    Air Conditioner Service Manual 

                                                                                             

 

Defrosting time chart 

 

 

          Outdoor Fan              ON                                    OFF                                ON 

 

 

          Revering Valve            ON                                    OFF                                      ON 

 

 

 

 

Compressor Relay      ON          OFF                            ON                              OFF            ON 

 

                                                39S      5S    Defrost Count MAX 12min    19S      15S                    t 

 

6.

 

  “FAN” mode operation   

The indoor fan motor always turns on at the set speed and the vane motor turns on at the set fettle. 

7.

 

4-way Valve control 

 

HEATING                          ON 

COOLING/DRY                OFF 

The 4-way valve reverses for 5 seconds right before start-up of the compressor as following chart: 

                                      COOLING/DRY TO HEATING                HEATING TO COOLING/DRY 

      Compressor 

 

      4-way Valve 

                                                    5s                                                        2min 

      Outdoor Fan 

 

8.

 

Assistant Heater 

1) The heater mode is automatically controlled. 

2) The condition of the heater ON. (must accord with the following conditions) 

    a. The compressor has operated over 10 minutes. 

    b. The indoor fan motor has operated at normal over 15 minutes. 

    c. Not at the defrosting. 

    d. The heater latest off was over 30 seconds. 

    e. ST-RT

3

℃。

 

    f. RT

22

    g. IPT

43

 

3) The condition of the heater OFF. (accord with one of the following condition) 

    a. The compressor off. 

    b. RT

24

    c. IPT

48

 

    d. Indoor motor off. 

    e. Enter the sleep mode. 

9.

 

“SLEEP” mode 

When the SLEEP button is pressed, the SLEEP mode is selected as following: 

Содержание TFF-60HRA

Страница 1: ...TYPE AIR CONDITIONERS SERVICE MANUAL No 20170622 Models TFF 60HRA TOF 60HSA CONTENTS 1 IMPORTANT NOTICE 2 PRODUCT DIMENSIONS 3 REFRIGERATION CYCLE DIAGRAM 4 OPERATION DETAILS 5 WIRING DIAGRAM 6 EXPLO...

Страница 2: ...information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or improvement without any prior...

Страница 3: ...Air Conditioner Service Manual 3 2 PRODUCT DIMENSIONS Indoor Unit Outdoor Unit Model A B C D E F G H I J K 60K 650 405 1920 940 1250 340 600 400 375 50 63...

Страница 4: ...y Compressor Accumulator Heat exchange condenser Heat exchange Evaporator 2 way valve Liquid side 3 way valve Gas side Cooling Heating Gas side 3 way valve Liquid side 2 way valve Heat exchange Evapor...

Страница 5: ...nly then you CAN NOT preset the Heating operation with the remote controller 9 9 1 2 4 3 5 6 10 7 MODE button ECO button FAN SPEED button TEMP UP button TIMER button SLEEP button TEMP DOWN button To s...

Страница 6: ...essor Outdoor fan OFF when the indoor pipe temperature is 53 Outdoor fan ON when the indoor pipe temperature is 48 Compressor OFF when the indoor pipe temperature is 62 Compressor ON when the indoor p...

Страница 7: ...e is selected without setting temperature the system will set the temperature at 23 automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according...

Страница 8: ...the temperature of the IPT is less then 35 for 2 minutes When the defrosting operation time on this condition exceeds 8minutes it will terminate C After the compressor operation continuously for 20 m...

Страница 9: ...HEATING HEATING TO COOLING DRY Compressor 4 way Valve 5s 2min Outdoor Fan 8 Assistant Heater 1 The heater mode is automatically controlled 2 The condition of the heater ON must accord with the followi...

Страница 10: ...sition and then set to the desired angle The positioning is decided as follows z When the ON OFF button is pressed z When the vane control is change from AUTO to MANUAL z When the SWING is finished z...

Страница 11: ...n automatic speed The operation continues unit the EMERGENCY operation switch is pressed or a button on the remote controller is pressed the normal operation will start NOTE Do not press the EMERGEMCY...

Страница 12: ...tes in set speed and in the HEATING the outdoor unit stops the indoor fan operates in cold air prevention control The system doesn t receive the signal of remoter controller except the signal of shut...

Страница 13: ...Air Conditioner Service Manual 12 5 WIRING DIAGRAM MODEL TFF 60HRA TOF 60HSA INDOOR UNIT OUTDOOR UNIT FM...

Страница 14: ...Conditioner Service Manual 13 6 EXPLOSION VIEW AND PARTS EXPLOSION VIEW Mode TFF 60HRA INDOOR UNIT 1 2 3 4 5 6 7 8 9 19 18 17 20 21 10 11 12 13 14 15 16 22 23 24 25 28 27 26 30 31 32 33 34 35 36 37 38...

Страница 15: ...10800063 Synchronization Motor Cover 1 20 210736103 Out Blow Casing Foam 1 21 210736103 Step Motor 2 22 1071200014 Vertical Vane 1 23 210736100 Up Left Ornamental Panel 1 24 210736098 Up Panel 1 25 21...

Страница 16: ...TCL Air Conditioner Service Manual 15 MODEL TOF 60HSA OUTDOOR UNIT...

Страница 17: ...71990066 Switch of low pressure 1 3171990210 Switch of high pressure 1 3172522102 Discharge temp sensor 1 3092520401AB Outdoor PCB 1 8 1070350971 Handle 1 9 3210027077 Right back clapboard 1 10 312012...

Страница 18: ...accordance with the wiring rules z The air conditioner must be installed by professional or qualified persons Do not install the appliance at a distance of less than 50 cm from inflammable substances...

Страница 19: ...lures z The user is responsible for having the appliance installed by a qualified technician who must check that it is earthed in accordance with current legislation and insert a thermomagnetic circui...

Страница 20: ...Name 1 Airflow direction flaps 2 Deflectors 3 Indoor unit rating label 4 Signal receiver 5 LED Display 6 Control panel 7 Front panel 8 Air filter 9 Front panel 10 Remote controller Outdoor unit No Na...

Страница 21: ...ld be less than 20m Indoor unit Outdoor unit be less than 5m Height should Should be less than 20 m Mode Standard length m Refrigerant piping Max length m A Additional refrigerant Calculation g 20g m...

Страница 22: ...ry spaces as shown in the picture Select a place where the filter can be easily taken out OUTDOOR UNIT Do not install the outdoor unit near sources of heat steam or flammable gas Do not install the un...

Страница 23: ...screw terminals by following the numbering Use wire size suitable to the electric power input see name plate on the unit and according to all current national safety code requirements Note The cable c...

Страница 24: ...al for the success of the installation 1 Place the drain hose below the piping taking care not to create siphons 2 The drain hose must slant downwards to aid drainage 3 Do not bend the drain hose or l...

Страница 25: ...humidity left inside the refrigerant circuit can cause compressor malfunction After having connected the indoor and outdoor units bleed the air and humidity from the refrigerant circuit by using a vac...

Страница 26: ...does not operate at all Power supply voltage check Connector contact check Power trans output voltage PCB assembly check Power receptable voltage Product input voltage PCB assembly Power input voltag...

Страница 27: ...ture sensor open short check Thermistor and evaporator surface contact check Clearance is needed 5mm Connector check Contact power Connector check Contact power Disconnection short circuit check of co...

Страница 28: ...ort circuit mal connection Vane motor check PCB assembly check vane motor driving circuit Replace the vane motor Replace the PCB Heating operation ON by remote controller Connector check If the 4 way...

Страница 29: ...5 14 27 567 4 219 31 3 981 2 192 76 0 895 0 746 13 26 239 4 186 32 3 836 2 146 77 0 869 0 728 12 24 984 4 152 33 3 697 2 101 78 0 843 0 710 11 23 795 4 117 34 3 563 2 057 79 0 819 0 692 10 22 671 4 08...

Страница 30: ...Resistance at 25 5 k TH1 indoor room temperature sensor and outside air temperature sensor TH2 indoor exchange temperature sensor and outside exchange temperature sensor Before measuring resistance di...

Отзывы: