background image

 

 

 

3

 

 
 
The Flush Time   

 

Defines the duration of the flushing time per station. The following options are selectable: 
 
5-20   sec in steps of 1 sec 
20-55 sec in steps of 5 sec 
1-6     min in steps of 0.5 min 
 
 

The DP Set Point   

 
At  this  field  the  user  defines  the  pres

sure  difference  between  the  filter’s  inlet  and  outlet  that  when 

reached, a flushing cycle will take place. This field is meaningless when electronic DP sensor is not in 
use, therefore the user is expected to define the DP set point to be 00, as a result the actual DP value 
will appear as (- -).  
 
When the pressure is expressed in BAR the range of values is 0.1 

– 2.0 BAR. 

When the pressure is expressed in PSI the range of values is 1- 30 PSI. 
 
When the system does not include the built in electronic DP sensor but uses instead an external DP 
sensor, the flushing request signal arrives in the shape of a closed dry contact at the appropriate input 
terminals.  
 

 
The Flush Mode   

 
The Flush Mode defines how the flushing cycles is triggered. The selectable options are as follows: 
 

OFF

 -   

no flushing will take place  

By time

 

–  

In this case the flushing cycles will be repeated in a selected interval or will be triggered 
by  the  DP  signal  depending  on  what  happens  first.  No  matter  how  was  the  flushing 
cycle  started  the  interval  to  the  next  cycle  will  start  to  be  measured  again  after  each 
ending of a flushing sequence. The selectable intervals are the following: 

 
 

5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55, 60 minutes 

 

2, 3, 4, 5, 6, 8, 12, 18, 24, 72, 120 hours 

 
dp

 

–  

flushing will be triggered by DP only.  

 
 

 
If  the  “+”  and  “-“  keys  are  pressed  and  held  down  simultaneously  the 
“Flush Mode” field will show the left time until next cycle, alternately hours 
and minutes. 

 
 
 

The Accumulations   

 
The unit accumulates and displays the number of flushing cycles caused by DP, by time, or manually 
At each of the accumulation fields, 

the “+” or “-“ keys may be used for clearing the accumulated value. 

 

The Configuration   

 
In  order  to  enter  into  the  configuration  process  press  and  hold  down  the  ENTER  key  for  at  least  3 
seconds. 

REMARK

 

Содержание FILTRON 1-10 AC

Страница 1: ...D NAAMAN CENTER HAIFA ACCO ROAD 7000 P O BOX 775 KIRYAT MOTZKIN 26119 ISRAEL TEL 972 4 8775947 972 4 8775948 FAX 972 4 8775949 E mail talgil33 netvision net il FILTRON 1 10 DC AC U S E R S M A N U A L...

Страница 2: ...red by 110v or 220v from which it generates the 24v AC for the solenoids Flushing cycles may be triggered either by time or by the embedded electronic DP sensor reaching the set point or by a dry cont...

Страница 3: ...blinking Once entering this process of passing through the editable fields the user has no way back but by pushing the ENTER key repeatedly he passes through the chain of editable fields until arrivin...

Страница 4: ...Flush Mode The Flush Mode defines how the flushing cycles is triggered The selectable options are as follows OFF no flushing will take place By time In this case the flushing cycles will be repeated...

Страница 5: ...e selectable delay steps are 5 10 15 20 25 30 35 40 45 50 55 sec 1 1 5 2 2 5 3 3 5 4 4 5 5 5 5 6 min Dwell time the delay between stations can be set to 5 10 15 20 25 30 35 40 45 50 55 or 60 sec DP de...

Страница 6: ...es the flushing sequence will start from the beginning rather than continue from the stop point Connecting the DP sensor to the filter system The DP sensor is connected to the filter system by 2 comma...

Страница 7: ...1 Valve 2 Pre Dwell Flush time Valve 3 Valve 4 Dwell time Main valve Valve 1 Valve 2 Pre Dwell Flush time Valve 3 Valve 4 Delay valve Dwell time V V Valve Delay Timing Diagram Without Delay Valve Inc...

Страница 8: ...at 1 The External DP sensor is optional and it is intended for use in cases there is no Embedded Electronic DP included 2 The powering of the unit can be either by 6v DC or 12v DC 3 The solenoids will...

Страница 9: ...External DP sensor is optional and it is intended for use in cases there is no Embedded Electronic DP included 2 The powering of the unit is by 24VAC transformed from 220 110 VAC 3 The solenoids will...

Страница 10: ...Embedded electronic analog DP sensor or external dry contact DP sensor Pressure Sensor Dry contact pressure sensor Operating temperature 0 60 C AC MODEL Power source 220 or 110 v AC 50 or 60 Hz with...