TCL KFTHP-09 Скачать руководство пользователя страница 11

TCL Air Conditioner Service Manual 

                                                                                             

1 1

 

 

Press the Timer button(‘h’ flashes). 

 

Use the 

▲▼

 button to select the time at which the air conditioner must activate (between 0 and 10 

hours can be set at every half hour-between 10 and 24 hours can be set at every hour). 

 

Press the Timer button (‘h’ stops flashing) and the preset time appears in the display. 

 

Press the Timer button again to delete the selected data from the memory. 

Note : If no buttons are pressed during the programming of the timer function, thee remote control will 
switch off automatically after 10 seconds. 

(2)  To switch the air conditioner off at the desired time, follow the procedure specified below (the remote control 

and air conditioner are switched off): 

 

Press the timer button. 

 

Use the 

▲▼

 button to select the time at witch. 

13. EMERGENCY Operation 

When the EMERGENCY Operation switch is pressed once, COOLING mode is selected and if in 3 seconds the 
EMERGENCY Operation switch is pressed again, mode is selected. Then pressed once again, the unit is switch 
off. 
When the remote controller is missing, has failed or the batteries run down, press the EMERGENCY Operation 
switch on the front of the indoor unit. The unit will start. 
The first 30 minutes of operation will be the test run operation. The operation is for servicing. The indoor fan runs 
at high speed and the system is in continuous operation. The thermostat is ON and the timer is reset to normal. 
After 30 minutes of test run operation the system shifts to AUTO COOLING/HEATING mode, and the indoor fan 
runs in automatic speed. The operation continues unit the EMERGENCY operation switch is pressed or a button 
on the remote controller is pressed

 and 

normal operation will start. 

NOTE: Do not press the EMERGEMCY Operation switch during normal operation. 

14.  AUTO RESTART Function(Option)

 

1.When the indoor unit is controlled with the remote controller, the operation mode, set temperature, and the fan 
speed are memorized by the indoor electric control PCB. The AUTO RESTART function sets to work the 
moment power has restored after power failure. Then, the unit will restart automatically. 
2. How to set the AUTO RESTAR function. 

 

Press the emergency switch and power supply to the PCB following, 

hold

 10

 

seconds and the buzzer will 

beep three times. The AUTO-RESTAR is set. 

 

Do the operation again, the buzzer will beep four times and the AUTO-RESTAR function is cancelled. 

15. 

Failure Display and Handling

 

a) Failure 

Display 

When the controller 

has

 failure, the buzzer will 

sound

 long for three times, and displays the failure from the 

failure lamp. 

b) Failure 

Code 

If have the digital pipe that display

s

 the failure code for digital pipe, or display for the run lamp. 

Type of failure 

The lamp flash 

Display of digital pipe 

The failure of room temperature sensor 

Once/cycle 

E1 

The failure of indoor pipe temperature sensor 

Twice/cycle 

E2 

The failure of indoor fan motor 

6 times/cycle 

E6 

c) Failure 

Handling 

 

When the room temperature sensor or the indoor pipe temperature sensor 

has a

 failure, the system will be 

shut off, the compressor will be OFF, and the outdoor fan and the indoor fan will be OFF. The system 
doesn’t receive the signal of remoter controller except the signal of shut off it. When the failure 
disappear, the controller can operate in normal mode. before this, presses the “ON/OFF” to start the 
system, and it will operate in COOLING or HEATING for 30 minutes, and follows shut off. During 

Содержание KFTHP-09

Страница 1: ...CONDITIONERS CONTENTS 1 IMPORTANT NOTICE 2 2 TECHNICAL SPECIFICATION 3 3 OPERATION DETAILS 4 4 ELECTRICAL SCHEMATIC DIAGRAM 13 5 EXPLOSION VIEW 16 6 PARTS LIST 22 Models KFTHP 12 KFTHP 18 KFTHP 24 TCL...

Страница 2: ...or the interpretation of this information nor can it assume any liability in connection with its use The information specifications and parameter are subject to change due to technical modification or...

Страница 3: ...i m 3 h 700 730 950 1000 1400 1450 Indoor fan type Cross flow Cross flow Cross flow Cooling rpm 1330 1150 950 1550 1230 1110 1550 1230 1110 Heating rpm 1330 1150 950 1550 1230 1110 1550 1230 1110 Dry...

Страница 4: ...controller 6 2 5 3 7 1 1 1 TCL Air Conditioner Service Manual Operation Details Remote Control The remote controller is not preset as Cooling Only Air Conditioner or Heat Pump by manufacturer Each tim...

Страница 5: ...ditioner Service Manual REMOTE CONTROLLER The four types of remote controller is as follow GYKQ 05 GYKQ 10e optional GYKQ 11e optional GYKQ 12e optional Note The function of remote controller above is...

Страница 6: ...compressor Outdoor fan OFF when the indoor pipe temperature is Outdoor fan ON when the indoor pipe temperature is 118 4 Compressor OFF when the indoor pipe temperature is Compressor ON when the indoor...

Страница 7: ...e is selected without setting temperature the system will set the temperature at automatically with the AUTO FAN speed 2 When selecting the HEATING mode operation the system will operate according to...

Страница 8: ...of the IPT is less than for 2 minutes When the defrosting operation time on this condition exceeds 8 minutes it will terminate C After the compressor operates continuously for 20 minutes and the IPT...

Страница 9: ...de the set temperature will be raised by 1 1 hour later and by 2 hour later When selecting HEATING operation with SLEEP mode the set temperature will be dropped by 1 1 hour later and 2 hour later Afte...

Страница 10: ...andard position and then set to the desired angle The positioning is decided as follows When the ON OFF button is pressed When the vane control is change from AUTO to MANUAL When the SWING is finished...

Страница 11: ...pressed or a button on the remote controller is pressed and normal operation will start NOTE Do not press the EMERGEMCY Operation switch during normal operation 14 AUTO RESTART Function Option 1 When...

Страница 12: ...gnal of remoter controller except the signal of shut off When the system checks the voltage is 220V and the delay control is finished it operates at normal again When the indoor fan motor is failure t...

Страница 13: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 12 13...

Страница 14: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 18 14...

Страница 15: ...TCL Air Conditioner Service Manual ELECTRICAL SCHEMATIC DIAGRAM MODEL KFTHP 24 15...

Страница 16: ...TCL Air Conditioner Service Manual 16 EXPLOSION VIEW MODEL KFTHP 12 INDOOR UNIT...

Страница 17: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 18 INDOOR UNIT 17 18 16 15 14 13 12 11 9 10 7 8 6 20 19 23 21 22 24 25 28 27 26 5 4 3 2 1 17...

Страница 18: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 24 INDOOR UNIT 17 18 16 15 14 13 12 11 9 10 7 8 6 20 19 23 21 22 24 25 27 26 28 29 30 31 5 4 3 2 1 18...

Страница 19: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 12 OUTDOOR UNIT 16 27 26 25 24 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 19...

Страница 20: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 18 OUTDOOR UNIT 24 16 28 27 26 25 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 20...

Страница 21: ...TCL Air Conditioner Service Manual EXPLOSION VIEW MODEL KFTHP 24 OUTDOOR UNIT 24 16 28 27 26 25 23 22 21 20 19 18 17 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21...

Страница 22: ...e Clamp Base 1 1070040006 Cable Clamp Cover 1 15 1110050903 Evaporator 1 16 1070350137 Water Drainage Assembly 12 17 1070350140 Vane 1 18 1070110011 Drainage Hose 1 19 1070350155 Evaporator Fastness C...

Страница 23: ...Assembly 1 15 1173090107 Transformer 1 16 1070500692 Front Panel 1 17 1070500502 Display PCB Cover 1 18 1091990054 Heater 1 19 1073090126 Display PCB Box 1 20 1090500501 Display PCB 1 21 1073090108 V...

Страница 24: ...ertical Vane 2 13 1070110012 Drainage Hose 1 14 1170230001 Indoor Sensor Assembly 1 15 1173090107 Transformer 1 16 1070850257 Front Panel 1 17 1070850148 Display PCB Cover 1 18 1091990055 Heater 1 19...

Страница 25: ...alve 1 14 1120130036 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1080050002 Right Plate 1 17 1070040001 Cable Clamp 6 1 1070040003 Cable Clamp 8 1 1070040008 Cable Clamp 10 1 18 11719900...

Страница 26: ...021 Two way Valve 1 14 1120130032 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1081990039 Right Plate 1 17 1074060118 Cable Clamp 1 18 1171990049 Terminal 1 19 1170100026 Compressor Capac...

Страница 27: ...r 1 13 1120120037 Two way Valve 1 14 1120130047 Three way Valve 1 15 1081990107 Electrical Box Cover 1 16 1080050043 Right Plate 1 17 1074060118 Cable Clamp 1 18 1171990049 Terminal 1 19 1170100007 Co...

Отзывы: