Tadiran Telecom AVL-200 Скачать руководство пользователя страница 6

SKY 

 

-

 

6

 

-

 
 
2.2 Technical data table – Models AVL-240, AVL-260, AVL-300 
 
 

AVL-240 AVL-260 AVL-300 

Model 50Hz 

R22 R407C R22 R407C R22 R407C 

Btu/h  240600 236000 264300 259000 288000 282000 

Cooling capacity 

Watt  70516 69166 77462 75907 84408 82648 

Btu/h  243000 235400 266900 259300 290800 283200 

Heating capacity 

Watt  71220 69000 78224 76000 85228 83000 

Power Consumption cooling 

Watt 

28000 

27600 

31000 

30500 

34000 

33400 

Power Consumption Heating 

Watt 

26600 

26000 

29400 

28800 

32200 

31600 

Operating Current cooling 

Amp 

47 

46.4 

50.1 

51.2 

53.2 

56 

Operating Current Heating 

Amp 

44.6 

43.6 

49.4 

48.3 

54.2 

53 

E.E.R-Energy Efficiency Ratio 

Cool 

8.6 

8.5 

8.5 

8.5 

8.47 

8.44 

C.O.P-Coefficient 

Of 

Performance

Heat 2.67 2.65 2.66 2.64 2.64 2.62 

Moisture Removal 

Lit/h 

29.2 

29.2 

30.6 

30.6 

32 

32 

Power Supply 

Volt/Hz/ph 

380/415V, 50Hz, 3ph 

380/415V, 50Hz, 3ph 

380/415V, 50Hz, 3ph 

Condensate Lines - Drain  

Ф

 - mm (in) 

29 (1 1/8") 

29 (1 1/8") 

29 (1 1/8") 

Liquid/Gas Lines 

Ф

 - inch 

1/2", 7/8" ; 5/8", 1

1/2", 7/8" ; 5/8", 1

1/2", 7/8" ; 5/8", 1

Maximum Piping Length 

m. 

30 

30 

30 

Maximum Height Difference 

m. 

12 

12 

12 

Time Delay Fuse  

Amp. 

3x63 

3x63 

3x63 

Control Mode 

  

I.R. Remote Control / Auto I.R. Remote Control / Auto  I.R. Remote Control / Auto

Temperature Control 

  

Microcomputer 

Microcomputer 

Microcomputer 

Indoor Unit 

50Hz 

AVL-240 

AVL-260 

AVL-300 

Casing 

Color 

RAL 7032 

RAL 7032 

RAL 7032 

Air Filter 

  

1 Removable/Washable  

1 Removable/Washable  

1 Removable/Washable  

Dimensions (LxDxH) 

mm 

2050x1000x950 

2300x1100x950 

2300x1100x1000 

m

3

/h 13600 

14960 

16320 

Air Flow (Nominal) 

cfm 8000 

8800 

9600 

Net Static Pressure (Nominal)     

mm  H

2

O 25 

25 

25 

Net Weight 

Kg. 

255 

300 

330 

Indoor Fan Motor: 

HP 

Speed (Nominal) 

R.P.M 

885 

765 

770 

Full Load Amperage 

Amp. 

6.5 

6.5 

6.5 

Blower Wheel 

Type 

Centrifugal-Belt Drive 

Centrifugal-Belt Drive 

Centrifugal-Belt Drive 

Outdoor Unit 

50Hz 

AVL-240 

AVL-260 

AVL-300 

Casing 

Color 

RAL 7030 

RAL 7030 

RAL 7030 

Dimensions (LxDxH) 

mm 

1700x1660x1000 

1700x1660x1150 

1700x1660x1150 

m

3

/h 34600 

33660 

32640 

Air flow  

cfm 20400 

19800 

19200 

Noise Level  

dba 

72 

72 

72 

Net Weight 

Kg. 

566 

588 

610 

Fittings Type 

Soldering 

Soldering 

Soldering 

Compressor Thermal Protection 

Internal 

Overload 

Overload 

Overload 

Full Load Amperage 

Amp. 

2x22 

22+28 

2x28 

Locked 

Rotor 

Amperage 

Amp. 

2x130 130+150 2x150 

Expansion Device 

  

Expansion valve Expansion 

valve Expansion 

valve 

R22 Kg. 

10+10 

10+11.5 

11.5+11.5 

Refrigerant Charge 

R407C Kg. 

9.5+9.5 

9.5+11 

11+11 

R22 Mineral 

160P 

160P 

160P 

Oil for Compressor 

R407C P.O.E 

160ZE 

160ZE 

160ZE 

Outdoor Fan Motor 

KW 

4x0.66 

4x0.66 

4x0.66 

Speed  

R.P.M 

900 

900 

900 

Motor Full Load Amperage 

Amp. 

4x1 

4x1 

4x1 

 
 
 
 
 
 

Содержание AVL-200

Страница 1: ...Service Manual And Spare Parts List And MODELS AVL 200 AVL 220 AVL 240 AVL 260 AVL 300 AVR 200 AVR 220 AVR 240 AVR 260 AVR 300 50 Hz...

Страница 2: ...DESCRIPTION 03 2 TECHNICAL DATA TABLES 05 3 REFRIGERATION CYCLE DIAGRAM 09 4 AIR FLOW TABLES 10 5 ELECTRICAL WIRING DIAGRAM 12 6 INSTALLATION INSTRUCTIONS 15 7 POWER AND CONTROL INSTALLATION 23 8 TRO...

Страница 3: ...contains information about the optional features offered by the SKY series as well as helpful information for service personnel on split air conditioners electrical wiring diagrams refrigeration cycl...

Страница 4: ...z A C power supply for example 380 3 50 380V 3 Phase 50 Hz COS Power factor for the unit FUSE Required fuse size Amp REFRIGERANT R 22 Quantity of refrigerant charge Gr COMPRESSOR Type and catalog numb...

Страница 5: ...ntrol Auto Temperature Control Microcomputer Microcomputer Indoor Unit 50Hz AVL 200 AVL 220 Casing Color RAL 7032 RAL 7032 Air Filter 1 Removable Washable 1 Removable Washable Dimensions LxDxH mm 2050...

Страница 6: ...ature Control Microcomputer Microcomputer Microcomputer Indoor Unit 50Hz AVL 240 AVL 260 AVL 300 Casing Color RAL 7032 RAL 7032 RAL 7032 Air Filter 1 Removable Washable 1 Removable Washable 1 Removabl...

Страница 7: ...00 930 Color RAL 7032 RAL 7032 Time Delay Fuse Amp 3xC63 3xC63 Control Mode I R Remote Control Auto I R Remote Control Auto Temperature Control Microcomputer Microcomputer Evaporator Side Air Filter 1...

Страница 8: ...AL 7032 Time Delay Fuse Amp 3xC63 3xC63 3xC63 Control Mode I R Remote Control Auto I R Remote Control Auto I R Remote Control Auto Temperature Control Microcomputer Microcomputer Microcomputer Evapora...

Страница 9: ...SKY 9 4 Refrigeration Cycle...

Страница 10: ...0 2 26 835 1 96 770 1 67 6400 10880 910 2 32 850 2 02 780 1 72 6720 11424 915 2 57 850 2 25 780 1 94 7040 11968 5 2 Air flow AVL R 220 EXTERNAL STATIC PRESSURE Pa in wg AIR FLOW 300 1 2 250 1 200 0 8...

Страница 11: ...8 150 0 6 rpm kw rpm kw rpm kw rpm kw CFM M3 H 940 3 11 770 2 62 720 2 25 660 1 90 7920 13464 810 3 06 760 2 67 710 2 30 650 1 95 8360 14212 820 3 24 770 2 85 715 2 47 660 2 10 8800 14960 820 3 44 775...

Страница 12: ...SKY 12 6 Electrical Wiring Diagram...

Страница 13: ...SKY 13...

Страница 14: ...SKY 14 NOTES...

Страница 15: ...ure The installation must be performed in accordance with manufacturer s specifications using only approved tubing original cables and original accessories 6 2 Lifting the Units Handle the units with...

Страница 16: ...a single length power cable without extensions For 3 Phase connections use 8 wire inter unit cables NOTE The compressor is equipped with oil heating element Main circuit breaker and power supply must...

Страница 17: ...venient access for service and maintenance purposes Protect the unit from any heat source such as direct sun rays Prevent from any dust or strong wind installation sites Position the unit in such a wa...

Страница 18: ...AIR INTAKE GRILL CEILING 2 min CONNECTION 6 6 Installing the Indoor Unit Distance Model a mm b mm c mm d mm AVL 200 700 1000 1000 1000 AVL 220 700 1000 1000 1000 AVL 240 800 1000 1000 1000 AVL 260 800...

Страница 19: ...r rubber absorbtion cushions on the four corners of the base as shown in the figure Attach the unit to the ceiling using the long anchor screws as shown in the figure 6 7 Air Duct Installation The air...

Страница 20: ...avoid links or flattening of the tubing Bend tubing with special bending tools to avoid the formation of sharp bends Keep the tubing free of dirt sand moisture and other contaminants to avoid damagin...

Страница 21: ...ding to the table for each meter of tubing used If the tubing is shorter than eight meters release gas from the system through the service valve into a recycling device Close the service port caps on...

Страница 22: ...SKY 22 NOTES...

Страница 23: ...t least 50 mm away from high voltage cables 230 or 400 Volts Avoid also proximity to communication cables or RF interference The use of shielded cables is recommended in such locations 7 2 Installing...

Страница 24: ...ing the clamps Make sure that all screws and wires are properly fastened Loose wires or connections can cause damage and present a fire hazard Reassemble the side cover 7 3 1 Outdoor Unit Terminal Box...

Страница 25: ...T2 T3 N N 17 E F L2 L2 L3 L3 L1 L1 14 15 16 14 16 N T1 T2 T3 T4 N N 17 E F L2 L2 L3 L3 FROM OUTDOOR UNIT On Off Mode Fan L1 L1 14 15 16 14 16 N T1 T2 T3 T4 N N 17 E F L2 L2 L3 L3 20 10 9 8 7 6 5 4 3...

Страница 26: ...erials Fasten tubes to the outside wall Seal the hole through which the cables and tubing are passing Connect the air conditioner to the power source Check all air conditioning operating modes Consult...

Страница 27: ...tton on R C 4 Make sure that noting blocking the R C transmission to the A C display 5 Repair or replace wall socket 2 Only indoor fan ventilator works although cooling or heating is desired 1 The sel...

Страница 28: ...r fan motor is blocked or turns slowly 2 Loose or broken V belt 3 Indoor fan motor winding is burnt 4 In Heat mode delayed start for indoor fan motor 5 Clogged air filters 1 Check voltage Repair wirin...

Страница 29: ...running at all 1 Power supply failure 2 Fan motor relays failure 3 Fan contactor failure 4 Motor winding failure check resistance 1 Check power supply 2 Replace faulty relays 3 Replace faulty contact...

Страница 30: ...defective 8 Service valves are not fully open 1 Charge refrigerant gas 2 Recharge gas 3 Repair leakage 4 Replace strainer 5 Replace 4 Way valve 6 Replace solenoid 7 Replace compressor 8 Open the valve...

Страница 31: ...ully open 1 Charge refrigerant gas 2 Recharge gas 3 Repair leakage 4 Replace strainer 5 Replace 4 Way valve 6 Replace solenoid 7 Replace compressor 8 Open the valves full 2 Air circulation failure Air...

Страница 32: ...SKY 32 NOTES...

Страница 33: ...05010312 Condenser Heat Exchanger Right 11 050104E0R 05010312R 05010312R Condenser Heat Exchanger Left 12 Electrical Components Part No AVL R 240 AVL R 220 AVL R 200 Part Description No 405Z063 405Z06...