17 

2.2 

Connection and Testing 

2.2.1 

Connection Sequence 

 

 

WARNING

 - Ensure that all necessary safety procedures are followed at all times! 

a. 

Connect earth lead between test object earth and PT30-10 earth terminal. 

b. 

Connect  discharge/earthing  probe  to  the  PT30-10  earth  terminal.    The  earth  hook  on  the  probe 
must now be placed on the test object HV connection point. 

c. 

Connect the phases not being tested to earth.   This means 1 phase for bipolar test and 2 phases 
for a unipolar test. 

d. 

For a unipolar test connect the black/negative HV lead to the negative output socket on the PT30-
10  and  the  test  object.    The  positive  output  must  be  blanked  off  using  the  plastic  blanking  plug 
provided  (not  the  metal  dust  cap).    It  is  also  possible  to  carry  out  a  positive  unipolar  test,  as 
shown in figure 3, although it is more common to use a negative test as this is more onerous. 

e. 

For a bipolar test connect both the red/positive and black/negative HV leads to the output sockets 
on the PT30-10 and the test object as shown in figure 4. 

f. 

Connect the PT30-10 to mains supply. 

h.

 

Check that all connections are secure and that all safety procedures have been followed.  

Re-check that all personnel are out of the test area. 

 

 

6

8

10

4

2

0

8

10

2

4

6

0

Cable under test

Connect to low 

impedance 

local earth

DP40 Discharge 

Probe

Mains 

supply

Blanking plug

 

Figure 2 Connections for positive unipolar test 

 

Содержание PT30-10 mk2

Страница 1: ...Test Set Type PT30 10 mk2 PT30 10C mk2 with Current Limit DESIGNED AND MANUFACTURED BY T R Test Equipment Limited 15 16 Woodbridge Meadows Guildford Surrey GU1 1BJ United Kingdom Telephone 01483 2074...

Страница 2: ...2...

Страница 3: ...l is unit that must be connected to a local earth Ensure that the unit is properly grounded before making any connections to inputs or outputs Terminal ratings must be observed to prevent fire hazards...

Страница 4: ...The following safety symbols appear in this manual CAUTION This action or procedure may be dangerous if not carried out correctly and may cause damage to the equipment or connected equipment WARNING T...

Страница 5: ...ial rise due to the resistance and reactance of the earth connection should be considered Precautions should be taken to prevent accidental contact of live terminals by personnel either by shielding t...

Страница 6: ...6...

Страница 7: ...7 1 Automatic Discharge Earthing 12 1 7 2 Manual Earthing Using DP40 Discharge Earthing Probe 12 1 8 Construction 12 1 9 Storage 13 2 OPERATION 14 2 1 Safety 14 2 1 1 Installation 14 2 1 2 Operation 1...

Страница 8: ...8 5 PERFORMANCE SPECIFICATION 25 6 REVISION 27...

Страница 9: ...e earthed Output current 5mA continuous from each output 10mA from each output with a duty cycle of 5 minutes on 15 minutes off Current limiting PT30 10C only The PT30 10C has an extra pushbutton cont...

Страница 10: ...HV output F Output control N Earth terminal G Output HV off pushbutton P HV Output blanking plug 1 3 Output Voltage Control The voltage from the equipment is controlled by the output control on the f...

Страница 11: ...and voltage metering for each output 1 6 1 kV Meters The equipment is fitted with two output kilovolt meters which monitor both the positive and negative outputs simultaneously Both instruments have...

Страница 12: ...Must the Discharge Earthing Probe be Used on Energised A C Distribution Systems Failure to Observe the Above Will Result in Severe Damage to the Discharge Probe and more importantly possible fatal In...

Страница 13: ...aces The PT30 10 is housed in a padded bag for maximum protection during transit 1 9 Storage The PT30 10 when not in use must be stored in a dry environment corrosion damage may occur to the HV compon...

Страница 14: ...ether this be a permanent test area or a temporary test area Appropriate controls and safety measures must be applied to this area including interlocks connected to the supply to ensure that the unit...

Страница 15: ...her side of the connection should be grounded first Extra discharge probes and earth sticks are available from T R Test Equipment as an optional accessory If the test circuit includes capacitors each...

Страница 16: ...unit and all leads are inspected for integrity and for signs of damage each time before any testing is started Ensure the high voltage leads are carefully stored and that the exposed ends are kept cl...

Страница 17: ...test object The positive output must be blanked off using the plastic blanking plug provided not the metal dust cap It is also possible to carry out a positive unipolar test as shown in figure 3 alth...

Страница 18: ...nnect to low impedance local earth Cable under test Blanking plug Figure 3 Connections for negative unipolar test 6 8 10 4 2 0 8 10 2 4 6 0 Mains supply Cable under test Connect to low impedance local...

Страница 19: ...lthy cable h After 30 seconds discharge the cable This may be achieved either using the DP40 discharge probe or the internal dump circuit depending on the level of energy stored in the cable If the DP...

Страница 20: ...ith output voltage The output over current trip is inactive when current limit mode is selected 2 3 2 Current Limit Operation Current limit mode is selected by pressing the current limit push button o...

Страница 21: ...tor carbon brush condition on a regular basis Access is gained by removing the unit from the padded bag and then removing both of the side panels Rotate the regulator until the carbon brush can be see...

Страница 22: ...22...

Страница 23: ...cable fitted with HT plug clip colour coded red Supplied with protective cap for plug e 5 metre high voltage output cable fitted with HT plug clip colour coded black Supplied with protective cap for...

Страница 24: ...24...

Страница 25: ...test 2 0kV rms for 1 minute between mains input and frame Induced voltage test 35kV DC for 5 minutes Flashover test 6 flashovers at 30kV DC on each output direct to earth Normal voltage test 30kV DC...

Страница 26: ...26...

Страница 27: ...27 6 REVISION Product Type High Voltage DC Cable Test Set PT30 10 mk2 File PT30 10 mk2 manual v2 doc Author I Lake Issue Date 2 24 06 2013 Modified By T Clark Checked By P Cole Date 24 06 2013...

Страница 28: ...28 Drawings Required A2 001344 latest issue...

Отзывы: