6

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

40.

39.

38.

37.

36.

35.

34.

33.

32.

COOL STAGE 3
DIFF:

program

setup

ENABLE DISCHARGE

AIR SENSOR?

SET CONTROL

MODE:

DISCHARGE AIR
LOW LIMIT:

TIMECLOCK OUTPUT

OCCUPIED=CLOSED

DISCHARGE AIR

HIGH LIMIT:

ENABLE OUTDOOR

AIR SENSOR?

COOLING LOCKOUT
TEMP:

HEATING LOCKOUT
TEMP:

1F

P+I

YES

45F

120F

YES

65F

70F

Cool Stage 3 or Stage 4 Differential

Screen.  

Enter a differential value for

cool stage 3 or stage 4. This screen only

appears if this stage is activated. (Only

shown on SZ1035.)

Control Mode Screen.  

Enter if you

want to control by temperature only (P)

or add a time factor (P+I).

Time Clock Output Screen.  

Choose

whether the auxiliary output will be

OPEN during occupied periods (and

closed during unoccupied periods) or

CLOSED during occupied periods (and

open during unoccupied periods).  (Not

shown on SZ1009.)

Discharge Air Sensor Function

Screen.  

Choose whether or not you are

using a discharge air sensor function. To

monitor only, select NO. See setup

instructions for dipswitch settings which

must also be set.  

Discharge Air Low Limit Screen.  

Enter a discharge air low limit value.

This screen will not appear if the dis-

charge air sensor function is disabled. 

Discharge Air High Limit Screen.

Enter a discharge air high limit value.

This screen will not appear if the dis-

charge air sensor function is disabled.  

Outdoor Air Sensor Function Screen.

Choose whether or not you are using an

outdoor air sensor function.  To monitor

only, select NO. See setup instructions

for dipswitch settings which must also be

set.  (Not shown on SZ1022.)

Cooling Lockout Screen.  

Enter an out-

door air cooling lockout temperature.

This screen will not appear if the outdoor

air sensor function is disabled. (Not

shown on SZ1022.)

Heating Lockout Screen.  

Enter an out-

door air heating lockout temperature.

This screen will not appear if the outdoor

air sensor function is disabled. (Not

shown on SZ1022.)

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

program

setup

MON

72F

12:00 AM

11-19-01

47.

46.

45.

44.

43.

42.

41.

SET DI2 SETPOINT

SHIFT:

program

setup

48.

program

setup

49.

SET ACCESS

CODE:

000

REQUIRE CODE FOR

CLOCK/SCHED?

YES

REQUIRE CODE FOR

PROGRAMMING?

YES

ENABLE SMART

YES

RECOVERY?

DELAY ON POWERUP

10 SECONDS

DI3 USED FOR:

FILTER SERVICE

DI2 USED FOR:

SERVICE

DI1 USED FOR:

MONITOR

00F

DI1 Choice Screen.  

Choose DI1 as

FAN PROVING or a MONITOR point.

Select MONITOR if unused. 

DI2 Choice  Screen.  

Choose DI2 as

SERVICE, COOL LOCKOUT, or MONI-

TOR.  Select MONITOR if unused.  

DI2 Shift Screen.  

Enter the setpoint

shift value.  This screen will only appear

if DI2 is set to MONITOR.  

DI3 Choice Screen.  

Choose FILTER

SERVICE, EXTernal OVERRIDE, or

EXTernal TIME CLOCK.  Select

EXTernal OVERRIDE if unused.  

Delay On Powerup  Screen.  

Enter a

value in seconds, such that when the

unit is powered up, all outputs are

delayed for this time period before they

are allowed to close.  

Smart Recovery Screen.  

Choose

whether or not smart recovery will be

used.  

Note: Smart Recovery is not

available when DI3 is used as EXTernal

TIME CLOCK.  

Programming Access  Screen.

Choose whether or not a code will be

required to enter programming setup.  A

dipswitch option to lock out access alto-

gether is also available.  

Clock and  Schedule Access  Screen.

Choose whether or not a code will be

required to enter clock and schedule

setup.  A dipswitch option to lock out

access altogether is also available.  

Access Code  Screen.  

Enter an

access (0 to 255) code that will be used

to enter the programming and/or clock

and schedule setups if access code has

been required in the last two steps.

The default is 248.  

Main Monitoring Screen.  

(Date not

shown on SZ1009 or SZ1022.)

Содержание SZ1009

Страница 1: ...quipment monitoring inputs and indication z External time clock input z Access to programming or schedule may be locked out or limited with the use of an access code z Fahrenheit or Celsius temperatur...

Страница 2: ...t the sensor mounting location Sensor wiring runs of up to 250 feet are attainable if properly shielded wire is used and the installation environment is free of electrical noise Sensor wire should be...

Страница 3: ...r sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1009 SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order...

Страница 4: ...ique address from 0 to 255 excluding 248 All con trollers on a network must have a sepa rate and unique communications address program setup program setup program setup program setup program setup pro...

Страница 5: ...if not using a third stage of heat or cool Not shown on SZ1009 or SZ1035 Heat Stage 1 Offset Screen Enter an offset value for heat stage 1 First stage is normally 0 offset Not shown on SZ1009 program...

Страница 6: ...will not appear if the outdoor air sensor function is disabled Not shown on SZ1022 Heating Lockout Screen Enter an out door air heating lockout temperature This screen will not appear if the outdoor...

Страница 7: ...TUESDAY The following screens are repeated for Wednesday Thursday Friday Saturday Sunday Holiday 1 2 COPY MON FOR TUE 7 ENTER DATES FOR HOLIDAY 1 DAYLIGHT HOL1 01 01 01 10 11 12 13 DURATION 00 DAYS S...

Страница 8: ...s meetings another option is to set the DI3 to external override and use the timed override button to put the unit in occupied mode To make the unit always occupied set DI3 to external time clock and...

Страница 9: ...ws unused stages to be set to activate physical alarms if desired In summary unlike most other multi stage programmable thermostats the Superstat allows independent adjustments of offsets and differen...

Страница 10: ...xt stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZ1009 SZ1022 SZ1031 and SZ1035 have an adjustable delay on power u...

Страница 11: ...g Temperature Display If any of the temperatures is reading slightly high or low there are three adjustment pots located in the cover to adjust them T1 is for the room temperature T2 is for the discha...

Страница 12: ...er We recommend the installer fill out the appropriate pages in the User s Guide and explain to the user how the thermostat operates what settings may be changed and how the time clock schedules are u...

Отзывы: