PREMIER SX INSTALLATION MANUAL.
Approved Document No: GLT.MAN-101T
PAGE 6
Issue : 1.6s Authorised: GH Date: 06/11/2002
The wiring for this input should be connected to the relevant terminal block on the Main Control PCB
and their screens terminated at the Panel’s base earth tag (see page 9 for more details).
2.6 AUXILIARY OUTPUT WIRING (DRY CONTACTS ONLY)
Auxiliary Fire Output (AUX): Turns on during any fire. Can be used for driving local fire fighting
equipment such as sprinkler systems, door release systems, roller shutter doors, etc.
Fault Output (FAULT): This Output is normally energised. When a Fault occurs, the Output turns
off to ensure failsafe operation even in the event of total power loss. That is, the normally open
contact will be closed when there is no fault, and open when there is a fault. This should be taken into
account when any device is connected to the fault relay.
Typical auxiliary output wiring
12 &0 1&
)$8/75(/$<
)$8/7
,1',&$7,21
'(9,&(
127(7+(1&&217$&7
,623(1:+(17+(5(,6
12)$8/7
7ULJJHU,3
12 &0 1&
),5(5(/$<
$872
',$/(5
7ULJJHU,3
12 &0 1&
),5( 5(/$<
12 &0 1&
)$8/7 5(/$<
28767$7,21
),5(
,1387
)$8/7
,1387
72$''5(66$%/(
),5($/$503$1(/
/223
/223
The wiring for each output should be connected to the relevant terminal block on the Main Control
PCB and their screens terminated at the Panel’s base earth tag (see page 9 for more details).
The fault relay is
used to connect
to a remote
indication device
The fire relay can be
used to connect to
various devices which are
activated on a fire alarm.
Eg. Auto dialer , magnetic
door release (24V),
sprinkler system etc.
Here the relays are used to
communicate with a larger
addressable fire alarm system. An
example use of this might be a
warehouse, which uses several
flame detectors, and needs to be
part of a larger system.