3
R T - 2 2 0 0 P R O D U C T S P E C I F I C A T I O N S
Functional
Data rate: 1600/3200 bps
Mechanical interfaces:
•
Form S connector for installing into meter socket
•
Form S socket for accepting meters equipped with TC-XXXX modules
Data interface: optical
Radio
Type: frequency agile, very narrow-band GFSK
Frequency range: 220-222 MHz
Channels: 200 with 5 kHz spacing
RF power output: +37 dBm (5 watts)
Out of band Spurious: < -65 dBc
Frequency stability: < +/- 1.5 ppm
Standard antenna: internal mounted
Standards
CFR Title 47 Part 15b (unintentional radiators)
CFR Title 47 Part 90, Sub-Part I & T (private land mobile radio services)
CSA C22.2 No. 0-M91 (product safety)
NEMA 4X (environmental)
Power
Power supply: 240 VAC from AC line mains
Power consumption
•
Standby: 2 watts
•
Transmit: 12 watts (pulsed)
•
Outage reporting (optional)
Physical
Size: 13.5” (H) 7.6” (W) 2.8” (D)
Weight: 6 lbs
Storage temperature range: -40
°
to +85
°
C
Operating temperature range: -30
°
to +60
°
C
Operating humidity range: 5 to 95% non-condensing relative humidity