INSTALLATION
Loosen the cover locking screw and remove
the cover. Do not remove the screw from the
cover not to lose locking nut.
1.
For wall mounting, use wall mounting hole
located in the center of the base.
For corner mounting, break 4 knockouts on
both side to use corner mounting holes.
2.
Break knockouts of wiring holes required
to connect wires. In case wiring through
upper wiring holes, pass the wires along
wiring channels on either side of the base
to connect them to the terminal.
3.
Attach the cover and tighten the cover
locking screw.
4.
WIRING
FUNCTION
TAMPER
1
2
3
4
5
6
POWER
ALARM
Power
}
Signal Input
Sensor
(
N.C.
)
Sensor
(
N.C.
)
■MODE SELECTOR
Switch
1
ON
4
2
OFF
(
Factory set
)
ALARM LED
The alarm LED will light up, synchronized with the
alarm contact, if you set the mode selector at ON.
FACTORY SET
ON
OFF
1
2
■Terminal Arrangement
■Basic connection
■WIRING DISTANCE BETWEEN SENSOR AND POWER SOURCE
The number of counts can be selected according to
environmental conditions.
ON
(
Factory set
)
Switch
2
OFF
POWER
(non-polarity)
9.5V to 28V DC
20mA Max.
Distance at 12VDC
Distance at 24VDC
Size of wire used
4,600ft (1,400m)
27,500ft ( 8,400m)
7,200ft (2,200m)
43,000ft (13,200m)
AWG 20 (Dia.0.8mm)
AWG 18 (Dia.1.0mm)
AWG 17 (Dia.1.1mm)
8,900ft (2,700m)
51,000ft (15,500m)
[When two units are used]
Note : 1)
2)
*
Allow approx. one minute for warm-up after power is supplied.
(Alarm LED is flashing) In the meantime, no alarm is initiated.
*
After the one minute has passed, the unit will be in the armed
status and will trigger an alarm when detecting a human body.
Maximum wiring distance, when two or more sets are connected,
is the value above divided by numbers of sets.
The signal line can be wired to a distance of 3,280 ft (1,000m)
with AWG 22 (0.65mm dia.) wire.
Sensor operation can be adjusted to fit the environmental conditions /
applications with the built-in mode selector.
ALARM OUTPUT
Dry contact N.C. (semi-conductor)
Reset : approx. 2 sec.
30V DC (24V AC) 0.25A Max.
(Protective resistor 3.3
Ω
)
TAMPER OUTPUT
Dry contact N.C.
Operation : Open when cover is detached.
30V DC 0.1A Max.
(Protective resistor 3.3
Ω
)
OPERATION CHECK
NOTE :
2 : Low voltage
TROUBLE ALARM
NOTE :
1 : Unit trouble
This function checks / monitors sensor unit itself in accordance with built-in
program.
When trouble is found out as a result of the check / monitor, alarm LED lights
and an alarm signal also continuously outputs.
Trouble alarm outputs when inner circuit / wiring is damaged / broken.
See "8. TROUBLESHOOTING" and remedy table.
The monitor functions regardless of mode settings but an alarm is
not indicated in case of setting alarm LED at OFF position.
When power is reset during the alarm status, trouble alarm stops
only for warming up time.
When power voltage of sensor drops down (approx. 8.5V DC or less),
trouble alarm outputs before sensor operation becomes unstable due to low
voltage. See "8. TROUBLE-SHOOTING" .
The monitor functions regardless of mode settings but an alarm is
not indicated in case of setting alarm LED at OFF position.
When power voltage recovers to normal level during the alarm
status, trouble alarm stops.
When installation is completed, turn the power "ON" and check operation after about 1min. warming up time, as follows:
1. Make sure that alarm LED finished flickering.
2. Make a walk test in the protected area to check if an alarm is initiated.
Check alarm LED and control panel for sensor operation.
3. After correct operation has been confirmed, use the mode selector
switch to disable the alarm LED, if required.
SIGNAL COUNT
4 : Less sensitivity; prevents false alarms caused by
temperature fluctuation.
2 : Normally set to this position.