                            TXC3100 Conventional Smoke Detector 

                                                                       

   

 

Page 5 

 

BUS

TX7000C

火灾报警

控制器

P+

N-

4.7K 0.5W

终端电阻

非编码型火灾探测器

非编码型火灾探测器

6.8K 1W

终端电阻

非编码型火灾探测器

非编码型火灾探测器

BUS

24V

JB-Q100GZ2L-LA040

JB-TB-242/SAN030

火灾报警控制器

LA1711

通用传感器

接口模块

P1+

N1-

6.8K 1W

End of line resistor

Conventional Detector

Conventional Detector

Conventional

control

panel

output or

zone

monitoring

module

 

 

 

 

 

 

 

 

Fig 5: Multiple TXC3100 Wiring   

6 Applications and Operation 

TXC3100  connects  conventional  control  panel  or  zone  monitoring  module  with  non-polarized  two  wire;  zone 

monitoring module can connect max 16pcs conventional devices (one 6.8K end of line resistor needed at loop 

terminal).  Zone  monitoring  module  can  monitor  loop  open  circuit  and  send  back  mal-function  signal  of  the 

device back to control panel. The module will display failure when any device removed from loop.   

7 Handling and Storage 

Detector  handling  and  storage  should  be  carried  out  under  packaging  status.  Careful  handling  is  needed  to 

avoid damage. Detector shall be stored in the ventilated and dry environment. It is strictly forbidden to store the 

detectors in the open air. 

8 Notes 

8.1  Do  not  remove  the  dust-proof  plastic  cover  from  the  detector  before  project  inspection  to  avoid  detector 

contamination. 

8.2 Strict and complete on duty and shifts records are required to monitor the smoke detectors in operation   

8.3 Conduct the alarm function test once every half a year. 

8.4 Please put the dust-proof cover onto the detector whenever decoration or painting is carried out to protect 

the detector from dust contamination. 

 

 

 

 