OY1110 LoRaWAN Temperature and humidity sensor, User manual, Version 1.0
18
9.5.1
Measurement interval
The measurements are done periodically. The interval time is controlled by the configuration
parameter Measurement Interval. The default setting is 15 minutes.
The measurement interval can be set between 1 and 10080 minutes (~1 week).
It is also possible to order a batch of OY1110 with a different default setting.
Example
Set measurement interval to 5 minutes:
Port 1: 01230005
Set measurement interval to 15 minutes:
Port 1: 0123000F
Note
: For larger intervals than 2 hours, only full hours are supported. Maximal interval is 168
hours, i.e. 7 days.
9.5.2
TX group size
Several measurements can be grouped into a group measurement report to save battery. The
TX group command defines how many measurements that should be included in each
measurement report. The default setting is that every measurement as sent in a measurement
report, i.e. TX group size = 1.
Example:
Group three measurements in one measurement report:
Port 1: 012403
Group one measurements in one measurement report:
Port 1: 012401
Note
: Only full hours are supported for measurement intervals longer than 2 hours. The
maximum interval is 168 hours, i.e. 7 days.
9.5.3
Reset device
The device can be remotely reset and forced into
Joining
state. All settings are back to
factory default.
Example: Remote device reset:
Port 1: 0305