background image

DANGER

HIGH VOLTAGE

C

AUTION

C

AUTION

C

AUTION

Dangerous Voltages Inside !

No user serviceable parts inside

Do not remove covers

Dangerous internal voltages exceeding 

380 Volts

 

- DO NOT REMOVE COVERS !

Equipment must be installed & serviced 

by suitably qualified service personnel in 

a restricted access area.

TPS13-3.5DC_RevB.pdf

www.tacpower.com.au

General

The TPS-13-3.5A power supply is designed for 

ITE and indoor use only

TPS13-3.5DC model is Dual Channel Switch Mode power supply providing 13.5Vdc at 3.5A continuous load current.  

When operating from mains,  these models provide an output of 13.5Vdc ( to power connected equipment) and are configured with a 
separate  battery charging channel. Available battery charge current is 300mA @ 13.5Vdc (total supply output current 3.8A )

Output short-circuit and overload protection are provided .  Removal of the fault / short circuit condition  will return the power supply 
to normal operation ( Auto-Reset ).

The TPS13-3.5DC power supply has been tested to AS/NZS60950.1:2015 electrical saftey and AS/NZSCISPR32:2015 Class B EMC in Australia 
by Austest Laboratories which is a NATA accredited laboratory. A certificate of compliance has been issued by SAA Approvals, Certificate 
of  Compliance SAA203368-EA.

Metal  Cabinet  Variants

TPS13-3.5DC

   

Single 3.5A battery charger, supply only - no cabinet  (225L x 120W  x 60H ) 

TPS-SMALL KIT

 

Small steel enclosure ( 250W x 310H x 100D mm ) will house 12V 7AH SLA Battery and 1 PDM

TPS-MEDIUM KIT

 

Medium steel enclosure ( 340W x 436H x 145D mm ) will house 12V 17AH SLA Battery and 2 PDM

TPS-LARGE KIT 

Large steel enclosure ( 480W x 470H x 185D mm ) will house 12V 55AH SLA Battery and 2PDM

All enclosures are supplied with mounitng hardware, tamper switches and battery leads.

Connection

 Single Output Models

10-way removable terminal block provides the following: 
( S

ee over the page for a layout  

)

* 13.5Vdc Output
* 13.5Vdc Charger for SLA (Sealed Lead Acid) Batteries
* AC OK  Relay Output 

(Relay is NC when mains is OK)

* Battery Fault / Low Battery Relay Output ( SPDT )

  (This relay is NO when Battery is OK, going NC when Battery  

voltage drops below approx. 10.5V during AC Fail)

Caution when handling batteries:

Exercise care when terminating and connecting batteries. Mishandling or short circuit of SLA batteries can cause severe damage and fire.

Отзывы: