background image

R

2800 LAURA LANE 

l

MIDDLETON, WI 53562 

l

(800) 288-9383 

l

FAX (608) 836-9044 

l

www.tcs-basys.com

10

P + I OPTION 

The SZ1009, SZ1022, SZ1031 and SZ1035 also have a P+I

option. Without enabling this option, stages turn on and off

based on temperature vs. setpoint alone, as described above.

By enabling this option, you allow a time factor to be added.

This is useful when you are forced to have a large differential

due to equipment size. At times when the building load is low,

the temperature could potentially sit a few degrees off setpoint

for some time. With the time factor added, the thermostat

would compensate for this, turning on the equipment even

though the temperature had not reached the limits described

above. 

DI2 COOL LOCKOUT

DI2 may be set as cool lockout for operation with economiz-

ers. An outdoor temperature switch may be wired in such that

when DI2 is closed, the second stage of cooling is disabled.

SMART RECOVERY 

“Smart Recovery” may be enabled to insure occupant comfort

while saving money. It takes the building load into considera-

tion and ramps the setpoint when going from the unoccupied

mode to the occupied mode. At the beginning of the occupied

mode, the occupied setpoint will be reached, many times with-

out the need for the second stage to come on. This feature is

automatically disabled when DI3 is set to external time clock.

AUXILIARY OUTPUT 

An auxiliary relay output is available to output a signal based

on the occupancy status. It is commonly used with an econo-

mizer minimum position control, or to signal an outdoor air

damper to open in occupied times in lieu of an economizer. It

may also be used for lighting or hot water heaters. Keep in

mind that although it is an isolated relay (separate common

terminal), it is rated at 24 VAC. For loads that exceed this, use

an external relay. It may be set to be open (NO) or closed

(NC) when the thermostat is operating in the occupied mode,

and will be the opposite during the unoccupied mode. 

BUILT-IN DELAYS 

The SZ1009, SZ1022, SZ1031 and SZ1035 have delays built

into the programming sequences to protect equipment. The fan

has a minimum on and off time of 30 seconds. When the fan

is in AUTO mode, it will come on 30 seconds before the heat-

ing or cooling stages are allowed to sequence on, and remain

on for 2 minutes after the heating or cooling stages sequence

off. Each stage has a minimum on and off time of two min-

utes. There is a minimum of two minutes between when one

stage turns on until the next stage is allowed to turn on, as

well as when one stage turns off until the next stage is allowed

to turn off. 

DELAY ON POWER UP 

The SZ1009, SZ1022, SZ1031 and SZ1035 have an adjustable

delay on power up. When several thermostats are used at one

location, and the power goes out, most thermostats turn all of

the units back on at the same time on regain of power, creating

a peak. The thermostat allows you to set a value, in seconds,

where no outputs are allowed to turn on for that length of time

on power up. Setting each unit to a different delay allows you

to soft start your system, and thus prevent this peak.

Checkout & Troubleshooting

CHECKOUT

Note: 

The fan has a minimum on and off time of 30 seconds.

The heating and cooling stages have a minimum on and off

time of 2 minutes. 

You may verify the status of heating and cooling stages and

fan in monitoring screens #5, #6, and #7, which are accessed

by pressing the SERVICE STATUS button. 

1.  Verify all wiring prior to powering the thermostat.

2. Turn power on.  The thermostat will display a momentary

screen with the model number , and then the main monitor-

ing screen with the time, day, date (SZ1031 and SZ1035

only), and current temperature. 

3. Press the PROGRAM SETUP button until you reach the

screen #14 which allows you to set the occupant setpoint

adjustment limits.  Change this to +/-20 °F (11.1 °C).  Press

the PROGRAM SETUP button once more to store the

change.  Then press the SERVICE STATUS button once to

exit the programming. 

4. Press the FAN SWITCH button to access the fan mode and

change the mode to AUTO.  Press the FAN SWITCH but-

ton once more to store the change.   Press the SYSTEM

SWITCH button to access the system mode and change the

mode to AUTO.  Press the SYSTEM SWITCH button once

more to store the change.  

5. Verify that the thermostat is operating in the occupied mode

by making sure that the top LED is lit.  If not, press the

OVERRIDE button.  The LED should light up. 

6. Take note of the current temperature reading.  Press the

WARMER (up) button.  The setpoint adjustment screen

should now be showing.  Press the WARMER button until

the heating setpoint is greater than the current temperature

by at least five degrees.  The fan will come on.  The heat-

ing stage(s) will sequence on after 30 seconds. 

7. Press the cooler (down) button until the heating setpoint is

one degree less than the current temperature.  The heating

stage(s) will sequence off.  The fan will turn off 2 minutes

after the last heating stage. 

8. Press the cooler button until the cooling setpoint is less than

the current temperature by at least five degrees.  The fan

will come on.   The cooling stage(s) will sequence on after

30 seconds. 

MON

TCS                        V1.0

11-19-01

12:00AM

72F

Содержание SZ1009

Страница 1: ...quipment monitoring inputs and indication z External time clock input z Access to programming or schedule may be locked out or limited with the use of an access code z Fahrenheit or Celsius temperatur...

Страница 2: ...t the sensor mounting location Sensor wiring runs of up to 250 feet are attainable if properly shielded wire is used and the installation environment is free of electrical noise Sensor wire should be...

Страница 3: ...r sensor only Using remote room sensor with both discharge and outdoor air sensors SZ1009 SZ1031 and SZ1035 only KEYPAD ACCESS The dipswitches in the thermostat cover shown above must be set in order...

Страница 4: ...ique address from 0 to 255 excluding 248 All con trollers on a network must have a sepa rate and unique communications address program setup program setup program setup program setup program setup pro...

Страница 5: ...if not using a third stage of heat or cool Not shown on SZ1009 or SZ1035 Heat Stage 1 Offset Screen Enter an offset value for heat stage 1 First stage is normally 0 offset Not shown on SZ1009 program...

Страница 6: ...will not appear if the outdoor air sensor function is disabled Not shown on SZ1022 Heating Lockout Screen Enter an out door air heating lockout temperature This screen will not appear if the outdoor...

Страница 7: ...TUESDAY The following screens are repeated for Wednesday Thursday Friday Saturday Sunday Holiday 1 2 COPY MON FOR TUE 7 ENTER DATES FOR HOLIDAY 1 DAYLIGHT HOL1 01 01 01 10 11 12 13 DURATION 00 DAYS S...

Страница 8: ...s meetings another option is to set the DI3 to external override and use the timed override button to put the unit in occupied mode To make the unit always occupied set DI3 to external time clock and...

Страница 9: ...ws unused stages to be set to activate physical alarms if desired In summary unlike most other multi stage programmable thermostats the Superstat allows independent adjustments of offsets and differen...

Страница 10: ...xt stage is allowed to turn on as well as when one stage turns off until the next stage is allowed to turn off DELAY ON POWER UP The SZ1009 SZ1022 SZ1031 and SZ1035 have an adjustable delay on power u...

Страница 11: ...g Temperature Display If any of the temperatures is reading slightly high or low there are three adjustment pots located in the cover to adjust them T1 is for the room temperature T2 is for the discha...

Страница 12: ...er We recommend the installer fill out the appropriate pages in the User s Guide and explain to the user how the thermostat operates what settings may be changed and how the time clock schedules are u...

Отзывы: