background image

R

2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

7

AI1 AMBIENT LIGHT INPUT

If using an ambient light sensor (0 to 5 or 1 to 5V); set 

the low and high scaling limits for AI2. These limits are 

what the light sensor reads at low limit and what the light 

sensor reads at full scale.
A Lighting Channel Threshold and Hysteresis for each 

of the available channels can be set for this input signal. 

The Channel Power Threshold is basically a setpoint for 

which AI1 is compared to determined when to turn off 

the selected cycle(s). The Channel Power Hysteresis is 

a buffer value which is prevents the channel from cycling 

off/on prematurely. For example, if the input is scaled 

0 to 1000 lumens and you want to turn off one channel 

if the input gets up to 500 lumens and allow it to come 

back on if the input falls to 400 lumens, enter in 0 for the 

scaling low limit, 1000 for the scaling high limit, 500 for 

the threshold and 10% for the hysteresis for that chan-

nel. 
Select a threshold and hysteresis for the channels which 

will be allowed to be shut off based on this input hitting 

the threshold. A common application for this feature is to 

control parking and exterior signage lighting. Essentially 

the channel will be on all the time it is occupied except 

when there is too much light. (Similar to the astronomical 

time function).

  If AI1 is not used, the threshold for all 

channels MUST equal the scaling high limit.

AI2 ENERGY / POWER / MONITORING INPUT

If using an energy meter, power meter or current trans-

ducer (0-5V), set the low and high scaling limits for 

AI2. These limits are what the energy or power meter 

reads at 0V and what the energy or power meter reads 

at 5V. For a 4 to 20mA input to be wired to AI2, a 250 

Ω resistor must be installed between AI2 and GND. If 

you want to use this input with a threshold and hyster-

esis (Channel Power section) to shut off lighting chan-

nels, select the relevant lighting channels (Enable AI2 

Threshold checkboxes) and enter a threshold and a 

hysteresis to be used. 

If AI1 is not used, the channel 

power threshold MUST equal the scaling high limit.

Select whether you want the time clock output (Digital 

Output Mode) to be Normally Open or Normally Closed 

during on periods.

The Channel Power Threshold is basically a setpoint to 

which AI2 is compared to determine when to turn off the 

selected channel(s). The Channel Power Hysteresis is a 

buffer value which prevents the channel from cycling off/

on prematurely. For example, if the AI2 input is scaled 0 

to 10000 KW and you want to turn off some channels if 

the input gets to 7500 KW and allow them to come back 

on if the input falls to 6500 KW, enter in 0 for the scaling 

low limit, 10000 for the scaling high limit, 7500 for the 

threshold and 10% for the hysteresis. You should choose 

this threshold to be larger than the accuracy/error specifi-

cation of the equipment/device being turned off so it does 

not cycle on and off.

AI2 AMBIENT LIGHT INPUT

If AI2 is not used for power limiting, a second light sen-

sor can be used to monitor another area. Set the low 

and high limits for AI2. These limits are the light sensor 

reading at 0Vand the sensor reading at 5V respectively. 

Click on the Enable box for each of the channels to be 

controlled by AI2 (in the Enable AI2 as Light Level Source 

column). Then proceed to enter threshold and hyster-

esis values for each channel (located just below the AI1 

AMBIENT LIGHT INPUT section). Each channel that is 

selected/checked (Enable AI2 as Light Level Source) 

will then have its threshold/hysteresis compared to AI2 

instead of AI1

CHANNEL MONITORING AND CONTROL

DI1 and Override 1 are used for Channel 1, DI2 and 

Override 2 are used for Channel 2, etc. 

There are four Digital Input Modes which can be used 

with a digital input: Regular, External Override, Momen-

tary Override, & Monitor.

Regular mode: 

The digital input is used in conjunction 

with the programmed schedule in determining when the 

relay output should be on or off.

External Override mode:

 The digital input acts the same 

as the override button on the front of the QWL 3.1 Rev 2 

Series panel. The switch used for this type of digital input 

must be a momentary N.O. switch.

Momentary Override: 

The digital input acts like a toggle 

switch. This must also be a momentary N.O. switch. If the 

time clock is on, pressing the switch turns it off, If the time 

clock is off, pressing the switch turns it on.

Содержание QWL 3.1 2 Series

Страница 1: ... Astronomical clock External time clock or occupancy sensor input for each channel Channel status LEDs Selectable normally open or normally closed relays Built in 2 Amp relays with hand off auto switches Contents Description 1 Features 1 Factory IP Network Address Configuration 1 Mounting 2 Wiring 2 RS 485 Controller Network Wiring Setup 3 Gateway Configuration Page 4 Commissioning Tools 5 Program...

Страница 2: ...ev 2 Series Panel accepts two 0 to 5 VDC inputs 8 dry contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 2 SERIES PANEL The QWL 3 1 Rev 2 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3 1 Rev 2 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or greater is to be installed within this panel M...

Страница 3: ...ev 2 Series Panel 4 NOTES 1 If using more than 64 control lers use additional QD1010 adapters 2 Each controller must use the same baud rate and be assigned a unique address B wires If the QWL 3 1 Rev 2 Series Panel will be at one end of the network hard wire a 120 Ω terminating resistor across the A and B terminals at the QWL 3 1 Rev 2 Series Panel See 1 below If the QWL 3 1 Rev 2 Series Panel wil...

Страница 4: ...elect a Controller Network Polling Cycle time for the QWL 3 1 Rev 2 Series Panel This is the time interval that the unit will poll the entire network of controllers on all ports The default setting is 1 min ute Select whether to allow caching the host name via DNS Typically this is left unchecked Select how often the QWL 3 1 Rev 2 Series Panel connects to the central server Typically this is set t...

Страница 5: ...ontrol the security of the gateway within the QWL 3 1 Rev 2 Series Panel and whether or not it can be accessed through the web interface Enabling Secure Mode disables all web interfaces including the configuration page and requires a specially configured USB flash drive or TCS Technical Support access to the QWL Panel if it is online with Ubiquity central server to unlock it Also the default login...

Страница 6: ...eight independent channels each with its own schedule If the occupied or ON time for a particular day is from 8 00AM to 5 00PM In the schedule enter 8 00 to 17 00 Within the Ubiquity programming page the desired schedule is simply selected from the drop down menu for each channel If the desired schedule is not shown in the drop down new schedules can be created or existing schedules can be edited ...

Страница 7: ...ing high limit Select whether you want the time clock output Digital Output Mode to be Normally Open or Normally Closed during on periods The Channel Power Threshold is basically a setpoint to which AI2 is compared to determine when to turn off the selected channel s The Channel Power Hysteresis is a buffer value which prevents the channel from cycling off on prematurely For example if the AI2 inp...

Страница 8: ...d override and if so whether it will be a schedule or chan nel override HOLIDAY VANISHING Choose whether to enable the Holiday Vanishing Feature If checked the controller will make the number of days for a holiday 0 after the holiday is over This will keep the holiday from occurring in subsequent years if it is not reprogrammed DIGITAL INPUT DELAY FILTER Enable the Digital Input Delay if you want ...

Страница 9: ...nality can be mimicked by using a Meter Multiplier value of 2 In the following picture both Type A and C are shown Three pulses are shown labelled 1 2 and 3 Notice how the Type A output closes and opens for each pulse where the Type C output simply changes state If you have a Type C device 3 terminals KYZ you will need to double the multiplier The SEQ100 only counts the contact closures for the K ...

Страница 10: ...o reboot the entire QWL 3 1 Rev 2 series panel This is accomplished by pushing and holding the button for 5 7 seconds Note During a reboot the lights associated with the Lighting Module of this product could go out it is recommended that you open the panel and place the Hand Off Auto switch for the corresponding channel in the Hand position to ensure that the lights that should be on remain on CPU...

Страница 11: ...pically a problem with wir ing Check wiring Make sure that communication wir ing runs are at least 5 away from fluorescent lights motors etc Make sure that all controllers on a net work have a unique address Make sure that the A and B wires are not switched or shorted Make sure that there is no stray voltage on the A and B wires B to A should measure between 0 5 VDC and 3 6 VDC B to A should measu...

Отзывы: