Do not couple aluminum to brass. Dissimilar metals coupled together can cause galvanic
corrosion that can result in inability to unscrew threads or complete loss of thread engagement.

CAUTION

Nozzle must be properly connected. Mismatched or damaged threads may cause nozzle to leak or
uncouple under pressure and could cause injury.

CAUTION

Injury can occur from an inadequately supported nozzle. The mounting must be capable of
supporting the nozzle reaction force which can be in excess of 550 LBS (1000 GPM at 100 PSI).

Some volatile liquids can be ignited by static discharge. Static build-up can occur from:

Electrochemical separation of charge as water drains through low conductivity, refined
products.

Applying foam over a low conductivity liquid of sufficient depth to retain the charge created as
the foam blanket drains.

Streaming currents as water or foam is introduced into the storage tank.

!

!

!

1

WARNING

WARNING

Water is a conductor of electricity. Application of water solutions on high voltage equipment can
cause injury or death by electrocution. The amount of current that may be carried back to the nozzle
will depend on the following factors:

Voltage of the line or equipment

• Distance from the nozzle to the line or equipment

Size of the stream

• Whether the stream is solid or broken

• Purity of the water

!
!

2

WARNING

1

2

Electrostatic Hazards of Foam Blanketing Operations by Peter Howels. Industrial Fire Safety July/August 1993
The Fire Fighter and Electrical Equipment, The University of Michigan Extension Service, Fourth Printing 1983. Page 47.

2.1 USE WITH SALT WATER

2.2 VARIOUS MODELS AND TERMS

Use with salt water is permissible provided nozzle is thoroughly cleaned with fresh water after each use. The service life of the nozzle
may be shortened due to the effects of corrosion and is not covered under warranty.

See figures 1A, 1B and 1C for views of the Industrial and Masterstream nozzles. The Masterstream Series Nozzle is available without
halo ring. See catalog for model numbers and details.

FIG 1A - Industrial Nozzle

Halo Ring

Coupling

Stream Shaper / Bumper

Baffle

N

ozzle

F

or
W

ater

and

F

oam

S

o

lutions

Nozzle

Fo
r

W

ater

and

Fo
a

m
Solutions

STRIAL

NOZZL

STRIAL

NOZZL

FIG 1B - Masterstream 1000 Selectable Gallonage Nozzle

Halo Ring

Coupling

Stream Shaper / Bumper

Flow Selector

selectable

©Copyright Task Force Tips, Inc. 1998-2004

LIM-035 October 5, 2004 Rev02

Содержание INDUSTRIAL Series

Страница 1: ... Deluge Nozzles With Fixed Selectable Flow 350 500 or 750 GPM 100 PSI 1300 2000 or 3000 LPM 7 BAR 700 KPA INDUSTRIAL 250 350 500 750 1000 GPM 100 PSI 1000 GPM MAX 100 PSI 1000 1500 2000 2500 3000 4000 LPM 7 BAR 700 KPA 1200 1800 2400 3000 3600 4800 LPM 10 BAR 1000 KPA 500 1000 1500 2000 2500 LPM 7 BAR 700 KPA 4000 LPM MAX 7 BAR 700 KPA MASTERSTREAM 1000 SELECTABLE MASTERSTREAM 1000 FIXED WARNING N...

Страница 2: ...ean far reaching straight stream They are adjustable from straight stream to a dense fog pattern Their rugged construction is compatible with the use of fresh water as well as fire fighting foam solutions A summary of each nozzle s characteristics is shown in the tables below This equipment is intended for use by trained personnel for firefighting Their use for other purposes may involve hazards n...

Страница 3: ...y be carried back to the nozzle will depend on the following factors Voltage of the line or equipment Distance from the nozzle to the line or equipment Size of the stream Whether the stream is solid or broken Purity of the water 2 WARNING 1 2 Electrostatic Hazards of Foam Blanketing Operations by Peter Howels Industrial Fire Safety July August 1993 The Fire Fighter and Electrical Equipment The Uni...

Страница 4: ... to complete task see NFPA for minimum duration time requirements Foam logistics have been carefully planned Allow for such things as Storage of foam in a location not exposed to the hazard it protects Personnel equipment and technique to deliver foam at a rapid enough rate Removal of empty foam containers Keeping clear path to deliver foam as hoses other equipment and vehicles are deployed Improp...

Страница 5: ...zzle s baffle Figure 3 gives relationship of flow and pressure for various orifice sizes The Masterstream 1000 Selectable Nozzle allows the user to select one of several orifice sizes by turning a knob at the front of the nozzle An indicator on the knob shows which flow has been selected Figure 3 gives relationship of flow and pressure for various orifice sizes 0 0 20 40 4 60 80 8 100 120 12 140 1...

Страница 6: ...Q D P Flow water with a smooth bore nozzle and record the nozzle s size pitot pressure and in line pressure gauge reading The smooth bore nozzle s flow is calculated from the Freeman formula Where F 29 71 for English units GPM INCHES PSI F 667 for metric units LPM MM BAR Note 1 BAR 100 KPA is smooth bore nozzle flow in GPM or LPM is nozzle exit diameter in INCHES or MM is pitot pressure in PSI or ...

Страница 7: ...1000 GPM at 100 PSI For other orifice sizes and pressures the graphs may be interpolated Notes on trajectory graphs Graphs show approximate effective stream trajectory at 30 degrees elevation in no wind conditions Distance to last water drops approximately 10 farther Trajectories shown are for water The addition of foam is expected to decrease the reach by approximately 10 Tail or head winds of 20...

Страница 8: ...limited warranty the claimant must return the equipment to TFT at 2800 East Evans Avenue Valparaiso Indiana 46383 within a reasonable time after discovery of the defect TFT will examine the equipment If TFT determines that there is a defect attributable to it TFT will correct the problem within a reasonable time If the equipment is covered by this limited warranty TFT will assume the expenses of r...

Отзывы: