Tanda TX7230 Скачать руководство пользователя страница 4

         

                         

TX7230 Isolator Module

 

 

 

                          Installation & Operation Manual 

                                                                                                                                                                                         

4050100319-Rev1.6-0916 

 

 

 

                    TANDA UK 

                                                                                                                                                                                       

Specifications are subject to change without prior notice 

4

 

1 Introduction   

 

1.1 Overview   

The  TX7230  manufactured  base  on  the  requirement  of  EN  54  part  17,  European  Standard.  In  the 
event of short circuit on the detection loop the TX7230 Isolators either side of the loop will detect the 
problem  and  open  circuit  and  isolates  the  faulty  part  of  the  loop,  enabling  other  devises  on  the 
unaffected part of the loop to operate normally. The module will continue to monitor for the fault to 
be repaired, once the fault is cleared the isolator will automatically reinstate the effected part of the 
loop. 

The  unit  is  aesthetically  pleasing  with  unobtrusive  design  that  will  complement  modern  building 
designs and its plug-in type assembles make installation and maintenance more convenient to the 
installer.  The  TX7230  Isolators  Module  is  compatible  to  the  TX7004  Analogue  Intelligent  Fire  Alarm 
Control  Panel,  produced  by  single  manufacture  T&A,  to  avoid  addressable  communication 
compatibility problem. 

1.2 Feature and Benefits   

 

EN54-17 Compliance 

 

In the event of a short circuit isolates faulty parts of the loop. 

 

Automatically resetting once the fault has cleared 

 

Can monitor up to 70 devices 

 

LED status indicator   

 

Loop powered device 

 

Aesthetically pleasing design 

 

Surface mounting with fix base for simple installation 

1.3 Technical Specification   

 

Listed   

 

 

   

                    LPCB Certification 

 

Compliance      

 

 

                    EN 54-17:2005 

 

Maximum Operating Voltage(V

MAX

)                      28VDC 

 

Operating Voltage(V

NOM

)             

 

      24V 

 

Minimum Operating Voltage(V

MIN

)                          16V 

 

Maximum Open Voltage(V

SO MAX

)                 

      11V 

 

Minimum Open Voltage(V

SO MIN

)                   

      8V 

 

Maximum Close Voltage(V

SC MAX

)         

      3V 

 

Minimum Close Voltage(V

SC MIN

                    1.4V 

 

Maximum Continuous Current(I

C MAX

)                      500mA 

 

Maximum Transient Output Current(I

S MAX

      5A 

 

Maximum Leakage Current(I

L MAX

 

      2mA 

 

Max closed impedance (Z

C MAX

                    0.65 ohms 

 

Current Consumption   

 

                    Standby 0.15mA, Alarm: 1.8mA 

 

Protocol 

 

 

 

                    T&A 

 

Number of monitored  

 

                    Max 70 Devices 

 

Output Impedance      

 

                    480 ohms 

 

Indicator Status     

 

 

                    Normal: Single blink/Active: Steady-on   

 

Material / Colour   

 

 

                    ABS / White Glossy finishing   

 

Dimension / LWH 

 

 

                    108 mm x 86 mm x38 mm 

 

Weight   

 

 

 

                    152g (with Base), 81g (without Base) 

 

Operating Temperature                                              -10°C to +50°C   

 

Ingress Protection Rating                                            IP30 

 

Humidity 

 

   

 

                    0 to 95% Relative Humidity, Non condensing 

 

 

 
 
 