background image

- 12 -

TC1631R/S

User's Manual

Rev. 1.6

Chapter 3 - Troubleshooting

General

Alarm conditions occur whenever an optical problem or "fault" condition is detected by the TC1631.

All LEDs are Off

If no LEDs are lit on the unit, check the DC power supply, terminal block connector plug, change to alternate
power jack on the rear panel, fuses A and/or B indicated on page 16, and/or the power source.  If the problem
persists, contact the Technical Support Department at TC Communications, Inc.

Alarm LED

When an alarm condition is detected, the Alarm LED will flash.  The following fault conditions will cause
the alarm to be triggered:

1.

Optic signal lost from optic "RxA" or "RxB" (for optical redundant models only).

2.

Optic signal is marginal, which causes invalid data packets to be received; the "SYNC" LED will "Flash."

3.

Received "space" or "mark" from local T1/E1 device.

4.

An invalid Line Code setting exists.

5.

The Line Length setting does not match the Line Code.

6.

The local or remote T1/E1 signal is lost; the "LOCRD" or "RMTRD"  LED will be also be flashing.

Note: The "RMTRD" LED will "Flash" when there is no fiber cable connected or the fiber cable is bad.

Optic Cable Types

Conventionally, fiber optic cable with 

yellow-colored

 insulation is used for Single Mode applications; 

gray

or orange-colored

 insulated cable is for Multimode use.  If Multimode cable is used in a Single Mode

application, the test results could be erroneous and confusing.

Calculating the Loss on the Fiber

The fiber optic link and/or connectors are frequently the source of various problems.  Check out the
connectors and the integrity of the link first.  Ideally, the link should be calibrated for total loss after the
installation has been completed.  This will accomplish two things: (1) it will verify that the total loss of the
link is within the loss budget of the device and (2) it will provide a benchmark for future testing.  For example,
a system that has been tested as having 6dB total loss when installed and suddenly tests out as having a loss
of 10dB probably has a connector or link problem.

*These numbers are listed for reference only.  We recommend an OTDR reading be used to determine actual link loss.

These are the reference values we use to calculate the loss on the fiber:

Multimode 850nm

:

3 dB loss per km on 62.5/125µm cable*

Multimode 1310nm

:

2 dB loss per km on 62.5/125µm cable*

Single Mode 1310nm

:

0.5 dB loss per km on 9/125µm cable*

Single Mode 1550nm

:

0.25 dB loss per km on 9/125µm cable*

Содержание TC1631R

Страница 1: ...cifica tion TC Communications Inc reserves the right to change or modify the contents of this manual at any time without prior notification TC1631R S With TB output RACK MOUNT STAND ALONE T1 E1 FIBER...

Страница 2: ...setting should be marked AMI SW1 3 in the Down On position B8ZS HDB3 SW1 3 in the Up Off position ON 3 2 1 4 AMI B8ZS HDB3 DISALM RMTLB LOCLB ON 3 2 1 4 AMI B8ZS HDB3 DISALM RMTLB LOCLB Important Not...

Страница 3: ...lation Procedure 9 TC1631R S s Configuration 10 System Start Up 11 Chapter 3 Troubleshooting 12 General 12 All LEDs are Off 12 Alarm LED 12 Optic Cable Types 12 Calculating the Loss on the Fiber 12 Ca...

Страница 4: ...transmit data The TC1631R S has multiple LED indicators to ease installation and troubleshooting These LEDs indicate power operating voltage alarm status local and remote T1 E1 signal loss bipolar vio...

Страница 5: ...hen the optical signal is lost Configuration Setting LEN Copper Line Length indicator Off whenever the minimum T1 Line Length is set to 0 133 feet factory default setting or zero 0 for the E1 interfac...

Страница 6: ...the function SW2 6 SW2 7 SW2 8 These switches define the DSX 1 cross connect distance There are 5 partitions to choose from In a T1 application this is the length of twisted pair cable connecting the...

Страница 7: ...ck connector shown above is shown for reference only T1 E1 Signal Input Output Terminal Blocks POWER DRY CONTACT ALARM PWR A PWR B TC1631S Rear Panel IN OUT Normal open Rating 200 VDC 500ma max 12 VDC...

Страница 8: ...ck function The signal processor composes T1 E1 s timing and data to a bit stream The optic interface converts the electrical bit stream to an optic signal and vice versa Figure 4 TC1631R S Functional...

Страница 9: ...r panel the left pair of terminal block connectors are for T1 E1 signal going into the TC1631R S receive while the right pair of terminal block connectors are for the transmit signal coming out of the...

Страница 10: ...ct set the copper Line Length for the T1 transmit line driver according to the table below When connecting to DSX 1 cross connects for copper Line Lengths ranging from 0 to 655 feet see DIP Switch Fun...

Страница 11: ...oing signal each cable has two cores a shield 4 Verify optical connections Make sure the local TC1631 s optic TxA is connected to the remote TC1631 s optic RxA and vice versa For dual optical models o...

Страница 12: ...cable is bad Optic Cable Types Conventionally fiber optic cable with yellow coloredinsulation is used for Single Mode applications gray or orange colored insulated cable is for Multimode use If Multim...

Страница 13: ...Chapter 4 Bench Tests Optic Cables If the SYNC LED on the front panel is flashing this is an indication that the optical signal is not being correctly received Usually unsecured fiber optic connectors...

Страница 14: ...a signal will the TC1631R S unit set its LEDs appropriately for normal operation Proceed to the Local Loopback Test Local Loopback Test The purpose of this test is to verify 1 the signal source recog...

Страница 15: ...at the unit is in RMTLB mode Note other LEDs might flash for about three seconds but will settled down to their normal state 5 The PWRA and or PWRB Vcc Rx A SYNC RMTRD and LOCRD LEDs on the remote TC1...

Страница 16: ...N 4 3 2 1 SW1 Dry contact alarm relay terminal block connector T1 E1 Line interface module T1 E1 input and output terminal block connectors Power A and B Terminal block connectors Fuses A B Oscillator...

Страница 17: ...em Bit Error Rate 1 in 1010 or better Visual Indicators ALARM PWR A PWR B Vcc SYNC Rx A Rx B USE B RMTLB LOCLB BPV LEN AMI LAIS RAIS LOCRD RMTRD Dry Contact Alarm 200VDC 500mA 10watts Power Source Sta...

Страница 18: ...2 Locate the interface module at board location JP2 the board plugs vertically into the main board s socket 3 For 75 ohm impedance the jumpers on the interface module should be set as follows JP2 and...

Страница 19: ...am Figure 10 RJ45 Connection Diagram Note Pins 7 8 12 14 and 15 are not used on the DB15 connector Pins 5 6 10 and 13 are reserved for Telco use Note Pins 3 and 6 are not used on the RJ45 connector Pi...

Страница 20: ...DC 18 36VDC input 12VDC output and 100 Watts output power TCRM192 D 01 19 rack with dual power cards each has universal AC input 90VAC to 240VAC 50Hz to 60Hz with 12VDC output Maximum output power is...

Страница 21: ...POWER CARD POWER BACKPLANE TC1630 RACKMOUNT POWER SUPPLY INPUT 36 75V OUTPUT 12V 1 5 OUTPU TS MAX OUTPUT POWER 150W EDGE CONNECTOR TO TC1630R CARD 10 X PWR B PWR B PWR A PWR A 48 VDC 12 VDC 12 VDC 12...

Страница 22: ...o TC Communications Inc transportation charges prepaid for examination by TC Communications Inc Buyer shall bear the risk of loss until all goods authorized to be returned are delivered to TC Communic...

Отзывы: