background image

2

1.0

2.0

2.1

2.2

2.3

2.4

2.4.1

3.0

3.1

3.2

3.3

3.4

4.0

5.0

6.0

MEANING OF SAFETY SIGNAL WORDS

GENERAL INFORMATION

USE WITH SALT WATER

VARIOUS MODELS AND TERMS

PATTERN CONTROL

USE WITH FOAM

FOAMJET LX WITH MASTERSTREAM

NOZZLE

FLOW CHARACTERISTICS OF INDUSTRIAL

NOZZLE

FLOW CHARACTERISTICS OF MASTERSTREAM

SELECTABLE NOZZLE

FLOW CHARACTERISTICS OF MASTERSTREAM

FIXED NOZZLE

DETERMINING FLOW WITH PRE-PIPED

MONITORS

STREAM TRAJECTORY DATA

FLUSHING DEBRIS

MAINTENANCE

WARRANTY

1.0 MEANING OF SAFETY SIGNAL WORDS

A safety related message is identified by a safety alert symbol and a signal word to indicate the level of risk involved with a
particular hazard. Per ANSI standard Z535.4-1998 the definitions of the three signal words are as follows:

DANGER

CAUTION

WARNING

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or
serious injury.

WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.

CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.

2.0 GENERAL INFORMATION

WARNING

The Task Force Tips Industrial and Masterstream nozzles are deluge nozzles with clean far reaching straight stream. They are
adjustable from straight stream to a dense fog pattern. Their rugged construction is compatible with the use of fresh water as well as fire
fighting foam solutions. A summary of each nozzle's characteristics is shown in the tables below.

This equipment is intended for use by trained personnel for firefighting. Their use for other
purposes may involve hazards not addressed by this manual. Seek appropriate guidance and
training to reduce risk of injury.

SERIES

FLOW

(GPM)

FLOW
(LPM)

PRESSURE

(PSI)

PRESSURE

(BAR, KPA/100)

INDUSTRIAL

MASTERSTREAM

1000

350, 500, 750

100

1300, 2000, 3000

7

CUSTOMER SPECIFIED:

1000 GPM MAX

CUSTOMER SPECIFIED:

150 PSI MAX

CUSTOMER SPECIFIED:

4000 LPM MAX

CUSTOMER SPECIFIED:

10 BAR MAX

FIXED FLOW NOZZLES

FLOW

(GPM)

FLOW
(LPM)

PRESSURE

(PSI)

PRESSURE

(BAR, KPA/100)

250, 350, 500, 750, 1000

100

1000, 1500, 2000, 3000, 4000

1200, 1800, 2400, 3600, 4800

10

7

MASTERSTREAM SELECTABLE FLOW NOZZLES

TABLE OF CONTENTS

NOTES ON TABLES:

!

!

!

!

2 ½ inch NH female threads are standard. Other threads and coupling sizes can be specified at time of order.
Industrial series nozzle is available in UNS C83600 brass or hardcoat anodized ANSI 356 aluminum.
Masterstream series nozzle is constructed of hardcoat anodized 6061-T6 aluminum.
Masterstream series nozzle is also available in automatic pressure control models. See catalog for details.

©Copyright Task Force Tips, Inc. 1998-2004

LIM-035 October 5, 2004 Rev02

Содержание MASTERSTREAM 1000 Series

Страница 1: ...Deluge Nozzles With Fixed Selectable Flow 350 500 or 750 GPM 100 PSI 1300 2000 or 3000 LPM 7 BAR 700 KPA INDUSTRIAL 250 350 500 750 1000 GPM 100 PSI 1000 GPM MAX 100 PSI 1000 1500 2000 2500 3000 4000...

Страница 2: ...an far reaching straight stream They are adjustable from straight stream to a dense fog pattern Their rugged construction is compatible with the use of fresh water as well as fire fighting foam soluti...

Страница 3: ...be carried back to the nozzle will depend on the following factors Voltage of the line or equipment Distance from the nozzle to the line or equipment Size of the stream Whether the stream is solid or...

Страница 4: ...to complete task see NFPA for minimum duration time requirements Foam logistics have been carefully planned Allow for such things as Storage of foam in a location not exposed to the hazard it protects...

Страница 5: ...zle s baffle Figure 3 gives relationship of flow and pressure for various orifice sizes The Masterstream 1000 Selectable Nozzle allows the user to select one of several orifice sizes by turning a knob...

Страница 6: ...D P Flow water with a smooth bore nozzle and record the nozzle s size pitot pressure and in line pressure gauge reading The smooth bore nozzle s flow is calculated from the Freeman formula Where F 29...

Страница 7: ...000 GPM at 100 PSI For other orifice sizes and pressures the graphs may be interpolated Notes on trajectory graphs Graphs show approximate effective stream trajectory at 30 degrees elevation in no win...

Страница 8: ...imited warranty the claimant must return the equipment to TFT at 2800 East Evans Avenue Valparaiso Indiana 46383 within a reasonable time after discovery of the defect TFT will examine the equipment I...

Отзывы: