13
ENGLISH
ATTENTION:
- do not use single cables (with one single wire), ex. telephone cables, in order to avoid break-
downs of the line and false contacts;
- do not re-use old pre-existing cables.
- In case of long sections of cables (> 20 m) for N.O./N.C. controls (e.g. OPEN / CLOSE, STOP, PEDE-
STRIAN, etc.), in order to avoid gate malfunctions, it will be necessary to uncouple the various
controls using RELAYS or using our 750T-RELE device.
2. TESTING
When you have completed the connection:
• All the green LEDs must be on (each of them corresponds to a Normally Closed input). They go off
only when the controls to which they are associated are operated.
• The red opening command LEDs must all be unlit (each corresponding to a Normally Open input)
and illuminate only when the commands they are associated with are given; red LED DL8 must be
illuminated steadily.
3. TECHNICAL CHARACTERISTICS
Power input to board
230V AC - 50 Hz
Nominal power
400 W
Fast acting fuse for protection of input power supply 230V AC (F1 - 5x20)
F 3,15 A
Input voltage of motor circuits
230V AC
Input voltage of auxiliary circuits
24V AC
Fast acting fuse for protection of auxiliary circuits 24V AC (F2 - 5x20)
F 500 mA
Working temperature
-20°C ÷ +55°C
Box degree of protection
IP 44
4. TERMINAL BOARD CONNECTIONS
Terminals
Function
Description
1 - 2 - 3
POWER
SUPPLY
POWER input 230V AC - 50Hz (115V AC - 60 Hz).
1= NEUTRAL 2= EARTH 3= PHASE;
4 - 5
FLASHING
LIGHT
FLASHING LIGHT output 230 Vac 50 W max. The signal is already
modulated for direct use. The flashing frequency during closing is
double. 4= 230V AC, 5= 0V AC;
6 - 9
OPEN/CLOSE
OPEN/CLOSE pushbutton input (Normally Open contact);
7 - 9
PEDESTRIAN
PEDESTRIAN pushbutton input (Normally Open contact);
N.B. by factory setting the automation will open 120 cm.
8 - 9
STOP
STOP pushbutton input (Normally Closed contact);
10 - 11
SENSITIVE
EDGE
SENSITIVE EDGE input (resistive sensitive edge or fixed safety edge);
Works only when the gate is opening; temporarily stops the gate and
partially closes it by about 20 cm in order to allow the obstacle to be
removed. (10=Common);
NOTE: if a resistive sensitive edge is connected, set dip-switch no.
12 to ON;
If a fixed safety edge with NC contact is connected, set dip-switch
no. 12 to OFF;