©Copyright Task Force Tips, Inc. 2008-2014
LIY-500 May 12, 2014 Rev10
30
4.7.6.2 MONITOR GROUP CONFIGURATION
In a multiple monitor control system, all the wireless devices share the same ID code. Individual control of each monitor is then
selected by confi guring each monitor to only respond to control commands addressed to a specifi c “group”. A monitor group consists
of all equipment associated with water fl ow equipment and accessories associated with one specifi c monitor. This could include a
TFT RC Monitor, RC Valve Under Monitor, and a RC Extend-A-Gun.
Group Confi guration on Wireless Handheld Unit with Display:
1) Press POWER button to turn on wireless handheld operator station.
2) Press and hold DISPLAY MENU SELECT/ENTER button for 5 seconds to enter the confi guration menu.
3) Once in the confi guration menu, repeatedly press and release the DISPLAY MENU SELECT/ENTER button until “GROUP
CONFIG” is displayed in the command options and press the corresponding DISPLAY COMMAND button.
4) Select the number of monitors the wireless handheld unit will be confi gured to control. If only one monitor is selected then
the confi guration program will require the group number to assign to this controller.
5) After the number of monitors has been confi gured a name that is easier to remember can then be assigned to each group
number.
Group Confi guration on Monitor(s)
1) Press POWER button to turn on wireless handheld operator station.
2) Select the monitor group number to assign to a monitor.
3) Apply power to monitor.
4) Press and hold both FOG & STRAIGHT STREAM buttons simultaneously for 5 seconds.
5) Continue to press the FOG & STRAIGHT STREAM buttons and then press DOWN button for 2 seconds, OSC light will
begin to fl ash.
6) Release buttons. After several seconds the OSC will cease fl ashing indicating that it has learned a new group assignment.
7) Test operation by pressing direction control buttons on wireless handheld operator station.
8) Repeat this process for each of the other monitors that will be custom assigned group numbering.
4.7.7 CHANGING BATTERIES:
Four (AA) Batteries, Lithium Recommended
1) Remove two (2) screws on backside of handheld unit and slide bottom half of rubber bumper off enclosure.
2) Replace batteries verifying that polarity is correct.
3) Replace rubber bumper and retaining screws.
NOTICE
Properly dispose of old batteries. Do not puncture, incinerate, or disassemble batteries.
Do not mix battery types.