TCL Air Conditioner Service Manual 

                                                                                             

9

 

 

Defrosting time chart 

 

 

     Outdoor Fan       ON                  OFF                ON 
 
 
          Revering Valve            ON                                    OFF                                      ON 
 
 
 

 
Compressor Relay      ON          OFF                            ON                              OFF            ON 
 
                        39S   5S  Defrost Count MAX 12min  19S   15S          t 
 

6.    “FAN” mode operation   

The indoor fan motor always turns on at the set speed and the vane motor turns on at the set fettle. 

7. 4-way 

Valve 

control 

 

HEATING                          ON 
COOLING/DRY        OFF 
The 4-way valve reverses for 5 seconds right before start-up of the compressor as following chart: 
                                      COOLING/DRY TO HEATING        HEATING TO COOLING/DRY 
   Compressor 
 
      4-way Valve 
                                                    5s                                                        2min 
   Outdoor Fan 
 

8. “SLEEP” 

mode 

When the SLEEP button is pressed, the SLEEP mode is selected as following: 

 

The indoor fan speed is set at the low speed, the power lamp and the sleep lamp is on, the temperature off 
after 5 minutes. 

 

When selecting COOLING/DRY operation with SLEEP mode, the set temperature will be raised by 1

.8℉

 1 

hour later and by 

3.6℉

  2 hour later. 

 

When selecting HEATING operation with SLEEP mode, the set temperature will be dropped by 1

.8℉

 1 

hour later and 

3.6℉

 2

 

hour later. 

 

After the System operates in SLEEP mode for 8 hours, it will stop automatically. 

9.  Fan motor control 

(1)  Rotational frequency feedback control 

The indoor fan motor is equipped with a rotational frequency sensor, and outputs signal to the 
microprocessor to feedback the rotational frequency. Comparing the current rotational frequency with the 
target rotational frequency, the microprocessor adjusts fan motor electric to make the current rotational 
frequency close to the target rotational frequency. With this control, when the fan speed is switched, the 
rotational frequency changes smoothly. 

(2)  When the rotational frequency feedback signal has not output for 5 seconds (or when the microprocessor 

can’t detect the signal for 5 seconds), the fan motor is regarded locked-up. Then the electric current to the fan 

Содержание KFTHP-09

Страница 1: ...CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 ELECTRICAL SCHEMATIC DIAGRAM 13 5 EXPLOSION VIEW 16 6 PARTS LIST 22 Models KFTHP 12 KFTHP 18 KFTHP 24 TCL...

Страница 2: ...or the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or...

Страница 3: ...i m 3 h 700 730 950 1000 1400 1450 Indoor fan type Cross flow Cross flow Cross flow Cooling rpm 1330 1150 950 1550 1230 1110 1550 1230 1110 Heating rpm 1330 1150 950 1550 1230 1110 1550 1230 1110 Dry...

Страница 4: ...controller 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each tim...

Страница 5: ...ditioner Service Manual REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above is...

Страница 6: ...compressor Outdoor fan OFF when the indoor pipe temperature is Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is Compressor ON when the indoor...

Страница 7: ...e is selected without setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to...

Страница 8: ...of the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT...

Страница 9: ...de the set temperature will be raised by 1 1 hour later and by 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later Afte...

Страница 10: ...andard position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished...

Страница 11: ...pressed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When...

Страница 12: ...gnal of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure t...

Страница 13: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 12 13...

Страница 14: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 18 14...

Страница 15: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 24 15...

Страница 16: ...TCL Air Conditioner Service Manual 16 EXPLOSION VIEW MODEL KFTHP 12 INDOOR UNIT...

Страница 17: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 18 INDOOR UNIT 17 18 16 15 14 13 12 11 9 10 7 8 6 20 19 23 21 22 24 25 28 27 26 5 4 3 2 1 17...

Страница 18: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 24 INDOOR UNIT 17 18 16 15 14 13 12 11 9 10 7 8 6 20 19 23 21 22 24 25 27 26 28 29 30 31 5 4 3 2 1 18...

Страница 19: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 12 OUTDOOR UNIT 16 27 26 25 24 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 19...

Страница 20: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 18 OUTDOOR UNIT 24 16 28 27 26 25 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20...

Страница 21: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 24 OUTDOOR UNIT 24 16 28 27 26 25 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21...

Страница 22: ...e Clamp Base 1 1070040006 Cable Clamp Cover 1 15 1110050903 Evaporator 1 16 1070350137 Water Drainage Assembly 12 17 1070350140 Vane 1 18 1070110011 Drainage Hose 1 19 1070350155 Evaporator Fastness C...

Страница 23: ...Assembly 1 15 1173090107 Transformer 1 16 1070500692 Front Panel 1 17 1070500502 Display PCB Cover 1 18 1091990054 Heater 1 19 1073090126 Display PCB Box 1 20 1090500501 Display PCB 1 21 1073090108 V...

Страница 24: ...ertical Vane 2 13 1070110012 Drainage Hose 1 14 1170230001 Indoor Sensor Assembly 1 15 1173090107 Transformer 1 16 1070850257 Front Panel 1 17 1070850148 Display PCB Cover 1 18 1091990055 Heater 1 19...

Страница 25: ...alve 1 14 1120130036 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1080050002 Right Plate 1 17 1070040001 Cable Clamp 6 1 1070040003 Cable Clamp 8 1 1070040008 Cable Clamp 10 1 18 11719900...

Страница 26: ...021 Two way Valve 1 14 1120130032 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1081990039 Right Plate 1 17 1074060118 Cable Clamp 1 18 1171990049 Terminal 1 19 1170100026 Compressor Capac...

Страница 27: ...r 1 13 1120120037 Two way Valve 1 14 1120130047 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1080050043 Right Plate 1 17 1074060118 Cable Clamp 1 18 1171990049 Terminal 1 19 1170100007 Co...

Отзывы: