CAUTION
9. ADJ USTING SENSITIVITY
2. If the sensor does
not detect a person
entering the detection
area, increase the
sensitivity.
After rechecking, if there is still a problem, please contact us or your dealer.
14. ECDECLARATIONOF CONFORMITY
Reduce the detection area. Remove themoving object.
Reduce the detection area.
Decrease the sensitivity.
Ensure that the frequency setting of each sensor is not the same.
Re-power the sensor.
Set Monitor Mode to "Snow"
Problem
Possible Cause
Solution
Door opens and closes
for no apparent
reason (Ghosting)
The sensor detects themovement of the door.
Adjust the detection depth away fromthe door.
Door does not
operate
Door Operates
intermittently
Door operate by itself
Dust, frost or water droplet are on the sensor
lens.
Sensitivity too low.
Inappropriate detection area.
Wipe the DetectionWindow clean and install a weather cover if
necessary.
Increase the sensitivity.
Adjust the detection pattern.
Object moving in the detection area.
Detection area is too far fromthe door, causing
detection of passing pedestrians.
Sensitivity too high.
Another sensor is installed in close proximity.
Addition or removal of amat
Falling snow or footprints in snow.
Connection failure
Incorrect power supply voltage.
13. TROUBLESHOOTING
3. If the sensor detects
even though no one
is in the detection
area, decrease the
sensitivity.
1. Set the appropriate
sensitivity setting for the
mounting height of the
sensor.
.
3. Width adjustment Adjust the
detectionwidth by turning Area
Mask with a screwdriver.
8. ADJUSTING THE DETECTION PATTERN
2. Depth adjustment – Number
of Rows of Detection Section 6.
DIP SWITCH SETTINGS Delete
or add rows of detection
1. Depth Adjustment – Sensor Body
Adjust the detection pattern to either
0°or +5°by moving the sensor body
as illustrated.
The detection range will vary depending on the installation environment, object detected and sensor settings
(clothes and floor material as well as sensor sensitivity settings will all have an effect)
Ensure that the inner row of detection does not detect door movement
Door
Door
After installation and sensor setting adjustment, walk test the sensor to ensure that the detection area is as required.
If unreliable detection or false door activations occur then re-adjust the sensor detection range and sensitivity settings.
10. VERIFICATIONOF OPERATION
[m]
Wide
Narrow
Technical problems with the
DOORRAD/STA sensor are
indicated by a flashing Green/Red
LED. The frequency of flashing
indicates the type of problem.
12. SELF DIAGNOSTICS ERRORS
4 Rows ON
3 Rows ON
2 Rows ON
1 Rows ON
Power
OFF
Non-
Detection
Non- Detection
Non-
Detection
1
2
3
4
Detection
Detection
1. Safety Output Row 1,2 / TEST Input
1
2
3
4
Compiler of Technical File (EC Community)
Loris Virgilio Danieli
TAU S.r.l. - Via Enrico Fermi, 43 - 36066
Sandrigo (VI) - Italy
Tel: +39 0444 750190 - Fax: +39 0444 750376
Directives Fulfilled:
DIRECTIVE 2006/42/EC
DIN 18650-1:2010 Powered pedestrian doors Part 1:
Product requirements chapter 5.7.4
EN 12978:2003 +A1:2009
Industrial, commercial and garage doors and gates - safety devices for power
operated doors and gates
- Requirements and test methods
EN 62061:2005
Functional safety of electrical/electronic/programmable electronic safety-related
systems
EN ISO 13849-1:2008
Safety of machinery - Safety-related parts of control systems.
Harmonized Standards Used:
EN ISO 13849-1:2008
Declaration made by
L ocation of Declaration
Tau S.r.l.
Via Enrico Fermi, 43
Sandrigo (VI) - Italy
06/02/2019
Disclaimer
The manufacturer cannot be held responsible for below.
1.
Misinterpretation of the installation instructions, miss connection, negligence, sensor modification and inappropriate installation.
2.
Damage caused by inappropriate transportation.
3.
Accidents or damages caused by fire, pollution, abnormal voltage, earthquake, thunderstorm, wind, floods and other acts of providence.
4.
Losses of business profits, business interruptions, business information losses and other financial losses caused by using the sensor or
malfunction of the sensor.
5.
Amount of compensationbeyondsellingpriceinall cases.
D-MNL0DOORRADST
Rev. 01 del 01/10/2019
Description of Product:
DOORRAD/STA Combinedmotion and presence detection sensor for the activation and safety
of automatic doors.
Technology used is Active Infrared Technology.
Other Technical Standards Used:
DIN 18650-1:2010
EN 16005:2012
Date
Door opens and
remains in the open
position
Replace the sensor.
Increase the sensitivity.
Replace the sensor
The sensor sensitivity setting is too low.
Fast
Slow
Green
Red
Green
Red
Flash Frequency
LED
Cause
11. TIMING CHART OF EVENTS
5°
[0°]
1.0
2.0
0
1.0
2.0
3.0
1.0
2.0
[+5°]
[m]
0
1.0
2.0
3.0
2.0
2.0
1.0
1.0
0
2.0
2.0
1.0
1.0
0
Wide
Narrow
H
L
M
H
L
M
N.O.
N.C.
5
Blue
Yellow
Blue
Yellow
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
TEST
Response
Detection as
respose to
TEST
TEST
TEST
TEST
Non-TEST
Non-TEST
Non-TEST
OFF
8
ON
Gray(+)
Brown(-)
Supplying DC12 to 24V,
make current flow from
Gray to Brown.
Break the
current flow
on test state.
T1 : 10±1ms App.
T2 : 11±1ms App.
T2
T1
2. ActivationOutput Row 2, 3, 4
Power
OFF
1
2
3
4
.
6
.
Green
White
Green
White
1
2
3
4
2.0〜2.5
2.5〜3.0
L〜M
M〜H
Height
[m]
Criterion of
sensitivity
Adjust the sensitivity that is appropriate to the installation environment.
CAUTION
N.O.
N.C.
Tighten or reconnect the connector.
Apply proper voltage to the sensor. (AC/DC 12~24V)
Internal sensor error.
Reflection of the transmitted infrared signal
from the floor is too low.