Initial Software Set up
Enable Extended Functions:
z
Enter program mode by pressing and releasing the PGM
button
z
Press the PGM button to advance to the 'CC' and turn
this menu item 'On' via the UP or DOWN button
z
Press the PGM button to advance to 'diF' (thermostat
differential) and adjust as desired via UP/DOWN buttons.
A minimum of one degree (1F) is recommended.
z
Press the PGM button to advance to 'EF' (Extended
Functions) and turn this setting 'On' via the UP or DOWN
button
z
Press & Hold the PGM button to exit programming mode.
Select Desired Night Air Cooling Mode (NA1 or NA2):
z
Enter program mode by pressing and releasing the PGM
button
z
Press the PGM button until either one of the MODE LEDs
begins to blink or the word “OFF” flashes in the
SETPOINT window.
z
Press and release the UP or DOWN button until the
desired MODE is selected. With extended functions (EF)
enabled, the controller will present several additional
operating modes. Use the UP or DOWN button to select
the desired Night Air Cooling mode which is indicated as
either “NA1” or “NA2” in TEMPERATURE display window.
z
Press & Hold the PGM button to exit programming mode.
Configuring Temperature Probes
z
Enter program mode by pressing and releasing the PGM
button
z
Press the PGM button to advance to the 'CC' and turn
this menu item 'On' via the UP or DOWN button
z
Press the PGM button to advance to 'CP' and set to 'P1'
via UP/DOWN buttons.
z
Press the PGM button to advance to 'HP' and set to 'P2'
via UP/DOWN buttons.
z
Press & Hold the PGM button to exit programming mode.