2800 LAURA LANE • MIDDLETON, WI 53562 • (800) 288-9383 • FAX (608) 836-9044 • www.tcsbasys.com

1

Product Manual          

Description                             

The QWL 3.1 Rev 2 Series Integrated Building Manager 

Panel contains a Ubiquity

TM

 Site Gateway with integrat-

ed lighting and energy management controls.  

Features                                 

Ubiquity Site Gateway

•  Site gateway to Ubiquity: enables controller interoper-

ability with Ubiquity

•  Enables Ubiquity to maintain controller programming 

and scheduling

•  Compatible with all TCS Basys supported controllers

•  Controller protocols supported: TCSbus, Modbus

•  Supervisory control routines

•  Supervisory override strategy

•  Auto discovery of networked controllers

•  Three integrated RS-485 serial ports

•  Additional serial ports can be added via USB ports

•  Integrated Ethernet controller with firewall capabilities

•  Integrated configuration web page

•  User adjustable controller monitoring rate

•  Remotely upgradable gateway software 

Lighting Controller (SLQ218)

•  365-day programming for each circuit

•  Analog input for photo sensor with the ability to 

remotely adjust sensitivity level

•  Selectable power failure state

•  Eight channel lighting schedules for interior and exte-

rior applications

•  Digital photocell inputs

•  Astronomical clock

•  External time clock or occupancy sensor input for 

each channel

•  Channel status LEDs

•  Selectable normally open or normally closed relays

•  Built-in 2 Amp relays with hand/off/auto switches

Contents                                  

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Factory IP Network Address Configuration

  . . . . . . . . .

 1 

Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

RS-485 Controller Network Wiring & Setup

. . . . . . . . . . 3

Gateway Configuration Page

. . . . . . . . . . . . . . . . . . . . .

4

Commissioning Tools

. . . . . . . . . . . . . . . . . . . . . . . . . . .

5

Programming - Lighting Module . . . . . . . . . . . . . . . . . . . 6

Programming - Pulse Meter . . . . . . . . . . . . . . . . . . . . . . 9

TCS ZigBee Wireless Network. . . . . . . . . . . . . . . . . . . 10

LED Display and Push Buttons  . . . . . . . . . . . . . . . . . . 10

Checkout & Troubleshooting  . . . . . . . . . . . . . . . . . . . . 10

Energy Meter (SEQ100)

Utility Pulse Counting Meter for Monitoring of:

•  Electric single and 3 phase kW and kWh

• Gas

• Water

• BTU

R

QWL 3.1 Rev 2 Series

Integrated Building Manager Panel
Models to Support Wired and
Wireless Networks

Factory IP Network Address 

Configuration                                  

                  

The QWL 3.1 Rev 2 Series Panels are typically ordered 

pre-programmed to customer specific networks and no 

additional software configuration is required. This is the 

preferred purchasing method.  
If a QWL 3.1 Rev 2 Series Panel is purchased without 

pre-programming it will be shipped with DHCP client 

enabled. The configuration page is available through a 

browser for additional configuration of the QWL 3.1 Rev 

2 Series Panel local IP address. Contact your network 

administrator to determine the local IP address (refer to 

the MAC address available on the product label). 

v1216.1

Содержание QWL 3.1 2 Series

Страница 1: ... Astronomical clock External time clock or occupancy sensor input for each channel Channel status LEDs Selectable normally open or normally closed relays Built in 2 Amp relays with hand off auto switches Contents Description 1 Features 1 Factory IP Network Address Configuration 1 Mounting 2 Wiring 2 RS 485 Controller Network Wiring Setup 3 Gateway Configuration Page 4 Commissioning Tools 5 Program...

Страница 2: ...ev 2 Series Panel accepts two 0 to 5 VDC inputs 8 dry contact digital inputs and 4 pulse meter inputs POWERING THE QWL 3 1 REV 2 SERIES PANEL The QWL 3 1 Rev 2 Series Panel is powered from a 120VAC 60HZ to 12VDC power supply module includ ed The QWL 3 1 Rev 2 Series Panel is designed to contain 24 VAC devices and wiring ONLY No line voltage 120 VAC or greater is to be installed within this panel M...

Страница 3: ...ev 2 Series Panel 4 NOTES 1 If using more than 64 control lers use additional QD1010 adapters 2 Each controller must use the same baud rate and be assigned a unique address B wires If the QWL 3 1 Rev 2 Series Panel will be at one end of the network hard wire a 120 Ω terminating resistor across the A and B terminals at the QWL 3 1 Rev 2 Series Panel See 1 below If the QWL 3 1 Rev 2 Series Panel wil...

Страница 4: ...elect a Controller Network Polling Cycle time for the QWL 3 1 Rev 2 Series Panel This is the time interval that the unit will poll the entire network of controllers on all ports The default setting is 1 min ute Select whether to allow caching the host name via DNS Typically this is left unchecked Select how often the QWL 3 1 Rev 2 Series Panel connects to the central server Typically this is set t...

Страница 5: ...ontrol the security of the gateway within the QWL 3 1 Rev 2 Series Panel and whether or not it can be accessed through the web interface Enabling Secure Mode disables all web interfaces including the configuration page and requires a specially configured USB flash drive or TCS Technical Support access to the QWL Panel if it is online with Ubiquity central server to unlock it Also the default login...

Страница 6: ...eight independent channels each with its own schedule If the occupied or ON time for a particular day is from 8 00AM to 5 00PM In the schedule enter 8 00 to 17 00 Within the Ubiquity programming page the desired schedule is simply selected from the drop down menu for each channel If the desired schedule is not shown in the drop down new schedules can be created or existing schedules can be edited ...

Страница 7: ...ing high limit Select whether you want the time clock output Digital Output Mode to be Normally Open or Normally Closed during on periods The Channel Power Threshold is basically a setpoint to which AI2 is compared to determine when to turn off the selected channel s The Channel Power Hysteresis is a buffer value which prevents the channel from cycling off on prematurely For example if the AI2 inp...

Страница 8: ...d override and if so whether it will be a schedule or chan nel override HOLIDAY VANISHING Choose whether to enable the Holiday Vanishing Feature If checked the controller will make the number of days for a holiday 0 after the holiday is over This will keep the holiday from occurring in subsequent years if it is not reprogrammed DIGITAL INPUT DELAY FILTER Enable the Digital Input Delay if you want ...

Страница 9: ...nality can be mimicked by using a Meter Multiplier value of 2 In the following picture both Type A and C are shown Three pulses are shown labelled 1 2 and 3 Notice how the Type A output closes and opens for each pulse where the Type C output simply changes state If you have a Type C device 3 terminals KYZ you will need to double the multiplier The SEQ100 only counts the contact closures for the K ...

Страница 10: ...o reboot the entire QWL 3 1 Rev 2 series panel This is accomplished by pushing and holding the button for 5 7 seconds Note During a reboot the lights associated with the Lighting Module of this product could go out it is recommended that you open the panel and place the Hand Off Auto switch for the corresponding channel in the Hand position to ensure that the lights that should be on remain on CPU...

Страница 11: ...pically a problem with wir ing Check wiring Make sure that communication wir ing runs are at least 5 away from fluorescent lights motors etc Make sure that all controllers on a net work have a unique address Make sure that the A and B wires are not switched or shorted Make sure that there is no stray voltage on the A and B wires B to A should measure between 0 5 VDC and 3 6 VDC B to A should measu...