HGL Manual
5.0 PQconnect Connectivity
33
Read Parameters:
Table 22: Network Interface OUTPUT/Feedback Register Map
Parameter Name
I/O Reg
Address
Offset
Direction
Data Values and Examples
Description
I_TUNE_A_THD
79
Output
% THID
50 = 5.0% THID
Phase A THID for tuned circuit current feedback
I_TUNE_B_THD
80
Output
Phase B THID for tuned circuit current feedback
I_TUNE_C_THD
81
Output
Phase C THID for tuned circuit current feedback
V_LINE_AB_THD
33
Output
% THVD
50 = 5.0% THVD
A-B Phase to Phase THVD
V_LINE_BC_THD
34
Output
B-C Phase to Phase THVD
V_LINE_CA_THD
35
Output
C-A Phase to Phase THVD
V_LOAD_AB_THD
53
Output
A-B Phase to Phase THVD
V_LOAD_BC_THD
54
Output
B-C Phase to Phase THVD
V_LOAD_CA_THD
55
Output
C-A Phase to Phase THVD
V_TRAP_A_THD
73
Output
Tuning circuit A Phase THVD
V_TRAP_B_THD
74
Output
Tuning circuit B Phase THVD
V_TRAP_C_THD
75
Output
Tuning circuit C Phase THVD
I_LINE_A_TDD
42
Output
% iTDD
50 = 5.0% iTDD
Filter input total Demand Distortion Phase A iTDD
I_LINE_B_TDD
43
Output
Filter input total Demand Distortion Phase B iTDD
I_LINE_C_TDD
44
Output
Filter input total Demand Distortion Phase C
iTDD
SYS_POWER_ON
201
Output
0 = Power Off
1 = Power On
Indicates if the filter has input power available
SYS_STATUS_OK
202
Output
0 = Filter is operating
1 = Filter has indicated status
warning
Indicates filters status
SYS_AT_CAPACITY
203
Output
0 = Nominal
1 = At Capacity
Indicates if the filter is running at its maximum
current capacity
SYS_STATE
256
Output
0,1 = Initialization
2 = Power on Delay
3 = Unit Self State Inhibit
4 = Reset
5 = Force Open Contactor
6 = Force Close Contactor
7 = Auto Load Open
8 = Auto Load Close
9 = Auto kVAR Close
10 = Auto kVAR Open
11 = External Open
12 = External Close
13 = No Contactor
14 = Contactor Closed Inhibited
15 = Calibrate offsets
16 = Calibrate Magnitude
17 = No Communication
18 = Communication configuration
19 = Calibrate Check
Indicates the present state of the system state
machine.