                                                                                                       TX7120 Intelligent Smoke & Heat Detector 

 

 

        Installation & Operation Manual  

                                                                                                                                     
                                                                                                                               4050100264-Rev1.1-0815 

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

2 Installation   

 

2.1 Installation Preparation 

This sensor must be installed, commissioned and maintained by a qualified or factory trained service 
personnel. The installation must be installed in compliance with all local codes having a jurisdiction in 
your area or BS 5839 Part 1 and EN54. 

The TX7120 Smoke & Heat detectors operate on the principle of infra-red light refracting off smoke 
particles entering the chambers. This makes detector more sensitive to smouldering fires such as 
modern fabric or furnishing. Optical detectors are more prone to false alarm from steam or dusty 
environment. For best sensing ability, avoid installing the smoke detector in these areas.  

 

In open air applications as the detectors require ceilings to direct the smoke from the plume 
by convection. 

 

On  side  walls,  this  will  severely  delay  the  response  time  of  a  detector  and  where  ceiling 
heights exceed 10.5m. 

 

In  Rooms  where  cooking  will  take  place  such  kitchens,  or  similar  areas  where  steam  and 
condensation are present.  

 

Where exhaust fumes are present like car parks. 

 

Where smoke particles will not be produced by fire. 

 

Plant Rooms (unless full discussions regarding the room contents and status subject to a fire 
have been made between Client and Manufacturer), Boiler and Generator Rooms. 

 

2.2 Installation and Wiring 

1.

 

Mount the T&A standard base on standard one [1] gang electrical 
back box. Do not over-tighten the screws otherwise the base will 
twist. Use M4 standard screws. 

2.

 

Connect the wire in terminal as shown in Figure two [2]. Verify the 
device  number  or  other  device  parameters  if  desired  using 
handheld  programmer  then  stick  on  the  label  before  attaching 
detector.  The sticker labels are available on the control panel.  

3.

 

Attach the detector to the base, point the detector in the base by 
the mark-line and secure the detector in that position by rotating it 
clockwise, until it reaches the next mark line.  

4.

 

Do not remove the red plastic dust cover until the final handover is 
done. 

 

 

 

 

 

 

 

 

 

 

Figure 2  

 

Figure 1  

 

Terminal Description  

1

 

Signal In (+) 

2

 

Signal Out (+) 

3

 

Remote Indicator (+) 

4

 

Remote Indicator (+) 

5

 

Signal In (-) 

6

 

Signal Out (-) 

7

 

Remote Indicator (-) 

8

 

Remote Indicator (-) 

 

 

 

 

Содержание TX7120

Страница 1: ...TX7120 Intelligent Addressable Smoke Heat Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ...efore installing the detector to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For m...

Страница 3: ...uction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Preparation 6 3 2 Write Addressing 6 3 3 Set LED On Off 7 3 4 Read Configuration 7 4 General Maintenance 8 4 1 Cleaning 8 5 Troubleshooting Guide 9 Appendix 1 9 Limitation of Smoke Heat Detectors 9 ...

Страница 4: ...ammed fire scenarios smoke and heat patterns including rate of rise temperature for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7120 detector is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication comp...

Страница 5: ...0 5m In Rooms where cooking will take place such kitchens or similar areas where steam and condensation are present Where exhaust fumes are present like car parks Where smoke particles will not be produced by fire Plant Rooms unless full discussions regarding the room contents and status subject to a fire have been made between Client and Manufacturer Boiler and Generator Rooms 2 2 Installation an...

Страница 6: ...que address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Write Addressing 1 Connect the programming cable to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Fig...

Страница 7: ...ume the default setting press Clear and then press Write 5 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 4 Read Configuration 1 Attach the programming cable to 1 and 6 terminals of detector Press Power to switch on the unit 2 Switch on the programmer then press button Read or 1 to enter to Read mode Figure 9 The programmer will display the configuration after few s...

Страница 8: ...e chamber 5 Notify again proper personnel after conducting the maintenance and make sure to enable the detector and confirm if up and running 6 Perform the maintenance on semi annually or quarterly depending on the site conditions 4 1 Cleaning 1 Remove the detector cover by snooping away the four sides tabs using a flat screw driver and then pulling the cover from the base Figure 11 2 Remove the p...

Страница 9: ...at detector can sense every form of fire all the time Generally speaking detectors may not warn you about fire caused by insufficient safety measures violent explosions leaking gas improper storage of flammable materials like diluents and other safety hazards arson or children playing with fire The alarm of a Smoke Heat detector used in high velocity environment will be delayed due to dilution of ...

Отзывы: