L-2066 Operation

Compressor Time Delay

 

 

(Factory Default: 0 seconds)

This function is used when you have more than one unit on
board. To prevent electrical overload due to multiple
compressors starting when turning on power to the system,
or when power is interrupted, each SMX unit should be
programmed with a different time delay.

Time delay can be set in increments of 1 second. On older
systems (before 8/98) the time delay is set in 10-second
increments, up to 70 seconds.

To program time delay, go to each SMX switch, and follow
these steps:

• Enter the programming mode: Press OFF, Press SET

• Press DOWN, SET and UP simultaneously. The delay in

seconds will be displayed.

• Use the UP or DOWN keys to change the time to the

desired setting.

• Press OFF to exit the programming mode.

At initial power-up, you will see the countdown for each
compressor on the data display, if you are in the TEMP
mode. The countdown will not appear in the SET mode.

Fahrenheit/Celsius
Display

 

 

(Factory Default: Fahrenheit)

You can choose to view temperature in degrees Fahrenheit
or Celsius.

To select Fahrenheit or Celsius:

• Enter the programming mode: Press OFF, Press SET

• Press DOWN, TEMP and UP simultaneously.

• Use the UP or DOWN key to select F for Fahrenheit or C

for Celsius.

• Press OFF to exit programming mode.

Note

If you switch from Fahrenheit to Celsius for temperature
displays, the compressor restart differential will also oper-
ate on degrees Celsius. Thus, the factory-set compressor
restart differential will be 1.5° Celsius, which is too wide. To
correct this, reset the differential value from 12 to 6. This
will provide a differential of 0.75° C, or about 1.4° F.

This will also affect the Fan Response Differential, which is
factory set at a value of 4, or 0.5° Fahrenheit. When chang-
ing from Fahrenheit to Celsius, you should reset the Fan
Response Differential from 4 to 2. This will provide a fan
differential of 0.25° C, or about 0.5° F.

Compressor Differential

 

(Factory Default: 12 = 1.5°)

The compressor differential is the temperature change
needed for the compressor to cycle on and off. The factory
setting of 1.5° Fahrenheit should be adequate for most
applications. Differential selections are available in incre-
ments of 1/8°. Thus, to select one degree, you should
choose 8 (for 8-eighths).

To program the compressor differential:

• Enter the programming mode: Press OFF, Press SET

• Press SLOW and FAN simultaneously. The restart

differential will be displayed.

• Use the UP or DOWN key to change the setting.

• Press OFF to exit the programming mode.

Hint

Be careful not to set your compressor restart differential too
low, since it will cause the compressor to start and stop
quite often. This will place an undue load on your electrical
system and also wear out your compressor faster.

Fan Response Differential

  

(Factory Default: 4 = 0.5°)

When the fan is in the automatic mode, its speed is
governed by how far the room temperature differs from the
setpoint. The fan runs faster when the difference is great.
As the room cools or warms, the temperature approaches
setpoint, and the fan slows down automatically. The amount
of temperature rise in the room above setpoint needed to
cause the fan to increase in speed one step is called “fan
speed differential”. It can be adjusted from 1/4° to 4°, in
1/8° increments.

The fan speed range is divided by the SMX microprocessor
in five equal increments. If the fan response differential is
set at 1/2°, the fan speed will change 20% for each 1/2° of
temperature deviation from setpoint. Lowering the fan
speed differential will cause the fan to increase speed
quickly as temperature changes. Raising the fan speed
differential will result in slower fan speed changes for a
given temperature change. The factory setting of 1/2°
Fahrenheit is good for most applications, but you may wish
to try a slightly higher setting in your salon and a lower
setting in your stateroom.

To adjust fan response differential:

• Enter the programming mode: Press OFF, Press SET

• Press COOL and SLOW. The differential will be displayed

in increments of 1/8°.

• Use the UP or DOWN key to raise or lower this value.

• Press OFF to exit the programming mode.

Содержание Cruisair SMX II

Страница 1: ...SMX II Control Systems DX English INSTALLATION OPERATION Revised 12 17 02 L 2066 LP 11 DIRECT EXPANSION SYSTEMS For Direct Expansion SMX II Control Systems using these displays...

Страница 2: ...Anti Ice Routine 9 Seawater Temperature and Your Cruisair System 9 Programming the SMX II System 9 Factory Memory Reset 9 Programming Summary Table 10 Custom Programming Record 10 Compressor Time Del...

Страница 3: ...y different parts required for a complete installation so make sure that you have all the necessary items when installing the system Two different keypad displays are available for use with SMX II con...

Страница 4: ...integrated SMX II controls have the P L box already installed on the unit In selecting a location for the Power Logic box bear in mind that several sets of wires will be connected to it Refer to insta...

Страница 5: ...dard phone cable will not work with SMX controls Pressure Switches retrofit only Standard SX and FX units that have an integrated SMX II P L box include both the high and low pressure switches already...

Страница 6: ...Mode Indicator Lights when you press the COOL key to select the cooling mode 10 Heat Mode Indicator Lights when you press the HEAT key to select the heating mode 11 COOL Key Turns the system on in th...

Страница 7: ...he SMXir remote also has two quick hit buttons that allow easy access to the humidity control program and the automatic changeover mode The remote has three buttons that are not used on SMX II systems...

Страница 8: ...ressor is running When the compressor cycles off the Cooling Indicator goes off but the Cool Mode Indicator stays on Heat Mode Press the HEAT key to select HEAT Mode The Heat Mode Indicator will light...

Страница 9: ...he efficiency of the system operation depends on both the seawater and cabin temperatures In cooling the air conditioner will work best in seawater temperatures below 90 F 32 C At higher water tempera...

Страница 10: ...Compressor Differential SLOW FAN 12 4 to 24 Fan Response Differential COOL SLOW 4 2 to 8 SLOW FAN FAST Before 8 98 Low Fan Speed DOWN SET 32 30 to 56 High Fan Speed SET SLOW 60 41 to 90 Fan Mode Cont...

Страница 11: ...2 1 5 The compressor differential is the temperature change needed for the compressor to cycle on and off The factory setting of 1 5 Fahrenheit should be adequate for most applications Differential se...

Страница 12: ...actory default is 60 While listening to the fan noise level use the UP key to raise the displayed value past the point that you can hear an increase in the fan noise level Press the DOWN key to lower...

Страница 13: ...le 10 min Dehumidification cycle 30 min The factory settings are adequate for most moderate climates and boats For humid climates you may wish to shorten the overall time period and extend the dehumid...

Страница 14: ...he display will flash LO AC for low AC This is a sustained shutdown and the system will not resume operation even if the line voltage rises to normal levels To reset press the OFF key Fault Shutdowns...

Страница 15: ...are number Press OFF Press OFF SET and FAN simultaneously Press COOL twice until display reads 68 Press UP once The display should read Version Number Press SLOW until display reads F2 Press UP once T...

Страница 16: ...those expressly authorized herein TME shall not be responsible for any liability or expense except as is specifically autho rized and provided in this section TME reserves the right to improve its pro...

Страница 17: ...dry and checked periodically for electrical leakage If any electrical leakage is detected the component should be replaced or the fault causing the leakage corrected before the component is put back i...

Страница 18: ...cluding Parts and Labor Cruisair Tempered Water New complete system installation using any member of the SMX family 2 year warranty including Parts and Labor NOTE Excludes pump which has a 1 year warr...

Страница 19: ...460V 3Ph 50 60 Hz Dwg No 084901 P1050 Fig 6 SMX II Retrofit Typ 3 knob Dwg No 084001 P 1063 A 284 Fig 7 SMX II Retrofit F20C 48RC to 3 knob term strip Dwg No 082605 P 1065 A 279 Fig 8 SMX II Retrofit...

Страница 20: ...20 L 2066 Fig 1 SXR7 16CK 115 230V 50 60Hz...

Страница 21: ...21 L 2066 Fig 2 SX7 24CK 115 230V 50 60Hz...

Страница 22: ...22 L 2066 Fig 3 FX5 36CK 115 230V 50 60Hz...

Страница 23: ...23 L 2066 Fig 4 FX48RC 230V 50 60 Hz...

Страница 24: ...24 L 2066 Fig 5 FX20DC FX48EC 230V 460V 3Ph 50 60Hz...

Страница 25: ...25 L 2066 Fig 6 SMXII Retrofit Typical 3 knob...

Страница 26: ...26 L 2066 Fig 7 SMXII Retrofit F20C 48RC to 3 knob term strip...

Страница 27: ...27 L 2066 Fig 8 SMXII Retrofit F20C 48RC to condensing unit...

Страница 28: ...28 L 2066 Fig 9 Cable Diagrams Old and New P L Boards...

Страница 29: ...29 L 2066 Fig 10 SMXIR Mounting Template and Instructions...

Страница 30: ...or SMXIRB F SMXIR Keypad Display Black Full Door SMXIRW F SMXIR Keypad Display White Full Door SMXIR REM SMXIR Remote Control 5103400 Replacement Full Door for SMXIRB Black 5103400W Replacement Full D...

Страница 31: ...il info wardsmarine com Cruisair Suncoast Inc Location St Petersburg FL USA Territory Tampa St Petersburg and surrounding areas Phone 727 526 7875 Fax 727 528 9519 Email cruisairsuncoast aol com Kansa...

Страница 32: ...Fax 242 356 5271 Email rolandknowles bahamas net bs Bahrain International Agencies Location Manama Bahrain Phone 973 728691 Fax 973 728412 Email service intercol com Benelux ASA Boot Electro BV Locati...

Страница 33: ...espolo Cinzia C Sne Location Bevazzana de Latisana UD Italy Territory Northeast Italy Austria Croatia Slovenia Phone 390 431 53 644 Fax 390 431 53 460 Email nautica centis nauticacentis it Web www nau...

Страница 34: ...65 6861 1188 Fax 65 6861 4263 Email tritex pacific net sg Web www tritex com sg Slovenia Nautica Centis di Nespolo Cinzia C Sne Location Bevazzana de Latisana UD Italy Territory Northeast Italy Austr...

Страница 35: ...ne 758 452 0205 Fax 758 452 0206 Email stlucia regiselectronics com Zambia Southern Power Products Location Cape Town South Africa Territory Angola Botswana Mozambique Nambia S Africa Zambia Zimbabwe...

Страница 36: ...enviro va com www tmenviro com Taylor Made is a registered trademark of Nelson A Taylor Co Inc the Taylor Made Group Logo is a trademark of Taylor Made Group Inc the Cruisair logo is a registered trad...

Отзывы: