This distance is the minimum separation
distance. All possible directions of approach
must be considered. The minimum separation
distance, S, can be calculated using the
following formula:

S  =  (1600  x  T)  +  1200

The overall system response time, T, should
be measured several times and the highest
value recorded, plus a suitable allowance for
brake deterioration, should be used in the
calculation of the minimum separation distance.

Figure 4  - Minimum Separation Distance

MINIMUM SEPARATION

DISTANCE   'S'

DANGEROUS

PARTS

MACHINE

WORST CASE
POINT OF
DETECTION

BEST CASE
POINT OF
DETECTION

FRONT EDGE OF ACTIVE ZONE

NEAREST DANGER POINT

Содержание CKP/Solo Sensors

Страница 1: ...safety system WARNING Tapeswitch safety mat systems are intended to protect operators working at or near dangerous machinery They can only perform thisfunctioniftheyarecorrectlyfittedandinterfacedtoas...

Страница 2: ...1 GENERAL 4 2 SENSOR INSTALLATION 5 PERIODICCHECKING 5 1 GENERAL 5 2 COMMISSIONING CHECKS 5 3 SIX MONTHLY CHECKS 5 4 DAILY SETTING CHECKS 6 OPERATION MAINTENANCEANDSERVICING 6 1 OPERATION 6 2 MAINTEN...

Страница 3: ...is not suitable for detectingchildren The CKP Solo mat is ideal for use with safety bus systems The mats can connect directly to the same kind of standard safety bus I O connection modules that are us...

Страница 4: ...he maximum width of a mat is 1200 mm the maximum length of a mat is 2400 mm the maximum total area is 2 88m Figure 1 Dimensions of the inactive area around outer edge of sensor The dimensions of senso...

Страница 5: ...lyopenswitch Heavy gauge tin plated copper wire is used for all internal wiring and all connections to the switching elements are direct solder joints The switches are self bottoming and as a resultth...

Страница 6: ...mance of the machine Anymachineregardlessoftheefficiencyofits brakingsystem willtakeacertainamountof time to come to rest after a stop signal is generated From the instant that a persons foot touches...

Страница 7: ...erall system response time T should be measured several times and the highest value recorded plus a suitable allowance for brake deterioration should be used in the calculationoftheminimumseparationdi...

Страница 8: ...fsafetyintegrity determined by the risk assessment d Steps must be taken to prevent access to the dangerous parts of the machine from any direction not covered by the sensor Such stepscouldincludefixe...

Страница 9: ...0mm Keepmatsensors flatwheneverpossible Alwaysstoreflat Mat sensors with one edge longer than 1 metre should be handled by two people Figure 5 Ensure operator is always standing on active area of sens...

Страница 10: ...sor This specially designed edging comes in two parts a base and a cover The cover provides a 20 degree ramp to prevent a tripping hazard at the outer sensor edges TypeAE 13 edging is illustrated in F...

Страница 11: ...cable is fitted with an M12 plug Theconnectionstothematsensor are shown in Figure 9 One cable is used for the d c supply and one cableisusedforthe Volt FreeSafetyOutputs NOTE In order to achieve EN95...

Страница 12: ...oissuitablefor thelevelofriskpresentedbythe machine ii Checkthattheenvironmentissuitable for the use of the CKP Solo b Checkthatthedimensionsandpositionof the CKP Soloare correct taking into account t...

Страница 13: ...es over thewholeactiveareabywalking heeltotoe over the whole area in two directions as shown in Figure 10 l Examinethestoppingperformancemonitor iffitted toensurethatitisfittedandfunctioning correctly...

Отзывы: