T61 Smart Modem
Page 37 of 47
User Guide V1.4
7.3.8.6
Input Sensitivity (sec)
Integer
1-255
Number of seconds for the input to confirm the reading. E.g. the input is
confirmed to be high only when it is high for at least 2 seconds (when input
sensitivity is configured to 2 seconds).
7.3.8.7
AI Alarm Low Limit (%)
integer
0-50
Set the percentage of the full scale to be the analog lower limit. E.g. if the
analog input is connected to a voltage output with full scale of 1.8V and the
AI Alarm Low Limit is configured to be 30%, the alarm will be triggered when
the input voltage is lower than 0.3*1.8=0.54V.
7.3.8.8
AI Alarm High Limit (%)
integer
51-100
Set the percentage of the full scale to be the analog higher limit.
7.3.8.9
Output Settings
Index
0
Disable
1
Input Trigger. The digital output pin will be short to ground when the input
detects a critical condition.
2
Remote Control. User is able to control the output pin remotely.
3
Both
7.3.8.10
Output Duration (sec)
integer
1-255
Set how long (in seconds) the digital output will be on when it is triggered by
input, i.e. when Output Settings is configured to be Input Trigger or Both and
the output is triggered by input. If the output is triggered by remote control
(SMS or Command), it will be always on until further instruction from the
remote.
7.3.9
Utilities
T61 Smart Modem provides some basic and handy utility functions for users.
Options
1
Load Default Setting
–
device.
5
Recover Smart Modem Baud Rate
– This is a backup recovery option for the
situations in which CPU can no longer talk to module. It will set module baud
rate to be 460800bps.