9
SOME MODELS HAVE A SHIPPING
BRACKET INSTALLED TO PRO-
TECT THE BLOWER ASSEMBLY
DURING SHIPPING.
LOCATE AND REMOVE THE SHIP-
PING BRACKET FROM THE SIDE
OF THE BLOWER HOUSING
BEFORE OPERATING UNIT. SEE
FIGURE 3.
THE FOLLOWING MODELS
INCLUDE THE ADDITIONAL
BRACKET (WHICH MUST BE
REMOVED) ON THE BLOWER
ASSEMBLY:
RGFG-09EZCMS
RGFG-10EZCMS
RGFG-12ERCMS
CLEARANCE -
ACCESSIBILITY
The design of forced air furnaces with
models as listed in the tables under
Figure 4 are certified by CSA
Laboratories for the clearances to com-
bustible materials shown in inches.
See name/rating plate and clearance
label for specific model number and
clearance information.
Service clearance of at least 24 inches
is recommended in front of
all furnaces.
FOR PURPOSES OF SERVICING
THIS APPLIANCE, ACCESSIBILITY
CLEARANCES, WHERE GREATER,
SHOULD TAKE PRECEDENCE OVER
FIRE PROTECTION CLEARANCES.
!
WARNING
FURNACES MUST NOT BE
INSTALLED DIRECTLY ON CARPET,
TILE OR OTHER COMBUSTIBLE
MATERIAL. INSTALLATION ON A
COMBUSTIBLE MATERIAL OTHER
THAN WOOD FLOORING MAY
RESULT IN FIRE CAUSING DAM-
AGE, PERSONAL INJURY OR
DEATH.
-GFG upflow furnaces and are
designed and certified for installa-
tion on combustible (wood only)
floors.
Upflow furnaces are shipped with
a bottom closure panel installed.
When bottom return air is used,
remove the panel by removing the
two screws attaching the panel to
the front base angle. See filter sec-
tion for details (see Figure 5).
SITE SELECTION
1. Select a site in the building near
the center of the proposed, or
existing, duct system.
2. Give consideration to the vent
system piping when selecting the
furnace location. Vent from the
furnace to the termination with
minimal length and elbows.
3. Locate the furnace near the
existing gas piping. If running a
new gas line, locate the furnace
to minimize the length and
elbows in the gas piping.
4. Locate the furnace to maintain
proper clearance to combustibles
as shown in Figure 4.
FIGURE 3
REMOVING SHIPPING BRACKET
92-24379-01
CAUTION
!
Содержание RGFG
Страница 70: ...70 FIGURE 49 UPFLOW SIDE FILTER LOCATIONS CUT OUT AND DRILL DETAIL ROD FILTER SUPPORT ANGLE ASSEMBLY I332 ...
Страница 72: ...72 FIGURE 50 TROUBLESHOOTING CHART MODULATING INTEGRATED FURNACE CONTROL IFC TROUBLESHOOTING GUIDE ...
Страница 73: ...73 FIGURE 50 CONTINUED TROUBLESHOOTING CHART CONTINUED ...
Страница 90: ...90 TABLE 24 CONTINUED FURNACE FAULT CODES EXPANDED W DESCRIPTIONS AND SOLUTIONS CONTINUED ...
Страница 91: ...91 FIGURE 51 WIRING DIAGRAM STEPPER MODULATING GAS VALVE FUEL CODE HU FURNACE MODEL IS RGFG ...