AIR-IQ2 AIRFLOW MEASUREMENT SOLUTION

AIR-IQ2 INS

TALL GUIDE_2022_04

T.A. Morrison & Co. Inc.   |   P.O. Box 157 Smiths Falls Stn Main, Ontario, Canada K7A 4T1   |   800 561 3449   |   Fax: 800 668 8476   |   tamcodampers.com

EBTRON, Inc.   |   1663 Hwy. 701 S., Loris, SC USA 29569   |   800.2EBTRON (232.8766)   |   Fax: 843.756.1838   |   www.ebtron.com

B

+

2”

1"

1"

A*

A + 2”

4"

B*

Non-ducted applica�on

4"

5"

6"

5.1" 2.4"

12.5"

Ducted applica�on

13.5"

Minimum distance to 

trailing edge of intake louver

1"

9"

B

B

1"

Minimum 4" clearance for EBTRON insertion 

style sensor probes and electronic actuator. Does 

not include access for wiring after installation of 

assembly. 

See specific EBTRON and TAMCO series 

technical documentation for more information.

INSIDE SLEEVE DIMENSIONS:

Parallel to blade = A
Perpendicular to blade = B

OUTSIDE DAMPER FRAME DIMENSIONS: 

Parallel to blade = A + 2" 
Perpendicular to blade = B + 2"

OUTSIDE FLARE DIMENSIONS: 

Parallel to blade = A + 2" 
Perpendicular to blade = B + 2"

*NOTES:

 

A x B:  =   Always opening dimensions

 Width  =   A: Always dimension parallel 

to blades

 Height =   B: Always dimension 

perpendicular to blades

AIR-IQ2 shown 

with sleeve only

FLANGED TO DUCT INSTALL TYPE:

• 

If AIR-IQ2 unit is manufactured with the 1" flare, the minimum distance from the outside edge of the flare to the trailing edge of the intake louver 

must be no less than 9". For optimal performance, it is recommended that the 1" flare be used on ALL units where ductwork is not connected to 

the leading end of the assembly.

• 

If AIR-IQ2 unit is manufactured as "Sleeve Only", without the 1" flare, the unit may be flanged to the duct, so that the minimum distance from the 

outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10".

• 

AIR-IQ2 unit must be installed square.

• 

A Flanged to Duct Install Type AIR-IQ2 unit damper's finished, inside frame dimensions are equal to the specified duct or opening size. 

• 

If the AIR-IQ2 unit is manufactured with the 1" flare, the unit will be secured to the duct or opening using the damper flanges only, leaving the flare 

side free. The overall damper frame width and height dimensions are 2" larger than the duct or opening dimensions.

• 

If AIR-IQ2 unit is manufactured as "Sleeve Only", without the 1" flare, both sides of the unit can be secured to the duct work or openings. Both the 

damper's and the sleeve's overall, outside frame/flange dimensions are 2" larger than the duct or opening dimensions.

• 

Do not assume that the duct or opening is square. Verify that the duct flange or hole is square, flat and even. 

• 

Verify that the unit AIR-IQ2 unit is square. Operate the damper to verify free movement of the blades and correct sealing. 

• 

Secure the damper to the duct work or opening. Re-verify that the damper is square. 

• 

If the AIR-IQ2 unit is manufactured as "Sleeve Only" and ducted on both sides, repeat the procedure for the other flange.

• 

Caulk all joints.

AIR-IQ2: TYPICAL, SINGLE-SECTION, HORIZONTAL-BLADE DAMPER 

PROBES MOUNTED PARALLEL TO BLADES

FLANGED TO DUCT INSTALL TYPE

Airflow

5

Содержание AIR-IQ2

Страница 1: ...STALL GUIDE_2022_04 INSTALLATION GUIDELINES T A Morrison Co Inc P O Box 157 Smiths Falls Stn Main Ontario Canada K7A 4T1 800 561 3449 Fax 800 668 8476 tamcodampers com EBTRON Inc 1663 Hwy 701 S Loris SC USA 29569 800 2EBTRON 232 8766 Fax 843 756 1838 www ebtron com ...

Страница 2: ...rt Up Guide under separate cover Available individually or as a part of EBTRON A4 EF O M Manual LIMITED PRODUCT WARRANTY DESCRIPTION AIR IQ2 products are warranted against defects in materials or workmanship for 36 months from the date of shipment Should the product or component parts qualify as a warrantable failure within this time period the product or component involved will be repaired or rep...

Страница 3: ...ions or issues not covered in this document contact TAMCO Customer Service at 1 800 561 3449 EBTRON AIRFLOW MEASUREMENT STATION Refer to the EBTRON A4 EF2 O M Manual under separate cover for airflow measurement station wiring instrument setup and operation For additional assistance with EBTRON Airflow Measurement Station questions or issues not covered in the O M Manual contact your local EBTRON R...

Страница 4: ... back into position gently taking care not to disturb the EBTRON sensor probes and transmitter Do not install the AIR IQ2 Unit if damage is more than superficial if uncertain as to extent of damage or if the damper does not seal correctly Call TAMCO customer service at 1 800 561 3449 Operate the damper section manually on a flat section of floor to verify correct blade action and sealing 1 To corr...

Страница 5: ... is not connected to the leading end of the assembly If AIR IQ2 unit is manufactured as Sleeve Only without the 1 flare the unit may be flanged to the duct so that the minimum distance from the outside edge of the sleeve to the trailing edge of the intake louver is a minimum of 10 AIR IQ2 unit must be installed square A Flanged to Duct Install Type AIR IQ2 unit damper s finished inside frame dimen...

Страница 6: ...l always be on the face of damper downstream from the louver and will ship with all damper units that are two sections wide Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information AIR IQ2 shown with sleeve and flare INSIDE ...

Страница 7: ...carried out by affixing only the damper inside the duct work Do not use sleeve or flare to secure unit in duct work AIR IQ2 unit must be installed square An Installed In Duct Install Type AIR IQ2 unit damper s finished outside frame dimensions are smaller than the specified duct width and height dimensions to allow for clearance to insert the damper frame into the duct work Ensure that the duct is...

Страница 8: ...Non ducted applica on 4 5 6 5 1 2 4 12 5 Ducted applica on 13 5 Minimum distance to trailing edge of intake louver 9 B B 0 5 1 A 0 5 A 2 5 A 1 4 Minimum 4 clearance for EBTRON insertion style sensor probes and electronic actuator Does not include access for wiring after installation of assembly See specific EBTRON and TAMCO series technical documentation for more information Jumpers will always be...

Отзывы: