Operations & Maintenance Manual

 

January 2002

 

Doc: TC02 O&M

 

Page 12 of 20

 

Status: 

Final

 issue: 11 

 

©TB Controls 2011 

Factory Reset 

returns controller to factory defaults pressing the + button will restore the 

factory default settings. Pressing the 

– button restores the last power up settings. Displays 

“*Factory Reset*” 
 
Factory reset will invoke a system temperature sensor recount, and will alter the operating 
parameters accordingly, ie if an outside air sensor is fitted or omitted. 
 

Firmware Version

, “Firmware V4.13”, This menu is only available on firmware V4.12 and 

above. Displays the TC02 software version number. 
 

MODBUS network address

, “MODBUS add:1”, This menu appears only if the MODBUS 

protocol  option  has  been  purchased.  Sets  the  MODBUS  open  protocol  RS485  network 
address. This must be different for each unit on the network, range is 1 to 247. 

 
MODBUS  network  baud  rate

,  “MOD  baud:19200”,  This  menu  is  only  available  on 

firmware  V4.13  and  above.  Sets  the  MODBUS  open  protocol  RS485  network  baud  rate. 
Default is 19200 baud, available baud rates are 2400, 4800, 9600, 19200, 38400, 57600, 
115200. 
 
Engineer mode exits automatically after 30 seconds of inactivity, ie no buttons pressed. 

 

4.4.7.  User Mode 

 
User display mode default display when powered up will be 

Fan  Status

, it will read „Fan 

Off‟ or „Fan Speed x‟ on the top line and Mode on the bottom. Change Fan speed using 
the +/- buttons. If the user interface has been disabled the display is different see Lock the 
user interface above. 
 
The  options  are  four  speeds  and  Off.  The  unit  will  not  turn  the  fan  off  if  the  heating  has 
been on, this allows for cooling of the element. Run on time may vary ask engineering for 
the set time (normally 3 minutes). 

 

The 

Summer / Winter mode

 is selected by pressing the Mode button; the unit will display 

the status of the Heater “ Summer” or “Winter”. If an Outside temperature sensor is fitted 
then selection is not possible and the display will read “Automatic” 

 
The Duty Cycle

 display is selected by pressing the Mode button, the top line will display 

“Tp xx

C Dty xx%” this gives shows the Temperature at the grill „Tp‟ and the energy use as 

a percentage of the total available from the heater. These values will change relative to the 
temperature 

and  the  performance  of  the  heater.  “TP  xx

C  Dty  xx%”  Temperature  and 

Power Duty cycle. 

4.5. 

Final checks before Power UP 

Check all connections 
 

  Fan 
  Solid State Relay / Actuator 
  Sensor / Sensors 
  BMS signals where present 

Содержание TC02

Страница 1: ...B U I L D I N G C O N F I D E N C E TC02 Curtain heater controller Previously known as the mini FCU Operations Maintenance manual TBControls 2011...

Страница 2: ...ONTROL PLATE UNIT 6 3 1 TC02 Connections 7 4 MASTER SLAVE 8 4 1 Phased Start Sequence 8 4 2 Controller Start sequence 8 4 3 Error Messages 9 4 3 3 Master 9 4 3 4 Slave Messages 9 4 4 LCD Modes 9 4 4 5...

Страница 3: ...user interface to be locked Requested by Diffusion TC02 firmware V3 23 8 16 July 08 Final MODBUS BMS interface details LON comms error for slave device added Return air sensor now NOT required on slav...

Страница 4: ...s The curtain heater controller unit has the following features Powered from 12 24 volts AC or DC Four fan speed settings with silent fan speed switching Controlled by four snubberless triacs with hea...

Страница 5: ...230 VAC lamps as in the Ambassador unit On board real time clock for timed operation and event log time stamping Log of the last 500 system events Fan speed monitoring input to detect fan motor failur...

Страница 6: ...height is 5mm 3 mm fixing screws are recommended Push over type plastic stand offs may be used if it eases production The following points should be noted The controller should be freely accessible a...

Страница 7: ...re A RS485 black wire B RS485 shield in RS485 shield out RS485 jumper on shield out 24VAC feed Actuator drive open 24VAC feed 24VAC common 0v Earth Actuator drive closed Fan speed common output Fan sp...

Страница 8: ...ll settings of the Master Each slave will report its faults to the Control Plate Any unit may be set to a Master to suit site conditions this must be the only Master unit of the group Return air and O...

Страница 9: ...s the heating will be turned off The display will read Off Coil Sensor Fault Where the Return Air Temperature sensor fails the heating will still be functional The display will read Return Air Sensor...

Страница 10: ...xx C Range 10 to 70 C Default 18 C Winter Off Coil Setpoint is displayed as Winter OC xx C Range 10 to 70 C Default 40 C Summer Return Air Setpoint Trip is displayed as Summer Ret xx C Range 40 to 40...

Страница 11: ...en for Summer mode and closed for Winter mode BMS 0 10v fan input if enabled ENA the fan speed is taken from a 0 10v signal on the fan speed analogue input see 3 1 The fan speeds are set as follows Fa...

Страница 12: ...after 30 seconds of inactivity ie no buttons pressed 4 4 7 User Mode User display mode default display when powered up will be Fan Status it will read Fan Off or Fan Speed x on the top line and Mode...

Страница 13: ...oil and Return Air sensors only fitted will result in the temperature of the air leaving the supply grill being controlled to the given set point for Summer or Winter modes however when the return air...

Страница 14: ...1 Default Set points Setpoints 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Outside temperature C temperature C off coil setpoint retu...

Страница 15: ...New Look Mode Set points DIP 5 on 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 temperature C Outside temperature C Setpoints off coil setpoint r...

Страница 16: ...64 Sw8 128 Using various combinations of switches to on the requires address up to a decimal value of 255 may be set see next illustration Dipswitch Settings Switch ON position Switch Number 1 2 3 4 5...

Страница 17: ...5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8 9 10 ON 1 2 3 4 5 6 7 8...

Страница 18: ...7 1 Fitting the sensor For best results locate the sensor on the north side of the structure high under an eave This prevents incorrect readings due to direct sunlight and damage from the elements Mo...

Страница 19: ...Default 16 C R W 9 Winter Return Air Set point Trip range 10 to 40 C Default 25 C R W 10 Summer Outside Air Set point range 5 to 40 C Default 20 C R W 11 Winter Outside Air Set point range 5 to 40 C...

Страница 20: ...his may either be the main BMS system holding the units off or the N O or N C may need to be altered The contacts can be altered by accessing the engineering mode Should units be master slaved it will...

Отзывы: