HGP Kit Manual
4.0 Installation
19
Capacitor Brackets
Figure 9 – Capacitors and Brackets
Capacitor brackets supplied with the HGP CP kits mount the capacitors from a right angle bracket
using the studs on the bottom of the capacitors. The bracket surrounding the capacitors is mounted
near the top of the capacitor can. Rubber grommet material is placed around the large diameter holes
to prevent the edges of the bracket damaging the capacitor cans. This hole does not firmly clamp the
capacitors, and is not intended to do so: such a design would prevent the internal capacitor pressure
disconnection means from operating. This bracket prevents gross motion of the capacitors during
shipping vibration which could fracture the mounting bracket or allow the capacitors to hit other
components.
Contactor (Customer Supplied)
Your panels may include contactors to remove the tuned circuit from the filter under no load or
light load conditions. Select contactor size based on the contactor UL general purpose current
rating to handle 110% of the tuned circuit current from the tables above. The impedance of the
line and tuning reactors removes the need for special capacitor rated contactors in this
application.