1 Introduction  

 

1.1 Overview  

The  TX7120  Intelligent  Addressable  Optical  Smoke  &  Heat  Detector  is  the  ideal  device  for  most 
applications, due to its spiffing linear response to a wide variety of different types of smoke patterns 
and combining with heat sensing sensor for temperature response.  The unit manufactured base on 
the sensitivity requirement of EN 54 part 29, European Standard. The unit is aesthetically pleasing with 
unobtrusive  design  that  will  complement  modern  building  designs.  The  unit  incorporates  an 
intelligent  processor  that  provides  Algorithm  map,  inbuilt  A/D  converter,  Drift  compensation,  and 
Self-Diagnosis and History log. 

Secure and speedy communication through the on-board processor enables the detector to make 
its  own  decision,  resulting  in  greater  automation.  In  the  event  of  fire,  the  integral  microprocessor 
analyses the signal according to factors such as signal strength and rate of increase, then confirms 
these patterns with the pre-programmed fire scenarios, smoke and heat patterns including rate of 
rise temperature, for a faster and safer response. Once it is confirmed, the LED  indicates the sensor 
status  and  parallel  sending  communication  signal  to  the  control  panel.  The  TX7120  detector  is 
compatible  to  the  TX7004  Analogue  Intelligent  Fire  Alarm  Control  Panel,  produced  by  single 
manufacture T&A, to avoid addressable communication compatibility problem. 

1.2 Feature and Benefits  

 

EN54-29 Compliance 

 

Using microprocessor technology with memory capacity up to 10 events 

 

Analogue sending and digital addressing  

 

Provide real time algorithm to the control panel 

 

Smart linear drift compensation  

 

360 degree visual indicator  

 

Onsite Adjustable Parameter 

 

Removable chamber against dust and small insect  

 

Ancillary remote indicator output  

 

Aesthetically pleasing design 

1.3 Technical Specification  

 

Listed   

 

 

  

LPCB Pending 

 

Compliance     

 

 

EN54-29 

 

Input Voltage   

 

 

24VDC [16V to 28V] 

 

Current Consumption  Standby  

0.6mA, Alarm: 4mA 

 

Protocol/Addressing    

 

T&A, Value range from 1 to 254 

 

Smoke Sensitivity  

 

 

As per stipulated standard  

 

Heat Class Type 

 

 

A2R 

 

Indicator   

 

 

 

Single LED / 360 degree Visual  

 

Material / Colour  

 

 

ABS / White Glossy finishing  

 

Dimension / Height    

 

Diameter 99.7 mm / 57 mm 

 

Weight  

 

 

 

145g (with Base), 90g (without Base) 

 

Operating Temperature 

 

-10°C to +50°C 

 

Humidity 

 

  

 

0 to 95% Relative Humidity, Non condensing 

  
 
 
 
 
 
 

Содержание TX7120

Страница 1: ...TX7120 Intelligent Addressable Smoke Heat Detector Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved ...

Страница 2: ...efore installing the detector to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union For proper recycling return this product to your local supplier upon the purchase of equivalent new equipment or dispose of it at designated collection points For m...

Страница 3: ...uction 4 1 1 Overview 4 1 2 Feature and Benefits 4 1 3 Technical Specification 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Detector Configuration 6 3 1 Preparation 6 3 2 Write Addressing 6 3 3 Set LED On Off 7 3 4 Read Configuration 7 4 General Maintenance 8 4 1 Cleaning 8 5 Troubleshooting Guide 9 Appendix 1 9 Limitation of Smoke Heat Detectors 9 ...

Страница 4: ...ammed fire scenarios smoke and heat patterns including rate of rise temperature for a faster and safer response Once it is confirmed the LED indicates the sensor status and parallel sending communication signal to the control panel The TX7120 detector is compatible to the TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid addressable communication comp...

Страница 5: ...0 5m In Rooms where cooking will take place such kitchens or similar areas where steam and condensation are present Where exhaust fumes are present like car parks Where smoke particles will not be produced by fire Plant Rooms unless full discussions regarding the room contents and status subject to a fire have been made between Client and Manufacturer Boiler and Generator Rooms 2 2 Installation an...

Страница 6: ...que address number for each device according to the project layout before placing from the Terminal Base Warning Disconnect the loop connection whilst connecting to the handheld programmer 3 2 Write Addressing 1 Connect the programming cable to 1 and 6 terminals Figure 3 Press Power to switch on the unit 2 Switch on the programmer then press button Write or number 2 to enter Write Address mode Fig...

Страница 7: ...ume the default setting press Clear and then press Write 5 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 4 Read Configuration 1 Attach the programming cable to 1 and 6 terminals of detector Press Power to switch on the unit 2 Switch on the programmer then press button Read or 1 to enter to Read mode Figure 9 The programmer will display the configuration after few s...

Страница 8: ...e chamber 5 Notify again proper personnel after conducting the maintenance and make sure to enable the detector and confirm if up and running 6 Perform the maintenance on semi annually or quarterly depending on the site conditions 4 1 Cleaning 1 Remove the detector cover by snooping away the four sides tabs using a flat screw driver and then pulling the cover from the base Figure 11 2 Remove the p...

Страница 9: ...at detector can sense every form of fire all the time Generally speaking detectors may not warn you about fire caused by insufficient safety measures violent explosions leaking gas improper storage of flammable materials like diluents and other safety hazards arson or children playing with fire The alarm of a Smoke Heat detector used in high velocity environment will be delayed due to dilution of ...

Отзывы: