Installing the RT-2200 

Warning: Energized meters, meter sockets and distribution lines present 

the risk of electrical shock. All work on this equipment should be 
performed by qualified metering specialists or industrial electricians. 
Personnel working with this equipment should follow all utility company 
established operation and safety procedures. 

B E F O R E   Y O U   B E G I N  

1.  Advise the customer to turn off any sensitive electronic equipment including computers, 

stereos, televisions, etc. 

2.  Tell the customer that the power will be off for approximately 5 – 10 minutes. 

Note: For safety reasons, we recommend you attach a clear meter 
socket cover with a meter ring to the front of the RT-2200 unit prior to 
installation. 

I N S T A L L   T H E   R T - 2 2 0 0  

3.  Remove the existing meter from the meter socket. 

4.  Inspect the “jaws” of the meter socket to ensure that they are in good working condition 

(ie: the jaws should not be spread too far apart). 

[insert diagram of acceptable and unacceptable “jaws”) 

5.  Perform a voltage check, a line-to-line check, and a line-to-neutral check to ensure the 

voltage is at proper levels.  

6.  Visually inspect the back of the RT-2200 unit to ensure the power pins on the front and 

back are secure and everything is in place. 

[insert diagram of back of RT-2200 with cotter pins in place] 

7.  Grasp the RT-2200 unit on the top left and bottom right corners and plug it into the 

meter socket firmly. 

 

Содержание RT-2200

Страница 1: ...ation or any software included with it may be reproduced stored in a retrieval system or transmitted in any form or by any means including photocopying electronic mechanical recording or otherwise without the prior written permission of the copyright holder This document contains proprietary information of Tantalus Systems Corp ...

Страница 2: ...tion against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is not guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to ...

Страница 3: ...N E R A L I N F O R M A T I O N Tantalus provides two way real time data communications networks to monitor and control electric utilities Our long range wireless networks unite a utility s applications making meter reading load management and distribution automation cost effective and practical throughout urban and rural service areas The Tantalus Utility Network uses long range 220 MHz spectrum ...

Страница 4: ...s Out of band Spurious 65 dBc Frequency stability 1 5 ppm Standard antenna internal mounted Standards CFR Title 47 Part 15b unintentional radiators CFR Title 47 Part 90 Sub Part I T private land mobile radio services CSA C22 2 No 0 M91 product safety NEMA 4X environmental Power Power supply 240 VAC from AC line mains Power consumption Standby 2 watts Transmit 12 watts pulsed Outage reporting optio...

Страница 5: ...mend you attach a clear meter socket cover with a meter ring to the front of the RT 2200 unit prior to installation I N S T A L L T H E R T 2 2 0 0 3 Remove the existing meter from the meter socket 4 Inspect the jaws of the meter socket to ensure that they are in good working condition ie the jaws should not be spread too far apart insert diagram of acceptable and unacceptable jaws 5 Perform a vol...

Страница 6: ...equent response to Network Controller return to one way Solid ONG 9 Check the Communication LED at the bottom of the RT unit to ensure full two way communication with the NC 2200 I F T H E N The RT 2200 does not power up Remove the RT unit and replace it with another one The RT 2200 powers up but does not appear to find a Tantalus channel Remove the RT unit and replace it with another one The RT 2...

Страница 7: ...ay communication by checking the LED indicator I F T H E N The TC 2200 does not power up ie the LED does not turn on Remove the TC 2200 equipped meter and use another unit The TC 2200 powers up but does not appear to establish communications with the RT 2200 Remove the TC 2200 equipped meter and use another unit C O M P L E T E T H E I N S T A L L A T I O N 12 Once communication between the TC and...

Отзывы: