INSTALLATION OF THE INDOOR CASSETTE UNIT
Where possible the following areas should be avoided to avoid potential problems with the
appliance and/or safety risks:
1. Where flammable gas is likely to be in the air.
2. Where the air has a high salt content
3. Where caustic gasses are likely to be in the air.
4. Which is unable to safely bear the weight of the unit
5. With high levels of electromagnetic interference.
6. Where the unit may be subjected to acid or alkaline solutions.
7. With high levels of humidity.
Select the installation location taking consideration of the following:
1. Route of the pipework / wiring
2. Access to the upper parts of the unit for connection of the pipework/wiring after hanging
the unit
3. Ability of the area to support the weight of the unit.
Before hanging the unit the
refrigerant pipes, drain pipe
and connection wires
should be led to the
location of the outdoor unit.
Confirm the size of the
indoor unit and ceiling
opening using the
supplied installation
template.
SPACE AROUND THE UNIT
The following space must be
left around the unit.
1. At least 1m to each side.
2. At least 33cm between upper
side of ceiling and structure
above.
3. At least 5cm above the unit
to any structure or
obstruction.