TB Controls TC02 Скачать руководство пользователя страница 3

 

Operations & Maintenance Manual

 

 

Doc: TC02 O&M

 

Page 3 of 20

 

Status: 

Final

    Issue: 

11 

 

©TB Controls 2011 

 

1. 

Document Management 

1.1. 

Change Control 

Ver.No. 

Date of 

Issue 

Status 

Changes 

Description/Comment 

8 Sept 04 

Final 

All sections 

First Issue 

13 Oct 04 

Final 

 

Changes relating to additional 
air sensors 

15 Oct 04 

Final 

All sections 

Typographical amendments 
Increased index references 

16 Nov 04 

Final 

Section 7 added 

Outside sensor fitting 

20 Nov 06 

Final 

Name  change  &  Various 
updates 

Mini-FCU changed to TC02 

7 Feb 06 

Final 

Section  8  (fault  finding) 
added  and  various  minor 
text changes 

Updates from Diffusion 

24 May 07 

Final 

New  mode  to  allow  user 
interface to be locked 

Requested 

by 

Diffusion, 

TC02 firmware V3.23 

16 July 08 

Final 

MODBUS  BMS  interface 
details.

 

LON  comms  error 

for  slave  device  added. 
Return air sensor now NOT 
required  on  slave  units  if 
fitted to master. 

TC02 firmware V4.00 

30 Sep. 09 

Final 

LON  wire  colour  change  to 
match  Diffusion  drawings, 
terminals  11  and  13  (black 
and white). 

Requested by Diffusion 

10 

22 Apr. 10 

Final 

Reverse  sense  option  for 
return air sensor. Disable or 
setback 

heating 

when 

sensor is below a set-point. 

Requested  by  Diffusion  for 
New Look (firmware V4.10) 

11 

5 Apr. 11 

Final 

Set-point  limits  extended, 
DIP 5 for New Look settings 

Requested  by  Diffusion  for 
New Look (firmware V4.12) 

1.2. 

Document Review 

Reviewer. 

Remit 

Rob Boardley 

Technical Accuracy 

Kevin Byrne 

Presentation 

 

 

 

 

1.3. 

Document Status 

FINAL 

 

1.4. 

Document Ownership 

Rob Boardley  Design & Development 

 

 

Содержание TC02

Страница 1: ...B U I L D I N G C O N F I D E N C E TC02 Curtain heater controller Previously known as the mini FCU Operations Maintenance manual TBControls 2011...

Страница 2: ...ONTROL PLATE UNIT 6 3 1 TC02 Connections 7 4 MASTER SLAVE 8 4 1 Phased Start Sequence 8 4 2 Controller Start sequence 8 4 3 Error Messages 9 4 3 3 Master 9 4 3 4 Slave Messages 9 4 4 LCD Modes 9 4 4 5...

Страница 3: ...user interface to be locked Requested by Diffusion TC02 firmware V3 23 8 16 July 08 Final MODBUS BMS interface details LON comms error for slave device added Return air sensor now NOT required on slav...

Страница 4: ...s The curtain heater controller unit has the following features Powered from 12 24 volts AC or DC Four fan speed settings with silent fan speed switching Controlled by four snubberless triacs with hea...

Страница 5: ...230 VAC lamps as in the Ambassador unit On board real time clock for timed operation and event log time stamping Log of the last 500 system events Fan speed monitoring input to detect fan motor failur...

Страница 6: ...height is 5mm 3 mm fixing screws are recommended Push over type plastic stand offs may be used if it eases production The following points should be noted The controller should be freely accessible a...

Страница 7: ...re A RS485 black wire B RS485 shield in RS485 shield out RS485 jumper on shield out 24VAC feed Actuator drive open 24VAC feed 24VAC common 0v Earth Actuator drive closed Fan speed common output Fan sp...

Страница 8: ...ll settings of the Master Each slave will report its faults to the Control Plate Any unit may be set to a Master to suit site conditions this must be the only Master unit of the group Return air and O...

Страница 9: ...s the heating will be turned off The display will read Off Coil Sensor Fault Where the Return Air Temperature sensor fails the heating will still be functional The display will read Return Air Sensor...

Страница 10: ...xx C Range 10 to 70 C Default 18 C Winter Off Coil Setpoint is displayed as Winter OC xx C Range 10 to 70 C Default 40 C Summer Return Air Setpoint Trip is displayed as Summer Ret xx C Range 40 to 40...

Страница 11: ...en for Summer mode and closed for Winter mode BMS 0 10v fan input if enabled ENA the fan speed is taken from a 0 10v signal on the fan speed analogue input see 3 1 The fan speeds are set as follows Fa...

Страница 12: ...after 30 seconds of inactivity ie no buttons pressed 4 4 7 User Mode User display mode default display when powered up will be Fan Status it will read Fan Off or Fan Speed x on the top line and Mode...

Страница 13: ...oil and Return Air sensors only fitted will result in the temperature of the air leaving the supply grill being controlled to the given set point for Summer or Winter modes however when the return air...

Страница 14: ...1 Default Set points Setpoints 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Outside temperature C temperature C off coil setpoint retu...

Страница 15: ...New Look Mode Set points DIP 5 on 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 temperature C Outside temperature C Setpoints off coil setpoint r...

Страница 16: ...64 Sw8 128 Using various combinations of switches to on the requires address up to a decimal value of 255 may be set see next illustration Dipswitch Settings Switch ON position Switch Number 1 2 3 4 5...

Страница 17: ...5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8...

Страница 18: ...7 1 Fitting the sensor For best results locate the sensor on the north side of the structure high under an eave This prevents incorrect readings due to direct sunlight and damage from the elements Mo...

Страница 19: ...Default 16 C R W 9 Winter Return Air Set point Trip range 10 to 40 C Default 25 C R W 10 Summer Outside Air Set point range 5 to 40 C Default 20 C R W 11 Winter Outside Air Set point range 5 to 40 C...

Страница 20: ...his may either be the main BMS system holding the units off or the N O or N C may need to be altered The contacts can be altered by accessing the engineering mode Should units be master slaved it will...