                                                                                                       TX7210 Addressable Single Input/Output Module 

 

 

        Installation & Operation Manual  

                                                                                                                                4050100267-Rev1.6-0916                                                                      

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

     

1 Introduction  

 

1.1 Overview  

The TX7210 Addressable Single Input/output Module is characterized as one input or output volt free 
relay and control module. The unit is normally used for overriding equipment such as lift return, door 
holder, smoke  extract fans, air handling unit, auto dialler to fire brigade,  BMS and etc.  The  unit has 
built-in  feedback  signal  feature,  according  to  the  pre-configured  interface  module  command  fire 
scenario,  the  alarm  controller  send  out  start  command  to  the  equipment  required  to  start.  After 
receiving  the  command,  output  module  enables  its  relay  to  change  state.  Once  the  module  is 
under  control  and  operated  a  confirmation  signal  will  be  sending  back  to  the  alarm  controller.  In 
addition, the unit incorporates an intelligent processor that provides automatic monitoring for both 
open and short circuit of the input signal line.  

The  unit  manufactured  base  on  the  requirement  of  EN  54  part  18,  European  Standard.  The  unit  is 
aesthetically pleasing with unobtrusive design that will complement modern building designs and its 
plug-in type assembles make installation and maintenance more convenient to the installer. The unit 
is  compatible  to  the  TX7004  Analogue  Intelligent  Fire  Alarm  Control  Panel,  produced  by  single 
manufacture T&A, to avoid addressable communication compatibility problem. 

1.2 Feature and Benefits  

 

EN54-18 Compliance 

 

Built-in MCU processor and digital addressing  

 

24VDC/2A Output relay contact and Control module 

 

Input Fire or Supervisory signal configuration  

 

LED status indicator  

 

Onsite Adjustable Parameter 

 

Loop or external power input  

 

Aesthetically pleasing design 

 

Surface mounting with fix base for simple installation 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Certification 

 

Compliance     

 

 

EN 54-18:2005 

 

Input Voltage   

 

 

Loop Power:24VDC [16V to 28V] 
External PSU: 20 to 28VDC 

 

Current Consumption   

 

Loop: Standby 0.6mA, Alarm: 1.6mA 
External PSU: Standby 0.6mA, Alarm: 45mA 

 

Control output voltage 

 

24VDC / 2A rating 

 

Input Relay 

 

 

 

Normally Open dry contact 

 

Input Resistance  

 

 

5.1Kohms/ ¼ W 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Indicator Status   

 

 

Normal: Single blink/Active: Steady/Fault: Double Blink  

 

Material / Colour  

 

 

ABS / White Glossy finishing  

 

Dimension / LWH 

 

 

108 mm x 86 mm x38 mm 

 

Weight  

 

 

 

170g (with Base), 92g (without Base) 

 

Operating Temperature 

 

-10°C to +50°C 

 

Ingress Protection Rating 

 

IP30 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

  
 

 

 
 
 
 

Содержание TX7210

Страница 1: ...TX7210 Addressable Single Input Output Module Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ... with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For more information please visit the website at www recyclethis info EN54 Part 18 Compliance TX7210 Addressable Single Input output Module complies wi...

Страница 3: ...rview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Interface Module Configuration 7 3 1 Preparation 7 3 2 Write Addressing 7 3 3 Feedback Mode 8 3 4 Input Check Mode 9 3 5 Output Check Mode 9 3 6 Read Configuration 10 4 General Maintenance 10 5 Troubleshooting Guide 11 Appendix 1 11 Limitation of Interfac...

Страница 4: ...that will complement modern building designs and its plug in type assembles make installation and maintenance more convenient to the installer The unit is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication compatibility problem 1 2 Feature and Benefits EN54 18 Compliance Built in MCU processor and digital add...

Страница 5: ...voltage rating of the equipment and interface module are compatible 2 2 Installation and Wiring 1 Mount the interface module base on standard one 1 gang electrical back box Follow the arrow mark for the correct position Do not over tighten the screws otherwise the base will twist Use two M4 standard screws 2 Connect the wire in terminal according to the requirement as shown in Figure two 2 to five...

Страница 6: ...lly Open Normally Close Relay Output Yes Normally Open Normally Close Normally Close Normally Open Power Limited Output Yes 1 5 3Vdc 24Vdc Figure 2 Input Wiring Details Note Change the parameter Input Check into 3Y Loop Powered Figure 3 Relay Output Wiring Details Loop Powered mostly used Figure 4 Control Output Wiring Details With External Power Supply Figure 5 Control Output with Feedback Signal...

Страница 7: ...parately The programmer is packed with twin 1 5V AA battery and cable ready for usage once received It is mandatory for the commissioning personnel to have programmer tool in order to adjust the module conferring to the site situation and environmental requirements Program a unique address number for each device according to the project layout before placing from the Terminal Base Warning Disconne...

Страница 8: ...t feedback signal from Input terminal Default setting is External feedback mode 2 Connect the programming cable to Z1 and Z2 terminals Figure 6 Press Power to switch on the unit 3 Switch on the programmer then press button 3 to enter to Configuration mode Figure 10 4 Input the 1 for Self feedback mode or 2 for External feedback mode then press Write to change the setting Figure 11 Note If display ...

Страница 9: ... Press Power to switch off the programmer 3 5 Output Check Mode 1 Output Check mode is use to enable voltage monitoring The module will report to the panel in the event of low voltage output cause by open and short circuit occur in the wiring 2 Connect the programming cable to Z1 and Z2 terminals Figure 6 Press Power to switch on the unit 3 Switch on the programmer then press button 3 to enter to ...

Страница 10: ...face module it may affect the operation to respond to a fire condition and will void the manufacturer s warranty 4 Use a damp cloth to clean the surface 5 Notify again proper personnel after conducting the maintenance and make sure to enable the interface module and confirm if up and running 6 Perform the maintenance on semi annually or depending on the site conditions 1 Read 2 Write T 3 R W Confi...

Страница 11: ...terface Module cannot last forever In order to keep the interface module working in good condition please maintain the equipment continuously according to recommendations from manufacturers and relative nation codes and laws Take specific maintenance measures on the basis of different environments These interface module contains electronic parts Even though it is made to last for a long period of ...

Отзывы: