Equalization is used for FREEDOM batteries ONLY, it can ensure that the
individual cells within the batteries are fully charged, equal to one another, and that
the electrolyte is stirred up by the gassing of the cells. But this function was strongly
recommended not to use over once a month.
Please do read the related information about equalization charging in 4.2 before
you do it to battery.
WARNING
Please ensure you set the dip switch 2 and 3 back to OFF when you
finished the equalization charging each time.
Only be active after the battery charger is power ON.
As a protection, TRIDENT will stop charging if the switch is set to ON
before the battery is power on.
2.2.12 Built-in Safety
TRIDENT battery charger provides the following protection features:
1) Unit shutdown if there is a short circuit on output.
2) Electronic protection for reversed polarity
3) Unit shutdown in event of battery over voltage
4) Unit reduces output in event of battery charger over temp, and maintains the
temp at a balance level.
5) Unit shutdown in event of battery over temp, and automatic operation reset once
the temp comes down
2.2.13 Automatic temperature compensation
The remote battery temperature sensor is a standard accessory with TRIDENT
battery charger. With it is plugged to the battery charger, the unit provides a more
accurate temperature-compensated charge for the battery to which the sensor is
attached automatically.
2.2.14 High ambient Temperature rated
TRIDENT charger was designed to work at full load up to 40
℃
.
2.2.15 Protective Lacquer on each PCB