background image

Specifications

Model

RTR501B / 501BL

RTR502B / 502BL

RTR503B / 503BL

RTR507B / 507BL

Measurement 

Channels

Temperature 1ch

Temperature 1ch

Temperature 1ch, Humidity 1ch

Temperature 1ch, Humidity 1ch

Sensor

Thermistor (Internal)

Thermistor

Thermistor

Polymer Resistance

Thermistor

Polymer Resistance

Measurement 

Range

-40 to 80℃

-60 to 155℃

0 to 55℃

10 to 95%RH

-25 to 70℃

0 to 99 %RH (*1)

Accuracy

Avg. ±0.5℃

Avg. ± 0.3℃

  at -20 to 80℃

Avg. ±0.5℃

  at -40 to -20℃, 80 to 110℃

Avg. ± 1.0℃

  at -60 to -40℃, 110 to 155℃

Avg. ± 0.3℃

±5 %RH 

  at 25℃, to 0%RH

±0.3°C 

  at 10 to 40℃

±0.5°C 

  Others

±2.5 %RH 

  at 15 to 35℃, 

 

       30 to 80%RH

Measurement 

Resolution

0.1℃

0.1℃

0.1℃

1 %RH

0.1℃

0.1 %RH

Responsiveness

Thermal Time Constant: 

  Approx. 15 min.

  Approx. 25 min. (L Type)

Response Time (90%):

  Approx. 35 min.

  Approx. 47 min. (L Type)

Thermal Time Constant: 

  Approx. 30 sec. (in air)

  Approx. 4 sec. (in agitated water)

Response Time (90%): 

  Approx. 80 sec. (in air)

  Approx. 7 sec. (in agitated water)

Response Time (90%): Approx. 7 min.

Response Time (90%): Approx. 7 min.

Logging  

Capacity

16,000 readings

16,000 readings

8,000 data sets (One data set con-

sists of readings for all channels in 

that type of unit.)

8,000 data sets (One data set consists of 

readings for all channels in that type of unit.)

Recording 

Interval

1, 2, 5, 10, 15, 20, 30 sec. 1, 2, 5, 10, 15, 20, 30, 60 min. (Total of 15 choices)

Recording 

Mode (*2)

Endless: Overwrite the oldest data when capacity is full

One Time: Stop recording when capacity is full

Communica-

tion Interfaces

Short Range Wireless Communication

 

Frequency Range: 902 to 928 MHz

 

RF Power: 7 mW

 

Transmission Range: About 150 m if direct and unobstructed.

Bluetooth 4.2 (Bluetooth Low Energy) (*3)

Optical Communication

Power

Lithium Battery LS14250 x 1

L Type: Large Capacity Battery Adaptor Kit (RTR-500B1) x 1 (*4)

External Power Adaptor Kit RTR-500A2 (*5)

Battery Life (*6)

About 10 months L Type: About 4 years

Dimensions

H 62 mm x W 47mm x D 19 mm L Type: H 62 mm x W 47 mm x D 46.5 mm (excluding protrusions and sensor)   

Weight

Approx. 50 g, L Type: Approx. 65 g 

Operating 

Environment

-40 to 80℃

Wireless Communication -30 to 80℃

Waterproof 

Capacity

IP67 (immersion proof)

IP64 (splash proof / rated for use in daily life) (*7)

Compatible 

Base Units

RTR500BC, RTR500BW

RTR-500DC, RTR-500MBS-A, RTR-500NW/AW (*8)(*9)

RTR-500 (*9)

*1: 

When continually used in environments with temperatures above 60 ̊C, accuracy of humidity measurements will decrease over time. Also, humidity cannot be measured at temperatures below -20 ̊C.

*2:  Only “Endless” is available when using the RTR500BW, RTR-500NW/AW or RTR-500MBS-A as a Base Unit.

*3:  Bluetooth is available when using the RTR500BW as a Base Unit and making device settings in the mobile app (T&D 500B Utility).

*4:  When using RTR-500B1 it is necessary to purchase Lithium Battery (LS26500). For details, contact your local authorized distributor.

*5:  RTR-500A2 should not be used with the RTR501B, as it will cause the RTR-501 to display a higher than actual temperature reading of up to 3°C.

*6:  Battery life varies depending upon the ambient temperature, radio environment, frequency of communication, recording interval, and quality of the battery being used. All estimates are 

based on operations carried out with a new battery and are in no way a guarantee of actual battery life.

*7:  This is the waterproof capacity of the data logger with the sensor connected. Note that the temperature-humidity sensor is not water resistant.

*8: 

A firmware update is required.

*9:  A software update is required.

The specifications listed above are subject to change without notice.

How to Read the LCD Display

When being used in very hot or cold environments the display may become difficult to read. This is not a malfunction.

[REC] Mark

Shows the recording status.

ON: Recording in progress 

BLINKING: Waiting for programmed start 

OFF: Recording stopped

[ONETIME] Mark Shows the recording mode.

ON: One Time 

OFF: Endless

Battery Warning 

Mark

Indicates it is time for the battery to be replaced.

Measurement / 

Message Area

Measurements or operational messages are shown 

here.
When Recording Mode has been set to “One Time” and 

the logger reaches its logging capacity, recording will 

automatically stop and in the LCD the measurement 

and the word [FULL] will alternately appear.
The measurement and the word [SEnd] will alternately 

appear when data is being sent via wireless communi-

cation to the Base Unit. Recording will continue during 

wireless transmission.

[Ir] Mark

Indicates that the logger (Remote Unit) has not been 

registered to the Base Unit or the wireless communi-

cation is stopped (inactive radio).

[COM] Mark

Indicates that the device is in Bluetooth communication.

Unit of Measure-

ment

Shows the unit of measurement.