WARNING

: Do not install the heater where 

water, debris, or flammable vapors may get 
into the flue terminal. This may cause damage 
to the heater. 

 

 

WARNING

: United States regulations forbid 

installing the unit within 4’ of any opening into 
any building.  Similar Canadian regulations 
forbid the unit from being installed within 10’ of 
any opening into any building.  

 

WARNING

: Improper installation can cause 

nausea or asphyxiation from carbon monoxide 
and flue gases which could result in severe 
injury or death. 
For installation in altitudes above 4,500 feet, 
contact the manufacturer for instructions. 
 

Indoor Installation 

 
Follow all local codes, or in the absence of 
local codes, follow the codes for Installation of 
Gas Burning Appliances; National Fuel Gas 
Code ANSI Z221.23 in USA or CAN/CGA 
B149.1 or .2 in Canada. 

WARNING

:  In an indoor installation, the T-K2 

must be connected to a Category III special 
gas vent in order to direct the dangerous 
exhaust byproducts to the outdoors. 
Connect the 4” Category III vent pipe to the 4” 
round collar on the top of the unit. 

WARNING

: Do not install the unit directly on a 

combustible surface such as carpeting, wood 
floors, etc.  If it is necessary to install the unit 
standing on a surface, install a 3” 
noncombustible base between the unit and the 
surface. 

Combustible Air Supply 

The T-K2 must be installed in a location where 
the proper amount of combustible air will be 
available to it at all times.  If the unit is 
installed in a confined space, there must be 
permanent openings supplying air to the unit. 
If the openings will bring air directly from the 
outdoors, two openings are required, and they 
should be sized to give a minimum free area 
of one square inch for every 4000 BTUH of the 
maximum input rating of the unit.   
 

 

                                            Air Vents 
  T-K2 

 (47 

sq. 

in. 

 

 

 

              each) 

 
If the openings will bring air from another 
indoor area, they should be sized to give a 
minimum free area of one square inch for 
every 1000 BTUH of the maximum input rating 
of the unit.   

 

                  Air Vents 
                 (185 sq. in.            T-K2 
                     each) 
One of these openings should be within 12” of 
the ceiling, and the other should be within 12” 
of the floor. 
 

Содержание T-K2

Страница 1: ... which can cause serious injury or death Improper installation and or operation or installation by an unqualified person will void warranty WARNING If the information in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance W...

Страница 2: ... NG Dipswitch Settings 24 Indoor LP Dipswitch Settings 25 Outdoor LP Dipswitch Settings 25 Exploded Diagrams 26 29 Parts List 30 Flow Chart 31 Specifications Natural Gas Input Min 20 000 Btu Max 185 000 Btu LPG Input Min 19 000 Btu Max 175 000 Btu Gas Connection NPT Water Connections NPT Water Pressure Min 15 psi Max 150 psi Natural Gas Pressure Inlet Min 5 WC Max 10 5 WC LP Gas Pressure Inlet Min...

Страница 3: ... the Gas Company or the manufacturer 6 WARNING Do not disconnect the electrical supply if the temperatures will be near freezing The Freeze Prevention Device will only work if the unit has proper electrical power The Freeze Prevention Device is rated for temperatures down to 5º F 15º C in a wind free environment The wind chill factor will cause the Flash Water Heater to freeze and be damaged at te...

Страница 4: ...r turn on water demanding appliance 2 Unit will detect flow burners will ignite Fire On lamp will light up 3 If necessary mix in cold water to get a comfortable temperature Turning It Off To turn off the Flash water heater 1 Close the hot water tap or turn appliance off 2 Flow will diminish unit will shut off 3 Fire On lamp will go out Temperature The output temperature of the T K2 has been factor...

Страница 5: ...er heater in an area with extremely cold weather This will void your warranty and Takagi Industrial Co USA Inc will not be responsible for any damage that occurs WARNING The pipe heaters are located on the Flash Water Heater only Any hot or cold water pipes located outside of the unit will not be protected Properly protect and insulate these pipes from freezing If the heater will not be in use for...

Страница 6: ...he parts listed below were included with the unit Electrical Connections The T K2 requires a 60 Hz 120 VAC electrical power supply and it should be properly grounded in accordance with the most recent edition of the National Electrical Code ANSI NFPA 70 and any local codes In Canada all electrical wiring to the heater should be installed in accordance with the Canadian Electrical Code CSA C22 1 Pa...

Страница 7: ...nside panel of the appliance Wiring Diagrams Electrical Rating 120 VAC 60 Hz 0 8 A Note If any of the original wiring supplied with this appliance must be replaced it must be replaced with appliance wiring material 180c or its equivalent Wires are available through the manufacturer ...

Страница 8: ......

Страница 9: ......

Страница 10: ...your gas type Always install a manual shutoff valve on the gas supply line in case of an emergency or if service or maintenance is necessary This appliance and its individual shut off valve must be isolated from the gas supply piping system by unplugging the unit and turning off the main gas valve during any pressure testing of the gas supply piping system at test pressures equal to or less than P...

Страница 11: ... the hot line out of the unit with no check valves or control valves between the unit and the relief valve The Pressure relief valve must be rated for 150 PSI and have a discharge capacity of 185 000 BTU Connect the discharge opening of the relief valve to a suitable drain to prevent water damage should discharge occur If the pressure relief valve discharges periodically this may be due to thermal...

Страница 12: ... or in the absence of local codes follow the codes for Installation of Gas Burning Appliances National Fuel Gas Code ANSI Z221 23 in USA or CAN CGA B149 1 or 2 in Canada For outdoor installation purchase a TK TV04 and install on the top of the unit Set the dipswitches for an outdoor installation See pgs 21 22 Locate the water heater in an open unroofed area and maintain the following minimum clear...

Страница 13: ...ducts to the outdoors Connect the 4 Category III vent pipe to the 4 round collar on the top of the unit WARNING Do not install the unit directly on a combustible surface such as carpeting wood floors etc If it is necessary to install the unit standing on a surface install a 3 noncombustible base between the unit and the surface Combustible Air Supply The T K2 must be installed in a location where ...

Страница 14: ...ntain the following clearances to any combustible surface in an indoor installation Indoor Clearances Piping side 6 Front Maintenance space Suggested 24 Min 4 Floor Noncombustible base Back of heater 1 Non piping side 2 Top of heater 12 Manufactured Home Mobile Home Installation This appliance must be installed in accordance with the Manufactured Home Construction and Safety Standard Title 24 CFR ...

Страница 15: ...OU SMELL GAS Do not use any appliance Do not touch any electric switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Initial Operation 1 STOP Do not operate without reading the safety information first 2 Switch off the electrical power supply to t...

Страница 16: ...r other used a means such as a mixing valve shall be installed to temper the water for those uses in order to reduce scald hazard potential Water temperature over 125 F can cause severe burns instantly or death from scalds Chemicals such as diluted Glycol can be used for radiant floor Hydro warm air or Baseboard heating only Basic system drawings and Schematics Heating application only Warning Thi...

Страница 17: ...tion of the National Standard Code ANSI Z21 10 3 Warning This illustration is for concept only There are a wide variety of variations to the application of controls and equipment presented applications Designers must add all necessary safety and auxiliary equipment to conform to code requirements and design practice For more details contact Technical Department at 888 882 524 Pressure Relief Valve...

Страница 18: ...a qualified service technician to inspect the water heater and to replace any damaged parts WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life OPERATING INSTRUCTIONS 1 STOP Read the safety information above or in the Owners Manual 2 Turn off all electric power to the water heater 3 Do not attempt to light t...

Страница 19: ...ildren or the infirm without supervised DANGER Keep flammable products 1 Far away from heater 2 In approved containers 3 Tightly closed 4 Out of children s reach Vapors 1 Cannot be seen 2 Vapors are heavier than air 3 Go a long way on the floor 4 Can be carried from other rooms to the main burner by air currents DANGER Hot Water Heater temperature over 125 F can cause severe burns instantly or dea...

Страница 20: ...K2 is 6 9 GPM If it is necessary to achieve higher flow rates for longer periods of time then it can be installed in conjunction with a storage tank A pump will be necessary to keep the water hot We suggest a pump of 1 12 hp or greater depending on the system Recirculation Pressure Relief Valve Hot Water to House Cold Water Inlet Hot Water Return Pump with without Timer Check Valves This system wi...

Страница 21: ...emperature and flow capabilities See flow chart on the last page of this manual If the water doesn t seem hot enough compare the flow and temperature that is being attained to the T K2 flow vs temperature chart If the unit is not performing according to the chart first check that the gas supply line is sized properly and that the gas pressure is within the required range If the gas line is okay ch...

Страница 22: ... self diagnostic for errors If there is a problem with the installation or the unit it will give a signal through a pair of flashing lights on the circuit plate to communicate the source of the problem If the unit has a TK RE01 remote control installed this will give also give a numerical error code Consult the following chart for the meaning of an error code TK RE01 Computer Board TK RE01 Check P...

Страница 23: ......

Страница 24: ...t allows the maximum output temperature from the T K2 to be adjusted within the range of 95 F to 180 F and it also works as a diagnostic toll that will give a concise error code whenever there is a problem with the unit The temperature options are 95 100 102 104 106 108 109 111 113 115 117 122 131 140 158 167 and 180 F See the troubleshooting section for information on possible error codes TK TV03...

Страница 25: ...ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 NG Indoor Temperature Settings 105 F 112 F 120 F 180 F ERROR Outdoor NG Dipswitch Settings 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105...

Страница 26: ...ON 4 3 2 1 ON OUT NG LP IN 180 112 105 LP Indoor Temperature Settings 105 F 112 F 120 F 180 F ERROR Outdoor LP Dipswitch Settings 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 4 3 2 1 ON 4 3 2 1 ON OUT NG LP IN 180 112 105 LP Outdoor Temperature Settings 105...

Страница 27: ...Computer board assembly ...

Страница 28: ...Case assembly ...

Страница 29: ...Burner assembly ...

Страница 30: ...Water way assembly ...

Страница 31: ...G PLATE 22 O RING 67 GAS INLET 23 GASKET 68 FAN 24 QUICK RELEASE PLATE 69 SCREW 25 QUICK RELEASE PLATE 70 FAN DAMPER 26 SCREW 71 THERMOSTAT 27 FLOW SENSOR 72 SCREW 28 O RING 73 SCREW 29 INLET CONNECTION PIPE 74 PRESSURE SWITCH 30 O RING 75 SILICON TUBE 31 INLET THERMISTOR 76 PRESSURE SWITCH PORTPLATE 32 O RING 77 PRESSURE SWITCH PORT 33 WATER INLET 78 POWER DISTRIBUTION PLATE 34 FREEZE PROTECTION ...

Страница 32: ...e 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 Output Temperature Gallon per Minuite 40 F 4 4 4 1 3 9 3 6 3 4 3 3 3 1 2 7 2 5 2 2 50 F 5 2 4 8 4 4 4 1 3 9 3 6 3 4 3 0 2 7 2 4 60 F 6 2 5 6 5 2 4 8 4 4 4 1 3 9 3 3 3 0 2 6 70 F 6 7 6 7 6 2 5 6 5 2 4 8 4 4 3 6 3 3 2 8 110 115 120 125 130 135 140 155 165 180 ...

Отзывы: