Air Conditioner Service Manual
24
9. Installation manual
9.1 Installation Details
Connecting pipe length
Model
Pipe size(Inch)
Liquid
Gas
TFC-24HRA/TOC-24HNA
3/8
5/8
TFC-48HRA/TOC-48HSA
1/2
3/4
Outdoor unit:
Indoor
unit
Elb ow to
pre ven t water
from entering room
be less than 5m
Height should
Should be less than 20 m
Indo o r uni t
Outdoor u nit
be less than 5m
Height should
Should be less than 20 m
Mode
Standard length:
m
Refrigerant piping
Max. length: m
A
Additional refrigerant
Calculation: ×g=20g/m(A-5m)
TFC-24HRA/TOC-24HNA
5.0
20
30g/m
TFC-48HRA/TOC-48HSA
5.0
20
40g/m
Connecting cables
The power cord should be selected according to the following specifications sheet.
Appliance Amps
Wire Size
5
AWG21/0.75 mm2
10
AWG18/1.0 mm2
13
AWG15 /1. 5 mm2
18
AWG14/1.6 mm2
25
AWG12/2.0 mm2
30
AWG10/2.5 mm2