COOL STAGE 3
DIFF:
program
setup
ENABLE DISCHARGE
AIR SENSOR?
SET CONTROL
MODE:
DISCHARGE AIR
LOW LIMIT:
TIMECLOCK OUTPUT
OCCUPIED=CLOSED
DISCHARGE AIR
HIGH LIMIT:
ENABLE OUTDOOR
AIR SENSOR?
COOLING LOCKOUT
TEMP:
HEATING LOCKOUT
TEMP:
1F
P+I
YES
45F
120F
YES
65F
70F
Cool Stage 3 or Stage 4 Differential
Screen.
Enter a differential value for
cool stage 3 or stage 4. This screen only
appears if this stage is activated. (Only
shown on SZ1035.)
Control Mode Screen.
Enter if you
want to control by temperature only (P)
or add a time factor (P+I).
Time Clock Output Screen.
Choose
whether the auxiliary output will be
OPEN during occupied periods (and
closed during unoccupied periods) or
CLOSED during occupied periods (and
open during unoccupied periods). (Not
shown on SZ1009.)
Discharge Air Sensor Function
Screen.
Choose whether or not you are
using a discharge air sensor function. To
monitor only, select NO. See setup
instructions for dipswitch settings which
must also be set.
Discharge Air Low Limit Screen.
Enter a discharge air low limit value.
This screen will not appear if the dis-
charge air sensor function is disabled.
Discharge Air High Limit Screen.
Enter a discharge air high limit value.
This screen will not appear if the dis-
charge air sensor function is disabled.
Outdoor Air Sensor Function Screen.
Choose whether or not you are using an
outdoor air sensor function. To monitor
only, select NO. See setup instructions
for dipswitch settings which must also be
set. (Not shown on SZ1022.)
Cooling Lockout Screen.
Enter an out-
door air cooling lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled. (Not
shown on SZ1022.)
Heating Lockout Screen.
Enter an out-
door air heating lockout temperature.
This screen will not appear if the outdoor
air sensor function is disabled. (Not
shown on SZ1022.)
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
program
setup
MON
72F
12:00 AM
11-19-01
47.
46.
45.
44.
43.
42.
41.
SET DI2 SETPOINT
SHIFT:
program
setup
48.
program
setup
49.
SET ACCESS
CODE:
000
REQUIRE CODE FOR
CLOCK/SCHED?
YES
REQUIRE CODE FOR
PROGRAMMING?
YES
ENABLE SMART
YES
RECOVERY?
DELAY ON POWERUP
10 SECONDS
DI3 USED FOR:
FILTER SERVICE
DI2 USED FOR:
SERVICE
DI1 USED FOR:
MONITOR
00F
DI1 Choice Screen.
Choose DI1 as
FAN PROVING or a MONITOR point.
Select MONITOR if unused.
DI2 Choice Screen.
Choose DI2 as
SERVICE, COOL LOCKOUT, or MONI-
TOR. Select MONITOR if unused.
DI2 Shift Screen.
Enter the setpoint
shift value. This screen will only appear
if DI2 is set to MONITOR.
DI3 Choice Screen.
Choose FILTER
SERVICE, EXTernal OVERRIDE, or
EXTernal TIME CLOCK. Select
EXTernal OVERRIDE if unused.
Delay On Powerup Screen.
Enter a
value in seconds, such that when the
unit is powered up, all outputs are
delayed for this time period before they
are allowed to close.
Smart Recovery Screen.
Choose
whether or not smart recovery will be
used.
Note: Smart Recovery is not
available when DI3 is used as EXTernal
TIME CLOCK.
Programming Access Screen.
Choose whether or not a code will be
required to enter programming setup. A
dipswitch option to lock out access alto-
gether is also available.
Clock and Schedule Access Screen.
Choose whether or not a code will be
required to enter clock and schedule
setup. A dipswitch option to lock out
access altogether is also available.
Access Code Screen.
Enter an
access (0 to 255) code that will be used
to enter the programming and/or clock
and schedule setups if access code has
been required in the last two steps.
The default is 248.
Main Monitoring Screen.
(Date not
shown on SZ1009 or SZ1022.)