: ...n there is no need for heating or cooling As there becomes a need for heating or cool ing the analog output modulates toward 4mA or 20mA depending on whether analog output two is direct or reverse acting FOUR PIPE FAN COIL OPERATION For four pipe fan coil operation in step 28 select NO In step 29 select NO Four pipe fan coil operation assumes that there are two water sourc es available hot and col...

Страница 8: ...ow the day or time 2 Turn power on The thermostat will display a momentary screen with the model number and then the main monitoring screen with the time day fan speed and current temperature 3 Press the PROGRAM SETUP button until you reach screen 13 and set the System Mode to AUTO Continue on until you reach screen 14 and set the Occupied Fan Mode to AUTO Go to screen 22 which allows you to set t...

Страница 9: ...and tunoccupied fan mode in programming If the Fan Status is OFF press the Low Medium or High button If the fan is off but the fan LED is on check wiring Short terminals R to GL GM or GH and see if the fan comes on This is a check for a mechanical relay failure Heating or Cooling Does Not Come On Heating is on whenever the heating LED is on and cooling is on whenever the cooling LED is on If heati...

Страница 10: ...ability to put the unit into occupied mode by pressing the override button on the front By factory default the unit will remain in the occupied mode for 180 minutes This value may be changed from 0 to 255 minutes in programming step 23 Setting Clock Schedule The ability to set the clock and schedule is allowed by factory default An access code may be required as set in programming step 49 Programm...

Отзывы: