background image

10 

 

1.5 

Fault Burn Facility (except KV5-200 mk2) 

The KV5-100 mk2, KV3-250 mk2 and KV4-300 mk2, KV6-80  are provided with an internal 
current limit circuit which limits the output current from the unit under short circuit conditions.  
This can be used to “burn” faults. 

1.5.1 

Fault Burning 

 

Fault burn is where the arc is maintained through the failed test object.  The product does this 
by limiting the current and preventing the unit from tripping.  Fault burning should be 
approached very cautiously as it can cause serious damage to the test object, and is totally 
unsuitable for many test objects. 

1.5.2 

Burn Switch 

 

When the “burn” switch is in the “out” position, the unit behaves normally and the output 
current is not limited.  Switching the “burn” switch to “in” enables the current limiting 

 

The current is limited to the following values at maximum output voltage when the “burn” is 
enabled (the burn switch is in the “in” position): 

 

 

Output Voltage 

Maximum current 

KV5-100 mk2 

5kV 

90-100mA 

KV4-300 mk2 

4kV 

280 –300mA 

KV3-250 mk2 

3kV 

160-180mA 

KV6-80 

6kV 

75-80mA 

 

 

At lower output voltages, the burn current limit reduces in proportion to the output voltage. 

 
 

When the “burn” switch is in the “out” position, the maximum current is approximately 2A for 
short periods of time. 

1.6 

High Voltage Connection 

 

WARNING

 

The equipment is supplied with crocodile clips on the output.  These clips are 
not insulated for high voltage use, and under no conditions must the high 
voltage connection be approached or touched whilst the unit is switched on.  
The test object must be earthed before making or breaking connections after 
testing.  A prohibition zone of at least 30mm must be maintained around the 
high voltage connection (from EN50191:2000) 

This equipment must be used either with an interlocked enclosure for the 
object under test or in a suitable high voltage test area.  Adequate safety 
clearances must be maintained between the operator and all high voltage 
parts at all times.

 

Содержание KV6-80

Страница 1: ...mk2 KV4 300 mk2 KV5 100 mk2 KV5 100T mk2 KV5 200 mk2 KV6 80 DESIGNED AND MANUFACTURED BY T R Test Equipment Limited 15 16 Woodbridge Meadows Guildford Surrey GU1 1BJ United Kingdom Telephone 01483 207...

Страница 2: ...1...

Страница 3: ...is provided on the unit for connection to a local earth if necessary Ensure that the unit is properly grounded before making any connections to inputs or outputs Output ratings must be observed to pr...

Страница 4: ...rise due to the resistance and reactance of the earth connection should be considered Precautions should be taken to prevent accidental contact of live terminals by personnel either by shielding the l...

Страница 5: ...The following safety symbols appear in this manual CAUTION This action or procedure may be dangerous if not carried out correctly and may cause damage to the equipment or connected equipment WARNING T...

Страница 6: ...tering 9 1 5 Fault Burn Facility except KV5 200 mk2 10 1 5 1 Fault Burning 10 1 5 2 Burn Switch 10 1 6 High Voltage Connection 10 1 7 Construction 11 1 8 Timer Operation KV5 100T mk2 only 11 2 OPERATI...

Страница 7: ...6 3 MAINTENANCE 17 4 STANDARD ACCESSORIES 18 5 OVERALL PERFORMANCE SPECIFICATION 19 6 REVISION 20...

Страница 8: ...4kV 200mA 300mA KV5 200 mk2 0 5kV 100mA 200mA KV6 80 0 6kV 80mA One side of the high voltage transformer output is connected to the earth system of the equipment 1 1 3 Zero Voltage Interlock The equip...

Страница 9: ...3 Overload Protection The equipment is fitted with a fuse and variable overload protection circuits as standard 1 3 1 Variable overload The variable overload protection system senses current changes i...

Страница 10: ...e moving coil meters Unit Metering Ranges Voltage Current Low High X1 X10 KV5 100 mk2 3kV 6kV 10mA 100mA KV3 250 mk2 1 6kV 3 2kV 30mA 300mA KV5 200 mk2 3kV 5kV 20mA 200mA KV6 80 4kV 7kV 10mA 100mA The...

Страница 11: ...abled the burn switch is in the in position Output Voltage Maximum current KV5 100 mk2 5kV 90 100mA KV4 300 mk2 4kV 280 300mA KV3 250 mk2 3kV 160 180mA KV6 80 6kV 75 80mA At lower output voltages the...

Страница 12: ...imer cancel push button The audible alarm is cancelled using the Timer cancel push button WARNING The timer does not switch the high voltage output off it only warns the operator when the required tim...

Страница 13: ...to the supply or HV unit interlock to ensure that the unit cannot be switched on unless the area is secure Refer to BS EN50191 2001 and IEEE Std 510 1983 for further details of suitable test enclosure...

Страница 14: ...13 2 2 Front Panel Layout Figure 2 1 KV5 100 mk2 front panel kV AC 1 2 3 0 5 1 1 5 mA F G H J K L M P D B A N C E Figure 2 2 KV3 250 front panel...

Страница 15: ...14 Figure 2 3 KV5 100T front panel Figure 2 4 KV5 200 front panel...

Страница 16: ...ip level select Selects output current trip level L HV Output OFF pushbutton Switches HV output off Illuminated green when output is off M Mains supply switch key operated Key operated mains on off sw...

Страница 17: ...emergency stop button is released and that the regulator is in the fully anti clockwise position Press the HV ON pushbutton The HV output will now energise and the red HV on indicator in the pushbutt...

Страница 18: ...t and on the output leads Ensure that the unit is disconnected from the mains before removing any covers It is advisable to check the carbon brush on the variable transformer for signs of wear on a re...

Страница 19: ...ided with the equipment a Mains input lead b 2 keys for mains ON OFF switch c Operating Maintenance Manual d 1x F5A 1 inch fuse and 1x T4A 20mm fuse KV5 100 mk2 KV3 250 mk2 KV6 80 1xT5A 1 inch fuse an...

Страница 20: ...stance at 500V DC 10 megohms between mains input and frame Applied voltage test 2 0kV RMS for 1 minute between mains input and frame Accuracy of instruments kV meter 1 5 of FSD mA meter 2 5 of FSD Ins...

Страница 21: ...0 6 REVISION Product Type KV5 100 mk2 series High Voltage AC Test Systems File KV5 100mk2 series manual v8 doc Author P Cole Issue Date 8 24 02 17 Modified By K Mupotsa Checked By G Biggs Date 30 05 1...

Страница 22: ...21 Circuit diagram A2 001910 KV5 100 mk2 Other unit circuit diagrams available on request A2 000925 KV3 250 A2 001924 KV4 300 mk2 A2 001948 KV5 100T A2 001708 KV5 200 A3 002002 KV6 80...

Отзывы: