PAGE 12/22
119076.02 TELEPRESENCE T3 ROOM REQUIREMENTS 12.08
TANDBERG
Telepresence T3
POWER OUTlET fUSE
REQUIREMENTS
The following minimum power outlet fuse requirements apply to the TANDBERG
Telepresence T3:
ITEM
WATT
PlACEMENT
fUSE
ON/Off SWITCH
T1 Module × 3
2400
Back wall
A
1
Presentation
splitter × 2
60
Back wall
A
1
Table power outlet × 6
2400
Back wall
B
2
TCU
400
Back wall
C
2
Table quick buttons
50
Back wall
C
2
Presentation input
switch
5
Back wall
C
2
Touch collaboration
display splitter
20
Back wall
C
2
Touch collaboration
display
750
Back wall
C
2
Document camera
300
Ceiling
D
2
T3 Ceiling mounted
lights
750
Ceiling
D
3
T3 LED Module
1000
Back- / Front wall
D
4
Total power
9335
Note!
The table lists minimum fuse
requirements. All electrical work must
be done by electricians with local
knowledge.
Note!
Outside the room—adjacent to the
entrance—there shall be an emergency
power switch to switch off the power to
the entire system and the room.
On the inside adjacent to the exit there
shall be a sign with the following text:
fire emergency switch is
located on the outside of
this room.