12.0  MAINTENANCE

TFT nozzles are designed and manufactured to be damage resistant and require minimal maintenance. However, as the primary 

firefighting tool upon which your life depends, it should be treated accordingly. To help prevent mechanical damage, do not drop or 

throw equipment.

12.1 FIELD LUBRICATION

All Task Force Tip nozzles are factory lubricated with high quality silicone grease. This lubricant has excellent washout resistance 

and long term performance. If your department has unusually hard or sandy water, the moving parts may be affected. Foam agents 

and water additives contain soaps and chemicals that may break down the factory lubrication. 
The moving parts of the nozzle should be checked on a regular basis for smooth and free operation, and signs of damage. IF THE 

NOZZLE IS OPERATING CORRECTLY, THEN NO ADDITIONAL LUBRICATION IS NEEDED. Any nozzle that is not operating 

correctly should be immediately removed from service. 

12.2  SERVICE TESTING

In accordance with NFPA 1962 (2013), nozzles must be tested a minimum of annually. Nozzles failing any part of this test must be 

removed from service, repaired and retested upon completion of the repair. 

12.2.1  HYDROSTATIC TESTING

Each nozzle with a shut off mechanism shall be tested in the following manner.

1. The nozzle shall be placed in a device capable of holding it and the shut off shall be closed.
2. A device capable of exerting a hydrostatic pressure of 300 psi (2070 kPa) or 1.5 times the maximum operating pressure, 

whichever is higher, shall be attached to the nozzle.

3. All air shall be bled from the system.
4. The gage pressure shall be increased by 50 psi (3.5 bar or 345 kPa) increments, held for 30 seconds at each pressure up to 

the maximum pressure for which the nozzle is being tested, and then held for one minute without leakage.

5. There shall be no sign of leakage through the valve or shut off.

12.2.2  FLOW TESTING

Flow testing must be conducted in the following manner.

1. The  nozzle  shall  be  mounted  so  that  the  flow  rate  and  pressure  through  the  nozzle  and  the  pressure  at  the  inlet  can  be 

accurately measured.

2. With the shut off fully open, the inlet pressure shall be adjusted to the rated pressure ±2 percent.
3. The valve or shut off and pattern controls shall be operated through their full range of motion at 100 psi (6.9 bar or 690 kPa) 

with no signs of leaking, binding or other problems.

4. Evaluate the flow of nozzles as defined by NFPA 1964 in the following manner: 

Basic Spray Nozzles shall flow no less than and no more than 10 percent over the rated flow at the rated pressure in the 

straight stream and wide-angle fog settings.

12.2.3  RECORDS

A record of testing and repairs must be maintained from the time the nozzle is purchased until it is discarded. Each TFT nozzle is 

engraved with a unique serial number which, if so desired, can be used to identify nozzle for documentation purposes.

The following information, if applicable, must be included on the test record for each nozzle:

1.  Assigned identification number
2.  Manufacturer
3.  Product or model designation
4.  Vendor
5.  Warranty
6.  Hose connection size
7.  Maximum operating pressure
8.  Flow rate or range
9.  Date received and date put in service
10. Date of each service test and service test results
11.  Damage and repairs, including who made the repairs and the cost of repair parts
12. Reason removed from service

NFPA 1962: Standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles and fire hose appliances. (2013 

ed., Section 5.5.4). Quincy, MA: National Fire Protection Agency.

Содержание VORTEX

Страница 1: ...and understand the following 1 Firefighting and Emergency Response are inherently dangerous activities requiring proper training in their hazards and the use of extreme caution at all times 2 It is your responsibility to read and understand any user s instructions including purpose and limitations provided with any piece of equipment you may be called upon to use 3 It is your responsibility to kno...

Страница 2: ... FLOW CHARACTERISTICS AND CHARTS 5 0 NOZZLE CONTROLS 5 1 FLOW CONTROL 5 1 1 LEVER TYPE FLOW CONTROL 5 1 2 TIP ONLY 5 2 PATTERN CONTROL 6 0 USE WITH FOAM 7 0 USE OF NOZZLES 8 0 APPROVALS 9 0 COLOR CODED VALVE HANDLE AND PISTOL GRIP 10 0 EXPLODED VIEWS AND PARTS LISTS 11 0 WARRANTY 12 0 MAINTENANCE 12 1 FIELD LUBRICATION 12 2 SERVICE TESTING 12 2 1 HYDROSTATIC TESTING 12 2 2 FLOW TESTING 12 2 3 RECO...

Страница 3: ...eam and can result in injury death or loss of property See flow graphs or call 800 348 2686 for assistance WARNING The nozzle may be damaged if frozen while containing significant amounts of water Such damage may be difficult to detect visually and can lead to possible injury or death Any time the nozzle is subject to possible damage due to freezing it must be tested by qualified personnel before ...

Страница 4: ...ilable by request Two Vortex 2 5 models are available SVFV NJ Vortex with integrated detent ball valve SVFG NJ Vortex with integrated detent ball valve and pistol grip INLET THREADS OUTLET THREADS FOR CONNECTING TO SMOOTH BORE NOZZLE not included TWIST STREAM SHAPER TO SELECT STRAIGHT STREAM OR VORTEX DISPERSED PATTERN COUPLING PISTOL GRIP ON OFF FLOW CONTROL VORTEX TIP ONLY VORTEX WITH INTERGRATE...

Страница 5: ...50 200 Flow GPM 10 0 0 Figure 4 0 1 3 8 Waterway Flow Chart 3 3 NOZZLE COUPLINGS NH National Hose Threads per NFPA 1963 threads are standard on all nozzles Other threads such as NPSH National Pipe Straight Hose threads per ANSI ASME B1 20 7 can be specified at time of order CAUTION Nozzle must be properly connected Mismatched or damaged threads may cause nozzle to leak or uncouple under pressure a...

Страница 6: ...slowly to eliminate unnecessary strain on the hose and couplings and reduce pressure surges TFT recommends the use of a pistol grip for easier handling For additional stress reduction a hose rope or strap may also be used This permits more effective use and ease of advancement while minimizing strain and fatigue 5 1 FLOW CONTROL Open valve slowly to avoid sudden changes in nozzle reaction Close va...

Страница 7: ...ckwise moves the shaper to the straight stream position shown in figure 5 2 3 Twisting the shaper counterclockwise will result in an increasingly wider pattern until reaching the full Vortex pattern shown in figure 5 2 4 Allows up to 5 8 debris to pass TWIST CLOCKWISE FOR STRAIGHT STREAM TWIST COUNTER CLOCKWISE FOR FULL VOTREX Allows up to 5 8 debris to pass Figure 5 2 3 Straight Stream pattern se...

Страница 8: ...e fireground tactics and operations 8 0 APPROVALS Vortex 1 5 and 2 5 NH threaded nozzles meet the requirements of NFPA 1962 2013 and NFPA 1964 2008 WARNING There are a wide variety of foam concentrates Each user is responsible for verifying that any foam concentrate chosen to be used with this unit has been tested to assure that the foam obtained is suitable for the purpose intended WARNING Use of...

Страница 9: ...ION SHIM 2 P170 18 TRUNNION RIGHT 1 P120R 19 BACKUP RING 330 PTFE SINGLE TURN 1 VOB 330T 20 BASE 1 5 NHF X 1 5 NHM 1 SVF100NF 21 STREAM PATTERN LABEL 1 SVF131 22 VORTEX PATTERN LABEL 1 SVF132 23 ROLLER 6 SVF114 24 VANE 6 SVF110 25 O RING 015 6 VO 015 ITEM DESCRIPTION QTY PART 26 CAM SCREW 3 HD780 27 CAM FOLLOWER 3 SVF121 28 DOWEL PIN 6 VP156X1 00 29 BACKUP RING 332 PTFE SINGLE TURN 1 VOB 332T 30 S...

Страница 10: ...e discharge of its obligations under this limited warranty If TFT makes this election claimant shall return the equipment to TFT free and clear of any liens and encumbrances This is a limited warranty The original purchaser of the equipment any person to whom it is transferred and any person who is an intended or unintended beneficiary of the equipment shall not be entitled to recover from TFT any...

Страница 11: ...45 kPa increments held for 30 seconds at each pressure up to the maximum pressure for which the nozzle is being tested and then held for one minute without leakage 5 There shall be no sign of leakage through the valve or shut off 12 2 2 FLOW TESTING Flow testing must be conducted in the following manner 1 The nozzle shall be mounted so that the flow rate and pressure through the nozzle and the pre...

Страница 12: ...A National Fire Protection Agency WARNING Any nozzle failing any part of the checklist is unsafe for use and must have the problem corrected before use or being placed back into service Operating a nozzle that has failed the checklist is a misuse of this equipment 12 3 REPAIR Factory service is available with repair time seldom exceeding one day in our facility Factory serviced nozzles are repaire...

Отзывы: