Never fix the unit to its place by welding!
If the product is to be out of operation for a long time, drain the water and take precautions
against freezing.
6.4.
Installing the pipe connections
TANPERA storage water heaters and hot water storage tanks will be provided with internal thread
connection ports.
We advise you of the following:
Pipe connections must be made according to an approved installation project.
Risk of fire! The unit should not be approached with fire and any necessary precautions should
be taken in the event of welding. The insulation material and the sheath on the tank may burn.
There should be no shut-off valve between the safety valve and the tank, drain port of the valve
should not be blocked in any way and the drain piping should be downward inclined and as short
as possible.
9
We reserve the right to make changes in technical information.
Storage:
Should it be necessary to store the product for a longer period without installing, it should be stored
in upright position on the pallet with original packaging, in a closed place, which is absolutely free of
external weather conditions.
Rising of the unit:
The pallet should be removed before
mounting.
To remove the pallet, lay down the unit on the
ground, holding the
eyebolts
with the straps.
When doing this, take maximum care to ensure
that the vinyl sheath does not tear
(or the steel sheet sleeve does not deform).
Remove all tightening elements from the pallet.
Place the unit in its position on the floor, by
holding from the
eyebolts
with the straps
and
bringing it back to the vertical position and
lowering it on the legs.
Remove the straps, refit the thermoplastic cap and tighten the unit to the floor/pedestal using
the mounting holes on the feet.
When connecting the pipe system to the product make sure that no stress or strain is imposed,
by the pipe system, on the unit!
At least one safety valve must be used
having
the appropriate diameter and opening pressure, in the
system. According to the storage capacity, the minimum safety valve diameter to be used should be
¾” for
800
liters and below, 1" for
800
-3000 liters and 1 ¼” (or 2 pcs 1”) for over
3000
liters. The
opening pressure of the safety valve must not exceed 90% of the product operating pressure.